
C ontents
User Interface ...............................................................................3
Main screen, Keyboard, Status, Alarm, Login, Start, Parameters,
I/O display, I/O Config, Service, Language, About ........................ 3
Regulation set point ................................................................................ 3
Parameters ...................................................................................8
SetUp: ...........................................................................................8
Parameter: y01, y03, y07,Cid ................................................................ 8
Buzzer and relay ..........................................................................9
Parameter: BUZ, Adl, AOF ..................................................................... 9
Serial setting ................................................................................9
Parameter: Cid, Ser, bAU, COM ............................................................ 9
Password ......................................................................................9
Parameter: L01, L02, L03 ........................................................................ 9
Unit Configuration .....................................................................10
Parameter: H06, H40, HEA ...................................................................10
Temperature Control .................................................................11
Parameter: rEG, rET, Sc1, rC1, SH1, rH1, SdC, SdH, rin, SOE, SOO
11
Maximum number of compressor starts per hour: .................13
Parameter: CT0, CT1, CT2, CT3, CT4, CT5, CT6, CT7 ...................13
Inverter compressor ..................................................................14
Parameter: IV0, IV1, IV2, IV4, IV5 ........................................................14
Pump for the internal coil: ........................................................15
Parameter: P01, P02, AFr ......................................................................15
Valve in the liquid line ...............................................................16
Parameter: Pd1, Pd2, Pd3, Pd4............................................................16
Reversing cycle valve (4-way valve): ........................................17
Parameter: rE1 ..........................................................................................17
Compressor’s status ...............................................................................17
Defrost: .......................................................................................18
Parameter: d01, d02, d09, d10, d13, d14, d15, d16, d20, d21 18
Stepper motor valve setting for SuperHeat control: ..............19
Parameter: EEN, bAt, v10, EV0, EV1, EV2, EV3, EV4, EV5, EV6,
EV7, EV8, EV9 ........................................................................................... 19
SuperHeat control:: ...................................................................20
Parameter: SH0, N22, N10, N09, N19, N04, N20, N05, N11, N18,
N32, N17, N15, N21, o30 ...................................................................... 20
External coil ...............................................................................22
Parameter: F01, F02, FCS, FCD, FCi, FCd, FHS, FHD, FHi, FHd, .22
Stepless regulation of the fan: .................................................23
Parameter: F11, F12, F13 .....................................................................23
Heaters: ......................................................................................24
Parameter: HE1, HE2, HE3, HE4, HE5 ................................................24
ICE alarm: ...................................................................................25
Parameter: AIT, AID, AIA ........................................................................25
High pressure alarm: .................................................................26
Parameter: HPE, HPS, HPD ...................................................................26
Pressure alarms from analogue input:.....................................27
Parameter: Alr, AL1, LPC, ALE, LPS, LPD ..........................................27
Compressor high temperature alarms: ...................................28
Parameter: HT0, HT1, HT2 ....................................................................28
How to log data into SD card: ...................................................28
Parameter: SDL ........................................................................................28
Status variables: ........................................................................32
Software status: ....................................................................................... 32
Status: V01,…,V08, …, V11, …,V20, V22, V24, V26, V28, V29,V31,
V34, …, V37,…, V40,V43, V44,V53, …,V57, V59, …, V61, V65,
V67, V68, V72, V75, V81,…, V83, V85 C01,…, C04 ........................ 32
Preparatory, see
MCX Shape user guide: DKRCC.PS.RJ0.E3.02
MCXDesign manual: DKRCC.PS.RI0.Y3.02
2 RS8KB102 © Danfoss 2018-06 Visual Chiller

