EU Declaration of conformity.............................................11
Instructions S-Solo HWP
Safety notes
The following instructions refer to the standard
design of the S-Solo HWP substation. Special
versions are available on request.
To avoid injury of persons and damages to the
device, it is absolutely necessary to read and
observe these instructions carefully.
Necessary assembly, start-up and maintenance
work must be performed by qualified and
authorized personnel only.
Please comply with the instructions of the system
manufacturer or system operator.
Unused connections and shut-o valves must be
sealed with a plug. The plugs must be removed by
an authorized service technician only.
Choice of materials
Choice of materials always in compliance with
local legislation
Warning of high pressure and temperature
The maximum temperature of the ow medium
in the S-Solo HWP substations is 90 °C.
The maximum operating pressure of the substation
is 10 bar.
Be aware of the installation’s permissible system
pressure and temperature.
The substation installation must be equipped with
safety valves, however, always in accordance with
local regulations.
Warning of hot surface
The substation has got hot surfaces, which can
cause skin burns. Please be extremely cautious in
close proximity to the substation.
Warning of electric shock risk
Before cleaning or servicing disconnect power
supplies.
Warning of transport damage
Before substation installation, please make sure
that the substation has not been damaged during
transport.
Sound level
≤ 55 dB
Corrosion protection
All pipes and components are made of stainless
steel and brass.
The maximum chloride compounds of the ow
medium should not be higher than 300 mg/l.
The risk of equipment corrosion increases considerably if the recommended permissible chloride
compounds are exceeded
Disposal
Storage
The risk of persons being injured and equipment
damaged increases considerably if the
recommended permissible operating parameters
are exceeded.
This product consists of materials which must not
be disposed of together with domestic waste.
Dismantle the product and sort the components
in various groups before disposal. Observe the
disposal rules of the local legislation.
If the substation is stored before installation, make
sure that the place is dry and heated.
2
Produced by Danfoss Redan A/S · 03.2012
Instructions S-Solo HWP
Mounting
The substation must be installed and connected by
authorized service personnel only.
Installation must be in compliance with the local
standards and regulations.
Allow for adequate space around the substation for
mounting and maintenance purposes.
Prior to the substation installation all substation
pipes and connections should be cleaned and
rinsed.
The substation should be wall-mounted. The
mounting sheet on the back of the substation has
got holes for screw installation.
A symbol for each of the dierent connections is
placed on the substation.
Tightening of connections
Due to vibrations during transport all connections
must be checked and tightened before the
substation is installed.
After observing that the substations operates
in accordance with the dimensioning basis, the
connections must be tightened again and the
substation can be taken into continuous use.
Heat meter assembly, tting piece
The at station is equipped with a tting piece for
insertion of a heat meter.
Assembly of heat meter
Loosen nuts from tting piece, remove tting
piece and replace with heat meter.
Mount the heat meter according to the medium
ow direction.
After mounting of heat meter remember to
check all threaded connections
DCW meter (option)
The substation can be equipped with a tting
piece for insertion of DCW meter.
Assembly of DCW meter
Please refer to above assembly instructions for
heat meter.
Electrical connectionElectrical connections must be made by an au-
thorised electrician only.
Electrical connections must be made in accordance with current regulations and local standards.
Start-up
Prior to the S-Solo HWP installation all its pipes and
connections should be cleaned and rinsed. After
that the strainers should be cleaned.
Before starting-up, check if:
- pipes are connected according to the circuit
diagram,
- release valves are shut o,
- threaded and anged connections are
tightened.
Before making electrical connections, please note
the following:
- Please read the relevant parts of safety notes.
- The substation must be connected to 230 VAC
and earth.
- The substation must be connected via an exter nal main switch, which can be disconnected
by repairs.
All Danfoss substations have been pressure tested
prior to delivery.
