Danfoss S - Solo Fact sheet

Fact sheet
S - Solo
Substation for single-family, semi-detached and terraced houses as well as flats
FEATURES AND BENEFITS
• District heating substation for direct heating
• Connection pipes for DHW cylinder
• Equipped with A-labelled low-energy pump
• Pipes and heat exchanger in stainless steel
• Minimized risk of lime scale and bacte­ria formation
• The substation is very service-friendly due to practical piping and assembly
with nuts and gaskets
Application
The S-Solo is a complete district heat­ing substation for direct heating with mixing loop for single-family, semi-de­tached and terraced houses as well as flats. The substation features one heat­ing circuit and it is prepared for connec­tion to a domestic hot water cylinder. The substation is especially suitable for one pipe systems and systems with floor heating.
District heating (DH)
The substation is prefabricated with in­terconnecting components such as fit­ting piece and sensor pockets for inser­tion of a heat meter mounted in the DH return pipe, as well as strainer, ball valves and pockets for pressure gauge.
Heating (HE)
The heating side features manometer, thermometers, ball valves and a mixing loop, with circulation pump and a throt­tle valve, which provides a suitable tem­perature level e.g. for floor heating, and protects the heating circuit against too high temperatures.
The heating side is controlled by an ele­ctronic temperature controller Danfoss ECL 210 or 310 with wea ther compensation, in combination with an actuator and valve. Actuator and pump are electrically wired from factory and supplied with CEE plug for connec­tion to 230 V. The electronic control ECL 310 is prepa­red for WebAcess, which enables remote control and remote monitoring via the internet/intranet. The substation is delivered preas­sembled, electrically wired internal­ly and the electronic control is tested for function and preset from factory.
Connection pipes for domestic hot water cylinder (DHW)
As standard the S-Solo is supplied with primary connection pipes for DHW cy­linder.
Design
The S-Solo is designed for wall-moun­ting and during the construction much importance has been attached to a clear and user-friendly placement of all com­ponents.
The S-Solo can be supplied with a whi­te-lacquered steel cover with door, which enables easy access for meter rea­ding and service purposes.
Design
The S-Solo is designed for wall-moun­ting and during the construction much importance has been attached to a clear and user-friendly placement of all com­ponents. The S-Solo can be supplied with a white-lacquered steel cover with door, which enables easy access for me­ter reading and service purposes.
Reading and setting
All thermometers are placed so they are easy to read. Components, which can be adjusted, are easily accessible.
Service og maintenance
The substation is very service-friendly due to practical piping and assembly with nuts and gaskets. It is mounted on the wall and as all pipes are placed in pipe bracket distance, it is possible to establish a nice piping.
www.heating.danfoss.com
CIRCUIT DIAGRAM  EXAMPLE  SSOLO WITH ECL 210, A237
DHW
DCW
Circ.
DH Supply
DH Return
Design specifications:
Nominal pressure (prim/sec): PN 10 / PN 3 Max. supply temperature.: 120 °C
Weight: Max. 30 kg
4 Diff. pressure controller 5 Strainer 6 Non-return valve 7 Ball valve 8 Circulation pump 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 17 Air valve
23 Sensor pocket for heat meter 24 Fitting piece for heat meter, 25 Controller Danfoss ECL210/A237 26 Outdoor sensor, ESMT 27 Sensor ESMC 29 Actuator 30 2-way valve VS2 46 Balancing valve 49 Throttle valve
P, M and S refer to the Danfoss ECLinstruction manual
HE Supply
HE Return
Connections:
1. DH supply 4. Cylinder supply
2. DH return 5. HE supply
3. Cylinder return 6. HE return
Colour (cover): White RAL 9010
Electrical supply: 230 V AC
Dimensions (mm):
Without cover: H 635 x W 500 x D 295 Cover: H 520 x W 500 x D 380
DHW: Capacity examples with electronic control, ECL 310, A230
Heating capacity
20 75/40 40/65 25 3.0 491 688 20 80/45 45/70 25 3.0 491 688 20 90/50 50/70 19 4.0 430 860 30 75/40 40/65 56 6.0 737 1032 30 80/45 45/75 52 6.0 737 1032 30 90/50 50/70 43 9.0 645 1290 15 75/30 30/40 9 9.0 287 1290 15 80/30 30/40 7 9.0 258 1290 15 90/30 30/40 5 9.0 215 129 0
Heating
circuit
Primary
°C
Heating
circuit
Secondary
°C
Pressure loss
Primary
*kPa
Pressure loss
(Only sec. side of heat
exchanger)
kPa
Connections sizes:
DH, HE, Cylinder,: G ¾“ (int. thread)
Flow rate
Primary
l/h
Flow rate
Primary
l/h
© Danfoss | DHS-SRMT/ PL | 2018 . 05