SET3E
Installation Instructions
SET3E
Electronic 24-Hour Programmer
for Heating and Hot Water
This product should only be installed by a qualifi ed electrician or
competent heating installer and should be in accordance with the
current edition of the IEEE wiring regulations.
2.0 System Overview
Specifi cation
Power supply230 ± 15% Vac, 50/60Hz
Switch action2 x SPDT Type 1B
Switch rating
Timing accuracy± 1 min/month
Power reserveminimum 10 hours
Enclosure ratingIP30
Max. ambient temperature45°C
Dimensions, mm (W, H, D) 158 x 99 x 38
Design standardEN 60730-2-7
Control Pollution Situation Degree 2
Rated Impulse Voltage 2.5kV
Ball Pressure Test75°C
Max 264Vac, 50/60Hz, 3(1) A
3.0 Installation
1. Fix the wallplate to the wall or fl ush mounted box as required.
The connections are at the top and the vertical centre line of
the unit, at the position shown on the diagram C/L (in line with
terminal
).
2. Surface cables can only enter from below the unit. If mounted on
a fl ush mounted box, cables can enter from the rear through the
aperture in the wallplate.
3. For mains voltage applications a link must be fi tted between
terminals L, 2 and 5.
4. Whilst the unit does not require an Earth connection, a terminal is
provided on the wallplate for Earth continuity purposes.
4
SET3E
Leave suffi cient space
Outline of
programmer
Leave at least
25mm below
product
C/L
Rear entry
cable access
for screwdriver access
Terminal
block
Wall or
plasterbox
fi xing
Cable aperture
knockouts
5. Referring to the wiring diagrams on page 6-12, connect the unit
as shown.
GB
6. The unit is supplied ready for use in systems having PUMPED
primaries. Should the unit be required for use in a system having
GRAVITY primaries, remove the small link located on the rear of
the unit. The link, which is clearly labelled can be found on the
bottom RIGHT hand side of the unit.
7. Ensure all dust and debris are cleared from the area.
8. Locate the module on the latches at the bottom of the wallplate
and hinge upwards to fully engage the unit connectors into the
wallplate. Tighten the two fi xing screws to secure the unit to the
wallplate.
9. Before setting the programme, check the unit and circuit. Switch
ON the mains supply and press both WATER & HEATING rocker
switches to the ON position - both red LED’s should now be
illuminated. Adjust any remote thermostat to check the services
operate correctly.
10. Then press both WATER and HEATING rocker switches to the OFF
position and check that both services do not operate.
11. Finally, press both WATER and HEATING rocker switches to TIMED position prior to programming the unit.
Danfoss Heating
5
GB
3.1 Wiring
Typical wiring diagrams for various types of systems are shown on
the following pages.
Note: Whilst every attempt has been made to ensure the accuracy of this
information it is recommended that the specifi c information relating to
the ancillary controls is obtained from the manufacturers concerned.
TIMER
NOTES:
FOR SET2E LINKTERMINALS 1 & 5
N/O
N/C
N/O
N/C
FP975 ON A SET WALLPLATE
N
NOTE: For mains voltage applications links must be fi tted between
terminals L, 2 and 5.
L123
ON
COM
DHW
OFF
45
ON
COM
HTG
6
OFF
6
SET3E
3.2 Typical Gravity DHW Pumped HTG
D.H.W.HTG
Mains
Supply
Programmer
Terminals
N
L
3 amp fuse
BoilerPump
ONOFF
ONOFF
N L 1 2 3 4 5 6
Links
Room
Stat
N
N
N
GB
DHW = Domestic Hot Water
Danfoss Heating
7
3.3 Typical Fully Pumped System with Spring
Return Zone Valve in Heating
D.H.W.HTG
GB
Mains
Supply
Programmer
Terminals
N
L
3 amp fuse
Cyl.
Stat
Boiler
ONOFF
ONOFF
N L 1 2 3 4 5 6
Links
Room
Stat
N
N
N
S.R.Z.V
& Pump
Other Danfoss Randall products suitable for use with above circuit:AT cylinder thermostat;
2 x HP22 or HP28 motorised zone valve with spring return actuator
and SPST auxiliary switch.
in HTG
8
SET3E
3.4 Typical Gravity DHW Pumped HTG with
Spring Return Zone Valve in DHW
D.H.W.HTG
Mains
Supply
N
Programmer
Terminals
N
L
Cyl.
Stat
S.R.Z.V
in DHW
ONOFF
N L 1 2 3 4 5 6
3 amp fuse
N
N
N
BoilerPump
ONOFF
GB
Room
Stat
Other Danfoss Randall products suitable for use with above circuit:AT cylinder thermostat;
HP28C motorised zone valve with spring return actuator and SPDT
auxiliary switch.
Danfoss Heating
9
3.5 Typical Fully Pumped System with 3-Port
Mid-Position Valve
D.H.W.HTG
GB
Mains
Supply
Programmer
Terminals
N
L
3 amp fuse
Cyl.
Stat
Boiler
& Pump
N
ONOFF
ONOFF
N L 1 2 3 4 5 6
Links
Room
Stat
N
N
3-port
mid pos
valve
Other Danfoss Randall products suitable for use with above circuit:AT cylinder thermostat
HS3 3-port mid-position valve with spring return actuator.
10
SET3E
3.6 Typical Fully Pumped System with Spring
Return Zone Valve in each Service
D.H.W.HTG
N
Mains
Supply
S.R.Z.V.
in DHW
Programmer
Terminals
N
L
3 amp fuse
Cyl.
Stat
Boiler
ON
OFF
ON
OFF
N L 1 2 3 4 5 6
Links
Room
Stat
N
N
N
S.R.Z.V.
in HTG
GB
Other Danfoss Randall products suitable for use with above circuit:AT cylinder thermostat
2 x HP22 or HP28 motorised zone valve with spring return actuator
and SPST auxiliary switch
Danfoss Heating
11
3.7 Typical Fully Pumped System with Fully
Motorised Zone Valve in each Service
D.H.W.HTG
GB
Mains
Supply
N
Programmer
Terminals
Cyl.
Stat
F.M.Z.V
in DHW
N
ON
OFF
ON
OFF
N L 1 2 3 4 5 6
L
Links
3 amp fuse
Room
Stat
N
N
Boiler
N
F.M.Z.V
in HTG
Other Danfoss Randall products suitable for use with above circuit:AT cylinder thermostat.
12
SET3E
4.0 Replacement
Please see overleaf for a table containing replacement wiring
information.
Some timecontrols are connected in diff erent ways depending upon
the type of system and/or the controls which are fi tted. Consult
the column headed “NOTE: The conversion applies only if....” to
determine whether the SET3E GRAVITY or PUMPED is the correct
conversion.
If there is any doubt about the way in which the existing programmer
is connected, please contact our Technical Services Department
before proceeding with replacement.
Note: The SET3E is a direct plug-in replacement for a Danfoss
Randall SET5, although it does not off er 5/2 day programming
option.