Produced by Danfoss Redan A/S · 03.2013
3
Instructions S-Solo HWP
Components
1 Danfoss controller
2 Actuator HE
3 2-way valve *
4 Dierential pressure controller
5 Danfoss sensor *
6 Manometer
7 Balancing valve
8 Air valve *
9 Circulation pump
10 Thermometer, DH supply
11 Thermometer, DH return
12 Thermometer, cylinder return
13 Thermometer, HE supply
14 Thermometer, HE return
15 Sensor pocket for heat meter *
16 Fitting piece for heat meter
17 Strainer
18 Throttle valve
* not visible on photo
Please note:
Your substation may look dierent
than the substation shown, as variants with other components may
be supplied. The control function,
however, is basically as stated in this
instruction manual.
17
15
10
16
11
7
12
17
1
5
4
13
6
3
2
8
18
9
14
Instructions for the tted components will be supplied together
with the substation.
District heating (DH) - In the following
DH is specied as the heat source
for the substations. However, also
other heat sources such as an oil or
gas boiler or solar heating etc. could
be used as the primary supply for
the tted substations, enabling the
Danfoss Redan substations to be used
in numerous schemes with dierent
energy sources, depending on the
local operating conditions. In order
to simplify we have decided to use
DH as designation for the primary
supply.
Электроприводы для трехпозиционного регулирования AMV 150
www.danfoss.ru Страница 7
AMV 150 + AMV 150 + AMV 150 +
VS2 (DN 15) VMV AVQM (DN 15)
Instructions S-Solo HWP
GeneralPLEASE NOTE, that other variants may be supplied.
The control function, however, is basically as described below, and the control of the substation
should be done in accordance with the enclosed producer instructions for the mounted controller.
Description
Heating circuit
Temperature control
District heating substation for direct heating with
mixing loop for single-family, semi-detached and
terraced houses as well as ats. With one heating
circuit and with connection pipes for cylinder on
primary side. Designed for wall-mounting.
The heating temperature is controlled by an electronic temperature controller Danfoss ECL with
an outdoor temperature sensor.
The substation is supplied with mixing ciruit and
is thereby especially suitable for systems with
oor heating. The task of the mixing circuit is to
ensure a correct supply temperature for the heating circuit (to protect the heating circuit against
too high temperatures) and to ensure, that the
return water is cooled down to the required
temperature, before it ows back to the district
heating plant. The mixing circuit temperature is
controlled by an electronic temperature controller Danfoss ECL.
The temperature for the heating circuit is controlled
electronically by the Danfoss ECL controller. The supply
temperature ist calculated by the controller on basis of
the outdoor temperature.
The ECL Comfort 210 controller is loaded with a selected
application by means of an ECL Application Key (Plug&-Play). The Application Key contains information about
application, languages and factory settings.
From factory the VX Solo II H2WP is loaded with Application 1d. Other applications can, however, be loaded by
means of the ECL Application Key, and it is possible to
update the controller with new application software.
The controller is factory preset to turn o the heating
automatically in the summer period.
The controller settings can be changed in accordance with the enclosed producer instructions for the
mounted controller.
See ECL Application Key Box with ECL Comfort
210/310 user guide and mounting guide, for further
information.
Please see enclosed user guide,
2-way valve + electrical actuator.
The S-Solo HWP is supplied with a 2-way valve VS
2, which in combination with an electrical actuator Danfoss AMV 150 controls the heating circuit.
The electrical actuator is preset from factory. In
case of operating disturbances the actuator can
be closed manually.
Please see enclosed instructions,
Electrical actuator AMV 150
2-way valve VS 2
Close actuator by turning the manual override
knob on top of actuator counterclockwise.
Produced by Danfoss Redan A/S · 03.2013
Manual override
Note: Press and hold the button on the bottom side of
the actuator during manual override.
5
Instructions S-Solo HWP
Balancing valveFor regulation of the ow through the system the
S-Solo HWP can be supplied with a balancing valve.
For information about pre-regulation etc. please
refer to the enclosed instructions for use:
Kombi-3-Plus
Instruction for use
Dierential pressure controller
AVPL
AVPL is a self-acting dierential pressure controller
for PN 16 with adjustable dierential pressure setting.
Der AVPL keeps a constant dierential pressure even
with a variable system resistance.
