Installation Guide
Sets for systems with ow coming from wall or
oor comes with:
- Built-in valve RA-N(D)
- Thermostatic sensor RAE
- H-piece, type RLV-KS
- Fittings PEX-ALU 16x2 mm
1.0
2.0
Danfoss Heating Solutions VIIDL102 05/2014
1

Installation Guide
3.0
Danfoss integrated valve
Screw the integrated valve into the radiator until it is hand tight
and it’s ange is butting onto the radiator connection.
Then, using an open ended ring spanner, SW21, tighten the valve
into the radiator, this should be turned through an angle of 30°
equivalent to one of the notches on the valve body part on wich
the spanner ts. This equates to a torque of 30-35 Nm.
2
Danfoss Heating Solutions VIIDL102 05/2014

Installation Guide
3.1
Presetting the dimensioned setting values can be selected simply and precisely without tools, prior to the tting of the sensor. For this
purpose, the red scale ring must be turned to ensure that the presetting gure selected matches the setting mark.
In setting “N” the preset value is fully open.
Detailed information is available from stockists or from the radiator manufacturer.
Danfoss Heating Solutions VIIDL102 05/2014
33

Installation Guide
4.0
Danfoss Thermostatic Sensors RAE
Remove the protective cap from the valve insert by turning it
anti-clockwise.
Ensure that the setting mark on the sensor is positioned at the
top before mounting the sensor
Mount the thermostatic sensor on the valve and tighten it by
pushing on the thermostat until it ‘clicks’.
5.0
Adjusting Temperature Control Range
Setting the upper limit: e.g. at the III position
1. Set the thermostatic sensor to the maximum temperature.
2. Press down the limiter tab to the right of the setting mark with
a screw driver and turn the thermostatic sensor to position III,
while pressing/holding down the limiter tab.
3. Release the tab.
Setting the lower limit: e.g. at the II position
1. Set the thermostatic sensor to the minimum temperature.
2. Press down the limiter tab to the left of the setting mark with
a screw driver and turn the thermostatic sensor to position II,
while pressing/holding down the limiter tab.
3. Release the tab.
4
Danfoss Heating Solutions VIIDL102 05/2014

Installation Guide
6.0
Danfoss Heating Solutions VIIDL102 05/2014
55

Installation Guide
6
Danfoss Heating Solutions VIIDL102 05/2014

Installation Guide
Danfoss Heating Solutions VIIDL102 05/2014
77

Installation Guide
VIIDL102 /013R9585