Danfoss VHX-DUO, VHX-MONO Data sheet

Data Sheet

VHX Valve Sets with RTX Temperature Limiter for Designer Radiators & Bathroom Towel Rails

Application

VHX floor connection

VHX wall connection

The VHX-sets are specially designed for towel rails and designer radiators with '50 mm bottom connection' and ½” connection to the radiator. The VHX-sets include a RTX temperature limiter for regulation of the return flow temperature.

VHX valves controls the return flow from the radiator and have several features:

free choice of left/right mounting direction

available in versions for floor or wall connection

built-in shut-off function

four different surfaces matching most radiators

The VHX sets provides the perfect finishing touch for towel rails. The aesthetically pleasing and compact design allows the sensor to be mounted underneath the towel rail, parallel with the wall.

Ordering

VHX set

 

 

 

 

Description

Colour

Code no.

Code no.

 

Straight

Angle

 

 

 

 

 

 

 

 

 

VHX-DUO valve set, with RTX return flow sensor

Chrome

013G4376

013G4379

 

 

 

 

 

RAL 9016

013G4378

013G4381

 

 

 

 

 

 

 

 

VHX-MONO valve set, with RTX return flow sensor

Chrome

013G4382

013G4385

 

 

 

 

 

RAL 9016

013G4384

013G4387

 

 

 

 

 

 

 

Compression fittings

Description

Size

Code no.

Code no.

Nickel plated

Chrome plated

 

 

 

 

 

 

 

8 mm

013G4108

 

 

 

 

 

10 mm

013G4110

013G4192

 

 

 

 

For steel and copper tubes

12 mm

013G4112

013G4193

 

 

 

14 mm

013G4114

013G4194

 

 

 

 

 

 

15 mm

013G4115

013G4195

 

 

 

 

 

16 mm

013G4116

013G4196

 

 

 

 

 

12 x 2 mm

013G4172

 

 

 

 

For AluPex tubes

14 x 2 mm

013G4174

 

 

 

 

 

16 x 2 mm

013G4176

013G4200

 

 

 

 

 

12 x 1.1 mm

013G4143

013G4197

 

 

 

 

 

12 x 2 mm

013G4142

 

 

 

 

For Pex tubes

14 x 2 mm

013G4144

 

 

 

 

 

15 x 2.5 mm

013G4147

013G4199

 

 

 

 

 

16 x 2 mm

013G4146

013G4198

 

 

 

 

Danfoss Heating Solutions

VDUYN402

© Danfoss

10/2011

1

Danfoss VHX-DUO, VHX-MONO Data sheet

Data Sheet

VHX Valve Sets with RTX Temperature Limiter for Designer Radiators & Bathroom Towel Rails

 

 

 

 

 

Accessories

 

 

 

Product

 

Code no.

 

 

 

 

 

Electric heating element - 47 cm - 300 W - 1.2 m w/ Schuko plug 1)

 

013G4167

 

Electric heating element - 40 cm - 150 W - 1.2 m w/ Schuko plug 1)

 

013G4168

 

Electric heating element - 70 cm - 600 W - 1.2 m w/ Schuko plug 1)

 

013G4169

 

Adapter for electric heating element

 

013G4166

 

 

 

 

 

O-ring service set for VHX MONO angle valve and VHX DUO angle valve 2)

 

013G4179

 

O-ring service set for VHX DUO straight valve

 

013G4180

 

 

 

 

 

O-ring service set for VHX MONO straight valve

 

013G4181

 

 

 

 

Technical Data

Temperature Setting

Pre-Setting

1)Electric heating elements are according to the standard UNEL 47168/68-CEE (7) xvll.

2)Complete O-ring replacement of VHX DUO angle valve requires 2 x 013G4179.

Type

Connection

P-band

 

kv-values [m³/h] with RAX sensor at setting1)

 

(kvs)

Rad.

Sys.

1

 

2

3

4

5

6

7

N

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VHX-DUO

G½A

2K

0.12

 

0.14

0.16

0.17

0.18

0.19

0.20

0.21

0.56

 

 

 

 

 

 

 

 

 

 

5K

0.16

 

0.19

0.22

0.25

0.29

0.33

0.37

0.41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VHX-

G½A

2K

0.12

 

0.14

0.16

0.17

0.18

0.19

0.20

0.21

0.45

MONO

5K

0.16

 

0.19

0.22

0.25

0.29

0.33

0.37

0.41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. work. pressure: 10 bar, max. diff. pressure2): 0,6 bar, test pressure 16 bar, max. flow temp.: 120 °C

 

1)

 

 

 

 

 

 

 

 

 

 

 

 

 

The kv-value indicates the water flow (Q) in m³/h at a pressure drop (Δp) across the valve of 1 bar;

. The kvs-

value states the flow Q at a maximum lift, i.e. at fully open valve at setting N.

2)The maximum differential pressure specified is the maximum pressure at which the valves give satisfactory regulation. As with any device which imposes a pressure drop in the system, noise may occur under certain flow/pressure conditions. The differential pressure can be reduced by the use of the Danfoss differential pressure regulators.

RTX has - due to its mode of operation - a very

Changing the kv-setting from "N" (factory setting)

limited influence on the hydraulic balance of the

is therefore seldom required.

heating system.

 

XP = 0 K

min.

20

30

40

50

max.

°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

I

1

2

3

4

I

 

 

 

 

 

 

 

 

 

 

XP = 5 K

min.

15

25

35

45

max.

°C

 

 

 

 

 

 

 

At position 0 the valve is totally closed, i.e. the frost protection is off.

Danfoss pre-settable valve assemblies incorporate easy setting adjustment with clearly engraved setting markers scaled from 1 - 7 and N. Setting values can be set quickly and precisely, without the need for tools, as follows:

Remove protective cap or sensor.

Turn Red ring to the desired setting value.

The preset level can be selected in 0.5 increments between 1 and 7 (see chart for flow rates). At setting N the valve is fully open (flushing option).

2

VDUYN402

© Danfoss

10/2011

Danfoss Heating Solutions

Loading...
+ 2 hidden pages