Soft Starters for commercial compressor applications
TCI 12 CH-C/ TCI 15 CH-C/ TCI 25 CH-C
TCI 12 CH/ TCI 15 CH/ TCI 25 CH
Forbindelse - Wiring - Verdrahtung
*K |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*K |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Semicontuctor protection fusing |
TCI 12CH-C/CH |
TCI 15CH-C/CH |
TCI 25CH-C/CH |
Type 1 1) coordination |
35 A gL/gG |
50 A gL/gG |
63 A gL/gG |
Type 2 2) coordination Pt(=10ms) |
610 A2s |
1800 A2s |
6300 A2s |
Rating index |
|
|
|
AC-58-b: Hermetic refrigerant |
12A:AC-58b: |
15A:AC-58b: |
25A:AC-58b: |
compressor3) motor with bypass |
6-2:300 |
6-2:360 |
6-2:600 |
1)Type 1 coordination requires that, under short-circuit conditions, the device shall cause no danger to persons or installation and may not be suitable for
further use without repair and replacement of parts. |
LED |
2)Type 2 coordination requires that, under short-circuit conditions, the device shall cause no danger to persons or installation and shall be suitable for further use.
3)12A: AC-58b: 6-2:300 means max. load 6 x 12A for 2 sec.: Min. 300 sec. between starts.
*Der skal anvendes en contactor foran softstarteren
* It is mandatory to use contactor in front of the soft starter.
*Dem Softstarter muss ein Schütz vorgeschaltet werden.
LED status indikering/ LED status indication/ LED Zustandsanzeige
Rampe op |
Nominel drift |
Net-eller lastfejl |
Ramp up |
Full on |
Line or load error |
Ramp-up |
Nennbetrieb |
Netzoder Lastfehler |