Danfoss TP7001 Data sheet

Datasheet
Desired Event 1 temperature
Degrees below the desired
temperature at the beginning
of the Optimum Start Period
Available Start-Up Periods
With a -2°C deviation and the 30 min. curve selected the
heating plant will switch on 15 min. before the Event 1 time.
-1°C
-2°C
-3°C
-4°C 120
min.90min.60min.30min.
Event 1 time (0)
Selecting 0 effectively disables the OSC function.
TP7001 Series Programmable Room Thermostats
Features
TP7001 series offers several advanced features which can be selected by the installer at the time of installation, these include:
• Optimum start control : This feature uses internal temperature to calculate the time in advance of the programmed time that the system must switch on in order to ensure that programmed temperature is achieved by the programmed time.
• Chrono-proportional control: This feature denes the boiler cycle rate and the on/o times of the boiler within the cycle. This adds to comfort and improves boiler eciency, particularly with condensing type boilers.
• Delayed Start: This feature enables you to hold o the heating for some time during mild days
The TP7001 series combines the functions of a time clock and room thermostat into a stylish, easy to use controller with a large backlit display, which allows the user to programme different temperatures at different times of the day to match lifestyle demands. The TP7001 oers true 7-day programming, allowing each day to be set dierently if so required. In addition, the unit can be set to 5/2-day mode allowing one set of programmes to be used for weekdays with a dierent set being available for the weekends.
TP7001 series oers up to six temperature changes each day and includes the option of programming an “O”.
where the room temperature at the start of the event is close to the programmed temperature.
The range includes battery and mains powered versions in both built-in and remote sensor types, please refer to the data table for details and ordering codes.
• 7-day or 5/2 day programming options
• Up to 6 time and temperature events per day
• Hard wired versions available for battery and mains operation
• Holiday programming mode and thermostat mode
• Many user overrides including programme extension
Installer Settings ­DIL Switches
Installer Settings ­Optimum Start Control
© Danfoss HS | 09/2015 | 049v02 VDHSC202
SW. No
SW.1
SW.2
Keyboard Disabled
Reset Disabled
OFF
If the TP7001 has been set to Optimum start control enabled, the Optimum start control setting must be made within the user advanced programming mode. The graph to the right shows the calculated time before the programmed time that the rst event of the day will commence, dependant upon the difference in room temperature and the programmed temperature for the rst event. Setting options are 0:00, (OSC disabled, 0:15, 0:30, 0:45, 1:00, 1:15, 1:30, 1,45 or 2:00).
ON
Keyboard Enabled
Reset Enabled
1
Datasheet TP7001 Series - Programmable Room Thermostats
1
2
3
4
b
C
d
S COM
Room/outdoor/limit
sensor or contact
5
6
7
HTG OFF
HTG
COM
HTG
ON
ErP
4
Thermostat Specication
ErP Class
Product
Class
Thermostat Features TP7001 TP7001A TP7001M TP7001MA
Built-in sensor Remote sensor Built-in sensor Remote sensor
Default Time Zone CET +1 CET +1 CET +1 CET +1
Order codes 087N8007 087N8013 087N8008 087N8014
Control type - On/O or Chrono-proportional, 3/6/9/12 cycles per hour
Hard wired thermostat
Digital clock type 24 hour (can be set to AM/PM mode by user)
Selectable 24 hour, 5/2 day, A/B day or 7 day operation
Number of events per day Up to 6
Control temperature range O, 5-30°C (can be set to Fahrenheit by user)
Total switching dierential (On/O mode) 0.1°C
Factory pre-set programme Yes
Programmable holiday mode Yes, up to a year
Installer selectable optimum start control
Thermostat mode and frost mode Yes, set to 5.0°C, but adjustable between 5-30°C
Power supply
Memory back-up
Switching action of output relay SPDT
Switch rating of relay contact, voltage and current 3 (1) A, 10-230 Vac
Dimensions (mm) 140 wide x 91 high x 28 deep
Pollution situation Degree 2
Rated impulse voltage 2.5Kv
Ball pressure test 75°C
Remote Sensor 087N774800
ERP Class
The products represented within this document are classied according to, and allow completion of, the Energy Related Product (ErP) Directive System Package che and the ErP system data label. ErP Labelling obligation is applicable from 26th September
2015.
ErP Class Product Function and ErP Description Additional eciency gain
TPI Room Thermostat, for use with on/off output heaters
IV
An electronic room thermostat that controls both thermostat cycle rate and in-cycle on/o ratio of the heater proportional to room temperature. TPI control strategy reduces mean water temperature, improves room temperature control accuracy and enhances system eciency.
Yes - O, 0:15, 0:30, 0:45, 1:00, 1:15, 1:30, 1,45 or 2:00 minutes early switch on
2 x AA/MN1500/LR6
alkaline batteries
Capacitor during battery change
for 1 minute
Yes
Yes
at set-point minus 4K
230V, 50 Hz
3V battery (10 year lifetime)
2%
Wiring Details
TP7001 & TP7001A TP7001M & TP7001MA
Room/outdoor/limit
sensor or contact
1
2
b
3
4
d
C
S COM
5
HTG OFF
6
HTG
COM
7
HTG
ON
Z
Y
X
1
b
X, Y and Z can be connected to Room/Outdoor/Limit Sensor or contact
3
2
C
4
d
S COM
5
6 7
HTG
COM
HTG
ON
8 9
HTG OFF
L N
Danfoss Ltd.
Ampthill Road Bedford MK42 9ER Tel: 01234 364621 Fax: 01234 219705 Email: ukheating@danfoss.com Website: www.heating.danfoss.co.uk
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.