5/2 day programming 7 day programming
Sw
Optimum start controller enabled Optimum start controller disabled
Sw
Chrono-proportional control On/Off control
TP7000, A, B, AB, M, M, MA, RF & A-RF models with 3/6 cycles per hour option
Sw
Chrono-proportional, 6 cycles / hour Chrono-proportional, 3 cycles / hour
TP7000C, CA, CM, CMA, C-RF & CA-RF models with 6/12 cycles per hour option
Sw
Chrono-proportional, 12 cycles / hour Chrono-proportional, 6 cycles / hour
Note: Sw
is only active if Sw3 is set to chrono-proportional mode
Datasheet
TP7000, TP7000-RF and TP7000M
Programmable Room Thermostats
Features
• Optimum start control : This feature uses internal
temperature to calculate the time in advance
of programmed time that the system must
switch on in order to ensure that programmed
temperature is achieved by the programmed
time.
• Chrono-proportional control: This feature denes
the boiler cycle rate and the on/o times of the
boiler within the cycle. This adds to comfort
and improves boiler eciency, particularly with
condensing type boilers.
RF models incorporate a digital FM radio transmitter
which transmits a unique thermostat identity
code which is learnt by the RX receiver during
commissioning. Receivers, which are available in
The TP7000 combines the functions of a time clock
and room thermostat into a stylish, simple to use
controller that allows the user to programme
different temperatures for different times to
match lifestyle demands. The TP7000 oers true
7-day programming, allowing each day to be
set dierently if so required. In addition, the unit
can be set to 5/2-day mode allowing one set
of programmes to be used for weekdays with a
dierent set being available for the weekends.
TP7000 is available in hard wired versions and in
labour saving RF versions. Both hard wired and
RF models oer up to six temperature changes
each day and include the option of programming
an “O”.
TP7000 offers several advanced features which
can be selected by the installer at the time of
installation, these include:
1, 2 & 3 zone versions, can be mounted up to 30
metres from the thermostat and can be used to
switch boilers, pumps or control valves.
The range includes battery and mains powered
versions in both built-in and remote sensor types,
please refer to the data table for details and
ordering codes.
• 7-day or 5/2 day programming options
• Up to 6 time and temperature events per day
• Available in hard wired and RF versions
• Hard wired versions available for battery and
mains operation
• Holiday programming mode and thermostat
mode
• Many user overrides including programme
extension
Installer Settings DIL Switches
© Danfoss HS | 09/2015 | 560v09 VDRGI402
1
Datasheet TP7000 Series - Programmable Room Thermostats
Desired Event 1
temperature
Degrees below the desired
temperature at the beginning
of the Optimum Start Period
Available Start-Up Periods
With a -2°C deviation and the 30 min. curve selected the
heating plant will switch on 15 min. before the Event 1 time.
-1°C
-2°C
-3°C
-4°C
120
min.90min.60min.30min.
Event 1
time (0)
Selecting 0
effectively
disables the
OSC function.
Installer Settings Optimum Start Control
Thermostat Specication
If DIL SW2 has been set to Optimum start control
enabled, the Optimum start control setting must
be made within the user programming mode. The
table below shows the calculated time before the
programmed time that the rst event of the day will
commence, dependant upon the dierence in room
temperature and the programmed temperature
for the rst event. Setting options are 0:00, (OSC
disabled, 0:30, 1:00, 1:30 or 2:00).
Thermostat Features TP7000-RF TP7000 TP7000M
Order code - Built-in Sensor 087N741000 087N741400 087N740000 087N740400 087N740800 087N741900
- Remote Sensor
(A models)
Control type On/O or Chrono-proportional,
3/6 cycles per hour
Control type On/O or Chrono-proportional,
6/12 cycles per hour (C models)
RF - Wireless thermostat •
Hard wired thermostat • •
Digital clock type 24 hour (can be set to AM/PM mode by user)
Selectable 7-day or 5/2-day operation Yes
Number of events per day Up to 6
Control temperature range O, 5-30°C (can be set to Fahrenheit by user)
Total switching dierential
(On/O mode)
Factory pre-set programme Yes
Programmable holiday mode Yes, up to 99 days
Installer selectable
optimum start control
Thermostat mode and frost mode Yes, set to 8.0°C, but adjustable between 5-30°C
Power supply 2 x AA/MN1500/LR6 alkaline batteries 230V, 50 Hz
Memory back-up Capacitor during battery change for 1 minute
Switching action of output relay N/A SPDT
Switch rating of relay contact,
voltage and current
Transmitter frequency (RF models only) 433.92 MHz N/A
Transmitter range (RF models only) 30 metres max. N/A
Dimensions (mm) 138 wide x 88 high x 28 deep
Pollution situation Degree 2
Rated impulse voltage N/A 2.5Kv
Ball pressure test 75°C
Note 1: Unit must be powered up for 6 days to charge cell before full back up is available
087N741100 087N741500 087N740100 087N740500 087N740900 087N742000
• • •
• • •
<1.0°C
Yes - O, 30, 60, 90 or 120 minutes early switch on at set-point minus 4K
Rechargeable cell
(see note 1)
N/A 3 (1) A, 10-230 Vac
Receiver Specication
(RF Models Only)
2
© Danfoss HS | 09/2015 | 560v09 VDRGI402
Receiver Features RX1 RX2 RX3
Order codes 087N747600 087N747700 087N747800
Single channel receiver module,
works in conjunction with one thermostat
Two channel receiver module,
works in conjunction with two thermostats
Three channel receiver module,
works in conjunction with three thermostats
Transmitter code self learning feature • • •
Receiver frequencies 433.92 MHz
Supply voltage 220/240 Vac, 50 Hz
Output relay current rating 3 (1) A
Output relay conguration (commons linked internally) 1 x SPDT
Memory retention Memory retained electronically on power down
Dimensions (mm) 138 wide x 88 high x 32 deep
•
•
1 x SPDT
1 x SPST
•
1 x SPDT
2 x SPST