Danfoss Sets for systems with flow coming from wall or floor comes Installation guide

Sets for systems with ow coming from wall or oor comes with:
- Built-in valve RA-N(D)
- Thermostatic sensor RAE
- H-piece, type RLV-KS
- Fittings PEX-ALU 16x2 mm
1.0
2.0
Danfoss Heating Solutions VIIDL102 05/2014
1
3.0
Danfoss integrated valve
Screw the integrated valve into the radiator until it is hand tight and it’s ange is butting onto the radiator connection. Then, using an open ended ring spanner, SW21, tighten the valve into the radiator, this should be turned through an angle of 30° equivalent to one of the notches on the valve body part on wich the spanner ts. This equates to a torque of 30-35 Nm.
2
Danfoss Heating Solutions VIIDL102 05/2014
3.1
Presetting the dimensioned setting values can be selected simply and precisely without tools, prior to the tting of the sensor. For this purpose, the red scale ring must be turned to ensure that the presetting gure selected matches the setting mark. In setting “N” the preset value is fully open. Detailed information is available from stockists or from the radiator manufacturer.
Danfoss Heating Solutions VIIDL102 05/2014
33