VHX Valve Sets with RAX Thermostatic Sensor
for Designer Radiators & Bathroom Towel Rails
Application
VHX floor connectionVHX wall connection
Ordering
The VHX-sets are specially designed for towel
rails and designer radiators with '50 mm bottom
connection' and ½” connection to the radiator.
The VHX-sets include a RAX thermostatic sensor
for room temperature regulation.
The sets provides the perfect finishing touch for
towel rails. The aesthetically pleasing and compact design allows the sensor to be mounted under-neath the towel rail, parallel with the wall.
VHX set
DescriptionColour
VHX-DUO valve set, with RAX room sensor
VHX-MONO valve set, with RAX room sensor
VHX valves controls the return flow from the radiator and have several features:
Max. work. pressure: 10 bar, max. diff. pressure2): 0,6 bar, test pressure 16 bar, max. flow temp.: 120 °C
1)
The kv-value indicates the water flow (Q) in m³/h at a pressure drop (Δp) across the valve of 1 bar;
. At setting N the kv-value is stated according to EN 215, at XP = 2K i.e. the valve is closed at 2°C
higher room temperature. At lower settings the XP value is reduced to 0.5K of the setting value 1. The
kvs-value states the flow Q at a maximum lift, i.e. at fully open valve at setting N.
2)
The maximum differential pressure specified is the maximum pressure at which the valves give satisfactory regulation. As with any device which imposes a pressure drop in the system, noise may occur
under certain flow/pressure conditions. The differential pressure can be reduced by the use of the Danfoss differential pressure regulators.
VHX Valve Sets with RAX Thermostatic Sensor for Designer Radiators & Bathroom Towel Rails
Temperature Setting
Presetting
RAX thermostatic sensor
0= Positive shut off
= Frost protection setting
Danfoss pre-settable valve assemblies incorporate easy setting adjustment with clearly engraved setting markers scaled from 1 - 7 and N.
Setting values can be set quickly and precisely,
without the need for tools, as follows:
Remove protective cap or sensor.
▪
Turn red ring to the desired setting value.
▪
The preset level can be selected in 0.5 increments
between 1 and 7 (see chart for flow rates). At setting N the valve is fully open (flushing option).
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective
companies. Danfoss Heating Solutions and the Danfoss Heating Solutions logotype are trademarks of Danfoss A/S. All rights reserved.