The AVPL can be set at any dierential pressure between 0,05 bar and 0,25 bar. The preset factory setting
of the controller is 0,1 bar.
To alter the dierential pressure, use an Allen Key NV 3.
1 full turn is equivalent to approx. 0.01 bar. The arrow
on the controller top shows that the setting of the differential pressure is increased when it is turned clockwise and reduced when turned counter-clockwise.
The controller settings can be changed in accordance
with the enclosed producer instructions.
Circulation pumpGrundfos Pumpe ALPHA2 L
Substation start-up /pump
Do not start up the pump untill the system has
been lled with the ow media and vented. See
Grundfos instructions for the pump.
The pump is self-venting. It need not be vented
before start-up.
Air in the pump may cause noise, This noise ceases
after a few minu-tes running.
Please note, that the system cannot be vented
through the pump
Please note, that the pump must not run dry.
Pumpeneinstellung
GRUNDFOS ALPHA2 L has seven optional settings
which can be
selected with the push-button.
Enclosed photo shows the recommended and alternative pump settings for system types.
The pump is set at the factory to the “Higest proportional-pressure curve” (PP2). In this control
mode, the pump performance and consequently
the power consumption are adjusted according to
the heat demand in the system.
If the recommended pump setting does not give
the desired distribution of heat in the rooms of the
house, change the pump setting to the shown alternative.
For further infomation about pump settings please
Recommended and alternative pump settings according to system type.
refer to the enclosed Grundfos instructions.
ALPHA2 L,
Installation and operating instructions
6
Produced by Danfoss Redan A/S · 03.2012
Instructions S-Solo HWP
GRUNDFOS ANLEITUNG
GRUNDFOS ALPHA2 L
Montage- und Betriebsanleitung
ALPHA2 L
GRUNDFOSINSTRUCTIONS
www.grundfos.com/ALPHA2L
Summer operation
Stationen with Danfoss T°C Thermostat
In the summer, you can stop the pump by switching it o at the mains. However, remember to start
the pump (briey) at least once a month during the
summer.
Systems with Danfoss ECL:
Outside the heating period, the pump will be disconnected automatically from the heating system.
During the summer period, the controller will start
the pump for a minute at least once very three days
to prevent the pump from blocking.
Start-up after summer operation - venting
Please note that it may be necessary to vent the
system again. To vent the system, use the air vent,
if any, in the substation, or the radiators or, if appropriate, the air valve at the highest point of the
system.
Push-button for selection of pump setting
Domestic hot water
The S-Solo HWP is supplied with connection
pipes for cylinder on the primary side.
Produced by Danfoss Redan A/S · 03.2013
7
Instructions S-Solo HWP
Troubleshooting
Heating
If operating disturbances occur, the following
basic features should be checked before carrying
out actual troubleshooting:
- the substation is connected to electricity
- the strainer on the district heating supply is
- the dierential pressure is higher than or equal
to the normal (local) dierential pressure in the
district heating network. - if in doubt, ask the
district heating plant,
- there is pressure on the system.
clean,
- the district heating ow temperature is at the
normal level (summer, at least 60 °C, winter at
least 70 °C),
ProblemPossible causeSolution
Strainer clogges on DH or HE
side (radiator circuit)
Filter in district heating meter
clogged
Defective dierential pressure
controller
Defective actuator
2-vay valve defective - or possibly dirt in the valve housing
Clean strainer.
Clean the lter (after consulting the district heating plant).
Check the functioning of the
dierential pressure controller
- clean valve seat if required.
Check the functioning of the
actuator.
Check the functioning of valve
- clean valve seat if required.
No heat
Uneven heat distributionAir pockets in the systemVent the installation thorough-
Supply temperature too high
Automatic controls wrongly set
or defective - possibly power
failure
Pump out of operation
The pump is set at too low
speed of rotation
Air pockets in the system
Wrong setting of automatic
controls
Defective controller. The
controller does not react as it
should in accordance with the
instructions
Check if the setting of the controller is correct - see separate
instructions. Check the power
supply.
