Data Sheet
VHX Valve Sets with RTX Temperature Limiter
for Designer Radiators & Bathroom Towel Rails
Application
VHX floor connection VHX wall connection
Ordering
The VHX-sets are specially designed for towel
rails and designer radiators with '50 mm bottom
connection' and ½” connection to the radiator.
The VHX-sets include a RTX temperature limiter
for regulation of the return flow temperature.
VHX valves controls the return flow from the radiator and have several features:
free choice of left/right mounting direction
▪
available in versions for floor or wall connec-
▪
tion
VHX set
Description Colour
VHX-DUO valve set, with RTX return flow sensor
VHX-MONO valve set, with RTX return flow sensor
Compression fittings
Description Size
For steel and copper tubes
For AluPex tubes
For Pex tubes
built-in shut-off function
▪
four different surfaces matching most radia-
▪
tors
The VHX sets provides the perfect finishing touch
for towel rails. The aesthetically pleasing and
compact design allows the sensor to be mounted
underneath the towel rail, parallel with the wall.
Chrome 013G4376 013G4379
RAL 9016 013G4378 013G4381
Chrome 013G4382 013G4385
RAL 9016 013G4384 013G4387
8 mm 013G4108 –
10 mm 013G4110 013G4192
12 mm 013G4112 013G4193
14 mm 013G4114 013G4194
15 mm 013G4115 013G4195
16 mm 013G4116 013G4196
12 x 2 mm 013G4172 –
14 x 2 mm 013G4174 –
16 x 2 mm 013G4176 013G4200
12 x 1.1 mm 013G4143 013G4197
12 x 2 mm 013G4142 –
14 x 2 mm 013G4144 –
15 x 2.5 mm 013G4147 013G4199
16 x 2 mm 013G4146 013G4198
Code no.
Straight
Code no.
Nickel plated
Code no.
Angle
Code no.
Chrome plated
Danfoss Heating Solutions VDUYN402 © Danfoss 10/2011 1
min. 20 30 40 50 max. °C
0 I⊳ 1 2 3 4 uI
min. 15 25 35 45 max. °C
Data Sheet
VHX Valve Sets with RTX Temperature Limiter for Designer Radiators & Bathroom Towel Rails
Accessories
Technical Data
Product Code no.
Electric heating element - 47 cm - 300 W - 1.2 m w/ Schuko plug
Electric heating element - 40 cm - 150 W - 1.2 m w/ Schuko plug
Electric heating element - 70 cm - 600 W - 1.2 m w/ Schuko plug
Adapter for electric heating element 013G4166
O-ring service set for VHX MONO angle valve and VHX DUO angle valve
O-ring service set for VHX DUO straight valve 013G4180
O-ring service set for VHX MONO straight valve 013G4181
1)
Electric heating elements are according to the standard UNEL 47168/68-CEE (7) xvll.
2)
Complete O-ring replacement of VHX DUO angle valve requires 2 x 013G4179.
Type
VHX-DUO G½A G½
VHXMONO
Max. work. pressure: 10 bar, max. diff. pressure2): 0,6 bar, test pressure 16 bar, max. flow temp.: 120 °C
1)
The kv-value indicates the water flow (Q) in m³/h at a pressure drop (Δp) across the valve of 1 bar; . The kvs-
value states the flow Q at a maximum lift, i.e. at fully open valve at setting N.
2)
The maximum differential pressure specified is the maximum pressure at which the valves give satisfactory regulation. As with any device which imposes a pressure drop in the system, noise may occur under certain flow/pressure
conditions. The differential pressure can be reduced by the use of the Danfoss differential pressure regulators.
Connection
Rad. Sys. 1 2 3 4 5 6 7 N N
G½A G½
P-band
2K 0.12 0.14 0.16 0.17 0.18 0.19 0.20 0.21
5K 0.16 0.19 0.22 0.25 0.29 0.33 0.37 0.41
2K 0.12 0.14 0.16 0.17 0.18 0.19 0.20 0.21
5K 0.16 0.19 0.22 0.25 0.29 0.33 0.37 0.41
kv-values [m³/h] with RAX sensor at setting
1)
1)
1)
2)
013G4167
013G4168
013G4169
013G4179
1)
(kvs)
0.56
0.45
Temperature Setting
Pre-Setting
RTX has - due to its mode of operation - a very
limited influence on the hydraulic balance of the
Changing the kv-setting from "N" (factory setting)
is therefore seldom required.
heating system.
At position 0 the valve is totally closed, i.e. the frost protection is off.
Danfoss pre-settable valve assemblies incorporate easy setting adjustment with clearly engraved setting markers scaled from 1 - 7 and N.
Setting values can be set quickly and precisely, without the need for
tools, as follows:
Remove protective cap or sensor.
▪
Turn Red ring to the desired setting value.
▪
The preset level can be selected in 0.5 increments between 1 and 7
(see chart for flow rates). At setting N the valve is fully open (flushing
option).
2 VDUYN402 © Danfoss 10/2011 Danfoss Heating Solutions