User Interface
Main screen, Keyboard, Status, Alarm, Login, Start,
Parameters, I/O display, I/O Config, Service, Language,
About
The user interface has been developed for LCD displays.
Note: playing with MCXShape, it is very easy to customize
the structure and the visibility of the menu: so the following
indication cannot match with all the compiled software
Main screen
Keyboard
Regulation set point
: Scroll UP, increase a value
: 3s when in main screen: toggle ON/OFF
: Scroll down, decrease a value
: 3s when in main screen: toggle Heat/Cool mode
: exit and save,
: when in main screen: access the active alarm list
: 3s when in Alarm screen: manual reset
The LEFT and RIGHT keys, if present, allow you to move the cursor to the desired option
Visual Chiller RS8KB102 © Danfoss 2018-06 3

Menu Screen: Status
Menu: Alarm Each alarm is described through an alarm description (for LCD display only), an alarm code and
the time since its activation in the format hours:minutes:seconds (seconds for LCD display only).
Note: You can also access alarm visualization by pressing the ESC key from the main screen.
The alarm is only reset if the alarm has ended and it will return you to the main screen.
Note: Alarms can also be reset by pressing ESC for 3 seconds on the alarm screens
Menu: Login Parameters and Menu are organized into 4 access levels. Levels from 1 to 3 are linked to a password.
Elements cannot be accessed when they are on a higher level than the entry level. The level of each
parameter and menu is defined with MCXShape
• Level 0 is accessible without password
• Levels 1-3 are linked to a password (Check parameters L01, L02 and L03)
• Level 4 is not linked to a password, which can be used to make a menu or parameters
never accessible.
You can log in from the menu:
if the password provided is not correct you remain on the login screen. Otherwise you return to the
main menu.
Menu: Start
4 RS8KB102 © Danfoss 2018-06 Visual Chiller

Menu: Parameter This menu contains all the parameters.
The meanings of the parameters are explained in the last part of this manual
Menu: I/O Display Display input and output values
You have access to three screens showing all the input and output values; each screen shows a group
of 8 I/Os. Use UP and DOWN keys to scroll.
The second and third screens are used with MCX15 and MCX20 only.
The example below shows the first screen.
Menu: I/O Config From the menu I/0 Config it is possible to change the position of all the inputs and outputs used
in the software
Note: “CAL”is the offset to add of the reading, the other items are the ones available in the MCXShape
Visual Chiller RS8KB102 © Danfoss 2018-06 5

Parameters
SetUp:
Parameter: y01, y03, y07,Cid
How to switch ON-OFF and change the application mode from the
parameters.
y01- System ON/OFF O=OFF
1=ON
Together with the digital input ON_On/Off the parameter y01 defines whether the machine is in the
ON or OFF state
The parameter y01 can be also changed from the menu/Start, by Modbus or CANBUS and from the
start screen by holding the up-arrow key.
Below the logic that manages the ON-OFF status, the ON status is always delayed by 3 seconds from
the power ON
y03- System heat/cool O=Cool
1=Heat
Together with the digital input DHC_Heat/Cool, the parameter y03 defines whether the machine is in
Cool or Heat mode:
The digital input DHC_Heat/Cool is without predefined meaning, each time that it’ s switched, the
parameter y03 is automatically changed.
Note: It works for H40<> 0
y07- Restore default
parameters
Cid – Serial address (CAN) It defines the ID in the CANBUS communication
0=No means no action
1=Yes means that the default parameters (the ones used in the MCXShape) are loaded
Note: after the restore parameters process, the parameter y07 will be reset to zero
Note: the baud rate and the settings of the CANBUS communication are tuned through the bios
menu or through the MYK
8 RS8KB102 © Danfoss 2018-06 Visual Chiller

