Danfoss TCI 12 CH-C, TCI 15 CH-C, TCI 25 CH-C, TCI 12 CH, TCI 15 CH Installation guide [da]

...
Instructions
Soft Starters for commercial compressor applications
TCI 12 CH-C/ TCI 15 CH-C/ TCI 25 CH-C
Montering - Mounting - Montage
Afmontering - Dismounting - Demontage
TCI 12 CH/ TCI 15 CH/ TCI 25 CH
047C0447Info for UK customers only:Danfoss Ltd. Oxford Road, UB9 4LH Denham, UK
Mål - Dimensions - Abmessungen
AN00008641045201-000101 ©Danfoss A/S, 12-2020 (AC-SMC, sw) | 1
Soft Starters for commercial compressor applications
TCI 12 CH-C/ TCI 15 CH-C/ TCI 25 CH-C
Forbindelse - Wiring - Verdrahtung
TCI 12 CH/ TCI 15 CH/ TCI 25 CH
*K
*K
* Der skal anvendes en contactor foran softstarteren
* It is mandatory to use contactor in front of the soft starter.
* Dem Softstarter muss ein Schütz vorgeschaltet werden.
Semicontuctor protection fusing TCI 12CH-C/CH TCI 15CH-C/CH TCI 25CH-C/CH
Type 1 1) coordination 35 A gL/gG 50 A gL/gG 63 A gL/gG
Type 2 2) coordination Pt(=10ms) 610 A2s 1800 A2s 6300 A2s
Rating index
AC-58-b: Hermetic refrigerant compressor3) motor with bypass
1)
Type 1 coordination requires that, under short-circuit conditions, the device shall cause no danger to persons or installation and may not be suitable for further use without repair and replacement of parts.
2)
Type 2 coordination requires that, under short-circuit conditions, the device shall cause no danger to persons or installation and shall be suitable for further use.
3)
12A: AC-58b: 6-2:300 means max. load 6 x 12A for 2 sec.: Min. 300 sec.
between starts.
12A:AC-58b: 6-2:300
15A:AC-58b: 6-2:360
25A:AC-58b: 6-2:600
LED status indikering/ LED status indication/ LED Zustandsanzeige
LED
Rampe op Nominel drift Net-eller lastfejl Ramp up Full on Line or load error Ramp-up Nennbetrieb Netz- oder Lastfehler
2 | ©Danfoss A/S, 12-2020 (AC-SMC, sw) AN00008641045201-000101