SET2E
Installation Instructions
SET2E
Electronic 24-Hour Mini-Programmer
for Heating and Hot Water
This product should only be installed by a qualifi ed electrician or
competent heating installer and should be in accordance with the
current edition of the IEEE wiring regulations.
2.0 System Overview
Specifi cation
Power supply230 ± 15% Vac, 50/60Hz
Switch action2 x SPDT Type 1B
Switch rating
Timing accuracy± 1 min/month
Power reserveminimum 10 hours
Enclosure ratingIP30
Max. ambient temperature45°C
Dimensions, mm (W, H, D) 158 x 98 x 38
Design standardEN 60730-2-7
Control Pollution Situation Degree 2
Rated Impulse Voltage 2.5kV
Ball Pressure Test75°C
Max 264Vac, 50/60Hz, 3(1) A
3.0 Installation
1. Fix the wallplate to the wall or fl ush mounted box as required.
The connections are at the top and the vertical centre line of
the unit, at the position shown on the diagram C/L (in line with
terminal
).
2. Surface cables can only enter from below the unit. If mounted on
a fl ush mounted box, cables can enter from the rear through the
aperture in the wallplate.
3. For mains voltage applications a link must be fi tted between
terminals L and 2 and between 1 and 5.
4. Whilst the unit does not require an Earth connection, a terminal is
provided on the wallplate for Earth continuity purposes.
4
SET2E
Outline of
programmer
Leave at least
25mm below
product
Rear entry
cable access
Leave suffi cient space
for screwdriver access
C/L
Terminal
block
GB
Wall or
plasterbox
fi xing
Cable aperture
knockouts
5. Referring to the wiring diagrams on page 6-9, connect the unit as
shown.
6. Ensure all dust and debris are cleared from the area.
7. Locate the module on the latches at the bottom of the wallplate
and hinge upwards to fully engage the unit connectors into the
wallplate. Tighten the two fi xing screws to secure the unit to the
wallplate.
8. Before setting the programme, check the unit and circuit. Switch
on the mains supply and set the left-hand rocker switch to the
CONSTANT position and the right-hand rocker switch to the HW
+ CH position.
The red LED should now be illuminated. Adjust any remote
thermostats to check the services operate correctly.
9. Press the left-hand rocker switch to the OFF position and check
that both services do not operate.
10. Finally, return the left-hand rocker switch to TIMED and the righthand rocker switch back to HW + CH (winter) or HW (summer).
Danfoss Heating
5
GB
3.1 Wiring
NOTES:
FOR SET2E LINK
TERMINALS 1 & 5
FP975 ON A SET WALLPLATE
TIMER
N/O
N/C
N/O
N/C
N
NOTE: For mains voltage applications links must be fi tted between
terminals L and 2 and between 1 and 5.
Typical wiring diagrams for various types of systems are shown on
the following pages.
Note: Whilst every attempt has been made to ensure the accuracy of this
information it is recommended that the specifi c information relating to
the ancillary controls is obtained from the manufacturers concerned.
L123
ON
COM
DHW
OFF
45
ON
COM
HTG
6
OFF
6
SET2E
3.2 Typical Gravity DHW With Pumped Central
Heating
D.H.W.HTG
Programmer
Terminals
Mains
Supply
N
L
3 amp fuse
L
ONOFF
ONOFF
N L 1 2 3 4 5 6
N
Room
Stat
GB
BoilerPump
DHW = Domestic Hot Water
N
N
Danfoss Heating
7
3.3 Typical Fully Pumped System with Spring
Return Zone Valve in Heating
D.H.W.HTG
GB
Programmer
Terminals
Mains
N
Supply
L
Cyl.
Stat
N L 1 2 3 4 5 6
3 amp fuse
ONOFF
Room
Stat
N
ONOFF
L
Boiler &
Pump
N
HTG
valve
N
8
SET2E
3.4 Typical Fully Pumped System With 3-Port
Mid-Position Valve
D.H.W.HTG
Programmer
Terminals
Mains
N
Supply
L
Cyl.
Stat
3 amp fuse
L
ONOFF
ONOFF
N L 1 2 3 4 5 6
Room
Stat
N
GB
Boiler &
3-port
mid-pos
Pump
NN
valve
4.0 Replacement
Please see overleaf for a table containing replacement wiring
information. Some controls are connected in diff erent ways
depending upon the type of system and/or the controls which are
fi tted. If there is any doubt about the way in which the existing unit is
connected, please contact our Technical Services Department before
proceeding with replacement.
If the unit is to be used in association with a 6 wire Honeywell Y Plan, a
special wiring diagram may be required. Contact the Danfoss Randall
Technical Services Department for details.
Note: The SET2E is a direct replacement for a Danfoss Randall
SET2.