Datasheet
Desired Event 1
temperature
Degrees below the desired
temperature at the beginning
of the Optimum Start Period
Available Start-Up Periods
With a -2°C deviation and the 30 min. curve selected the
heating plant will switch on 15 min. before the Event 1 time.
-1°C
-2°C
-3°C
-4°C
120
min.90min.60min.30min.
Event 1
time (0)
Selecting 0
effectively
disables the
OSC function.
TP7001 Series Programmable Room
Thermostats
Features
TP7001 series offers several advanced features
which can be selected by the installer at the time
of installation, these include:
• Optimum start control : This feature uses internal
temperature to calculate the time in advance
of the programmed time that the system must
switch on in order to ensure that programmed
temperature is achieved by the programmed
time.
• Chrono-proportional control: This feature denes
the boiler cycle rate and the on/o times of the
boiler within the cycle. This adds to comfort
and improves boiler eciency, particularly with
condensing type boilers.
• Delayed Start: This feature enables you to hold
o the heating for some time during mild days
The TP7001 series combines the functions of a
time clock and room thermostat into a stylish,
easy to use controller with a large backlit display,
which allows the user to programme different
temperatures at different times of the day to
match lifestyle demands. The TP7001 oers true
7-day programming, allowing each day to be
set dierently if so required. In addition, the unit
can be set to 5/2-day mode allowing one set
of programmes to be used for weekdays with a
dierent set being available for the weekends.
TP7001 series oers up to six temperature changes
each day and includes the option of programming
an “O”.
where the room temperature at the start of the
event is close to the programmed temperature.
The range includes battery and mains powered
versions in both built-in and remote sensor types,
please refer to the data table for details and
ordering codes.
• 7-day or 5/2 day programming options
• Up to 6 time and temperature events per day
• Hard wired versions available for battery and
mains operation
• Holiday programming mode and thermostat
mode
• Many user overrides including programme
extension
Installer Settings DIL Switches
Installer Settings Optimum Start Control
© Danfoss HS | 09/2015 | 049v02 VDHSC202
SW. No
SW.1
SW.2
Keyboard Disabled
Reset Disabled
OFF
If the TP7001 has been set to Optimum start control
enabled, the Optimum start control setting must
be made within the user advanced programming
mode. The graph to the right shows the calculated
time before the programmed time that the rst
event of the day will commence, dependant
upon the difference in room temperature and
the programmed temperature for the rst event.
Setting options are 0:00, (OSC disabled, 0:15, 0:30,
0:45, 1:00, 1:15, 1:30, 1,45 or 2:00).
ON
Keyboard Enabled
Reset Enabled
1
Datasheet TP7001 Series - Programmable Room Thermostats
1
2
3
4
b
C
d
S COM
Room/outdoor/limit
sensor or contact
5
6
7
HTG
OFF
HTG
COM
HTG
ON
Thermostat Specication
ErP Class
Product
Class
Thermostat Features TP7001 TP7001A TP7001M TP7001MA
Built-in sensor Remote sensor Built-in sensor Remote sensor
Default Time Zone CET +1 CET +1 CET +1 CET +1
Order codes 087N8007 087N8013 087N8008 087N8014
Control type - On/O or Chrono-proportional,
3/6/9/12 cycles per hour
Hard wired thermostat • •
Digital clock type 24 hour (can be set to AM/PM mode by user)
Selectable 24 hour, 5/2 day, A/B day
or 7 day operation
Number of events per day Up to 6
Control temperature range O, 5-30°C (can be set to Fahrenheit by user)
Total switching dierential (On/O mode) 0.1°C
Factory pre-set programme Yes
Programmable holiday mode Yes, up to a year
Installer selectable
optimum start control
Thermostat mode and frost mode Yes, set to 5.0°C, but adjustable between 5-30°C
Power supply
Memory back-up
Switching action of output relay SPDT
Switch rating of relay contact, voltage and current 3 (1) A, 10-230 Vac
Dimensions (mm) 140 wide x 91 high x 28 deep
Pollution situation Degree 2
Rated impulse voltage 2.5Kv
Ball pressure test 75°C
Remote Sensor 087N774800
ERP Class
The products represented within this document are classied according to, and allow completion of, the Energy Related Product
(ErP) Directive System Package che and the ErP system data label. ErP Labelling obligation is applicable from 26th September
2015.
ErP Class Product Function and ErP Description Additional eciency gain
TPI Room Thermostat, for use with on/off output heaters
IV
An electronic room thermostat that controls both thermostat cycle rate
and in-cycle on/o ratio of the heater proportional to room temperature.
TPI control strategy reduces mean water temperature, improves room
temperature control accuracy and enhances system eciency.
Yes - O, 0:15, 0:30, 0:45, 1:00, 1:15, 1:30, 1,45 or 2:00 minutes early switch on
2 x AA/MN1500/LR6
alkaline batteries
Capacitor during battery change
for 1 minute
Yes
Yes
at set-point minus 4K
230V, 50 Hz
3V battery (10 year lifetime)
2%
Wiring Details
TP7001 & TP7001A TP7001M & TP7001MA
Room/outdoor/limit
sensor or contact
1
2
b
3
4
d
C
S COM
5
HTG
OFF
6
HTG
COM
7
HTG
ON
Z
Y
X
1
b
X, Y and Z can be connected to
Room/Outdoor/Limit Sensor or contact
3
2
C
4
d
S COM
5
6 7
HTG
COM
HTG
ON
8 9
HTG
OFF
L N
Danfoss Ltd.
Ampthill Road
Bedford MK42 9ER
Tel: 01234 364621
Fax: 01234 219705
Email: ukheating@danfoss.com
Website: www.heating.danfoss.co.uk
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already
on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2
© Danfoss HS | 09/2015 | 049v02 VDHSC202
Power Supply
10