Buzzer and relay
Parameter: BUZ, Adl, AOF
How to set it up.
BUZ- Buzzer activation time
number
Adl- Alarm relay activation
delay
AOF- Alarm relay active if unit
in off
It is in minutes. It defines the maximum time that the buzzer can work;
BUZ=15 means that there is no limit to the active time of buzzer
It is in seconds. It defines the delay of the alarm relay when there is an alarm
It defines whether the alarm relay works in OFF state of the chiller
Serial setting
Parameter: Cid, Ser, bAU, COM
How to configure the communication port.
SEr – Serial address (Modbus) Defines the ID in the Modbus communication
bAU – Serial baud rate
(Modbus)
COM – Serial settings
(Modbus)
Defines the baud rate in the Modbus communication
0 means Reserved: do not use
1 means 1200 bits/sec
2 means 4200 bits/sec
3 means 4800 bits/sec
4 means 9600 bits/sec
5 means 14400 bits/sec
6 means 19200 bits/sec
5 means 28800 bits/sec
8 means 38400 bits/sec
9 means 57600 bits/sec
8 means 115200 bits/sec
Defines the serial settings of the Modbus communication
0 means 8N1
1 means 8E2
2 means 8N2
Password
Parameter: L01, L02, L03
How to change the password
L01, L02, L03-
Level x password
Visual Chiller RS8KB102 © Danfoss 2018-06 9
Typing the parameter L0x, in the login screen, you will be able to see all the parameters and menu
with level <= of X;
The level of access is highlighted in the yellow square;

Unit Configuration
Parameter: H06, H40, HEA
General setting of the fridge circuit
Digital input: C11, C21
Digital output: C11, C21, HC1, HEA
Analogue output: CI1
H06 – Number of compressors
per circuit
H40 – Heat pump type 0=No means that the software doesn’t perform the heating mode
HEA – Enable Heater 0=No means that the heater is not used
It defines the number of compressors in the circuit;
Note: the software manages only one circuit
1=GAS means that the software performs the heating mode, the internal coil acts as evaporator in
cooling mode and condenser in heating mode
1=H2O means that the software performs the heating mode, the coils keep the same function in
both heating and cooling mode
Note: one digital output “HC1_Reverse Valve C1” is reserved for controlling the reverse flow valve
1=Heat the heater is managed by parameters HE1 end HE2
2=Defrost the heater works only during defrost and is managed by parameters HE3 end HE4
3=Both the heater works like HEA=1 and HEA=2
10 RS8KB102 © Danfoss 2018-06 Visual Chiller

Temperature Control
Parameter: rEG, rET, Sc1, rC1, SH1, rH1, SdC, SdH, Rin,
SOE, SOO
Digital input: SE2
Analogue input: Tin, TOE, SOV
rEG – Analogue input for
temperature regulation
rET – Regulation Type It defines the relation between the temperature gap and the power request to the circuits.
SC1- Cooling temperature
set point
rC1- Cooling temperature
differential.
SH1- heating temperature set
point
rH1- Heating temperature
differential.
Rin- Ti
SdC- Offset for set point in
cooling
SdH- Offset for set point in
heating
0= Tin : reference sensor is Tin_Tin Evaporator
1= TOUT : reference sensor is TOE_Tout Evaporator
0=P : Power request to the circuits increases proportionally with the regulation error, it is 100% when
the regulation error (the gap between set point and the reference sensor ) is equal to rC1 (rH1)
1=PI : the power request is the sum of P regulation (rET=0) more a component (Integral part) that
increases time by time in relation to the regulation error; the speed of the Integral part depends on
the parameter Rin.
In the PI regulation the balance is reached only when the regulation sensor gets to the set point.
It defines the set point in cooling mode
See parameter rET
It defines the set point in heating mode
See parameter rET
It is the integral time of the PI regulation, the bigger the value of Rin slower is the action of the Integral
part.
See parameter rET
In economy status and cooling mode the regulation set point is shift of SdC.
Note: the digital input SE2_Second set point defines if use comfort set point (SC1 or SH1) or the
economy set point (SC1+SdC or SH1-SdH);
In economy status and heating mode the regulation set point is shift of SdH.
Note: the digital input SE2_Second set point defines whether the comfort set point (SC1 or SH1)
or the economy set point (SC1+SdC or SH1-SdH) is used;
Visual Chiller RS8KB102 © Danfoss 2018-06 11