Check if the pump is receiving
power and that it runs. Check
if there is air trapped in the
pump housing - see pump
manual.
Set the pump at higher speed
of rotation.
Vent the installation thoroughly.
ly
Adjust automatic controls,
see instructions for automatic
controls.
Call in automatic controls
manufacturer or replace
controller.
8
Produced by Danfoss Redan A/S · 03.2012
Instructions S-Solo HWP
Troubleshooting
Heating
ProblemPossible causeSolution
Adjust automatic controls - see
instructions for automatic
controls
Call in automatic controls
manufacturer or replace
controller.
Place / t outdoor temperature
sensor correctly.
Clean strainer.
Increase total heating surface
Make sure that the heat is
distributed evenly across the
full heating surface - open all
radiators and keep the radiator
in the system from heating up
at the bottom.
Supply temperature too low
Poor cooling
Wrong setting of automatic
controls
Defective controller. The
controller does not react as it
should in accordance with the
instructions
Wrong placement / tting of
outdoor temperature sensor
Strainer clogges.
Too small heating surface/ too
small radiators compared to the
total heating requirement of
the building.
Poor utilization of existing heating surface.
The system is single-pipe
It is extremely important to
keep the supply temperature
to the radiators as low as ever
possible, while maintaining a
reasonable level of comfort.
Produced by Danfoss Redan A/S · 03.2013
9
Instructions S-Solo HWP
Maintenance
Meter reading
Cooling
Cleaning
Tightening
The substation requires little monitoring, apart
from routine checks and cleaning of strainers. To
ensure the best operating conditions regular inspection of the substation and a check of all relevant operating parameters are recommended,
for example in connection with meter reading.
Meter reading
We recommend that you read your meter regularly and that you write down the meter read.
Cooling / Return temperature reading
The cooling, i.e. the temperature dierence between district heating supply and district heating
return is of great importance for the total heat
economy. It is therefore very important to observe the supply and return temperatures.
Cleaning
All strainers should be checked and cleaned at
least once every year, typically in connection with
start-up of the heating system.
Tightening of connections
All threaded and anged connections should be
checked and tightened in connection with meter
reading. All threaded and anged connections
should be tightened regularly and especially in
connection with start-up after the summer period.
Venting
Strainer
Venting of system
Always vent the radiators and the substation before the heating season.
Strainer
Strainers should frequently be cleaned from
sediments by authorized personnel, according
to producer’s instructions and dependent on the
substation’s operating conditions.
10
Produced by Danfoss Redan A/S · 03.2012
Danfoss Redan A/S
District Energy
Omega 7, Søften
DK-8382 Hinnerup
Telephone +45 87 43 89 43
EC-DECLARATION OF CONFORMITY
For CE marking in EU (European Union)
Danfoss Redan A/S District Energy
DK-8382 Hinnerup
Declares under our sole responsibility that below products including all available power and control options:
S-Solo HWP
Main components: See Instruction Manual
Covered by this declaration is in conformity with the following directive(s), standard(s) or other normative document(s), provided that the products are used in accordance with our instructions.
EU Directives:
EMC Directive 2004/108/EEC
EN 61000-6-1 2007
industry.
EN 61000-6-2 2005 Electromagnetic compatibility- Generic standard: Immunity industry.
EN 61000-6-3 2007Electromagnetic compatibility- Generic standard: Emission for residential, commercial and light
industry.
EN 61000-6-4 2007Electromagnetic compatibility- Generic standard: Emission industry.
Machinery Directive 2006/42/EEC
EN ISO 14121-
EN 60204-1-Safety of machinery - Electrical equipment of machines — Part 1: General requirements
PED Directive 97/23/EEC
Conformity assessment procedure followed: Module A - Internal control of production
All substations that falls under Article 3 §3 and category 1 shall not be CE-marked according to this directive
CE marked affixed year 2010
Approved by:
Place and date of issue: Hinnerup, Aug. 24th, 2010
Name: Thavarupan Perinpam
Title: Quality and Lean Manager
Electromagnetic compatibility- Generic standard: Immunity for residential, commercial and light