Danfoss S 22 Fact sheet

Fact sheet
S 22
District heating substation for small properties and apartment houses
Application
The S 22 is made in a compact design and is especially suitable for supply of heating and do­mestic hot water for small properties and apart­ment houses. The S 22 is available with Danfoss ECL 310 for control of both heating and dome­stic hot water circuits. The substation is very suitable for one- and two pipe systems and is also applicable for systems with floor heating. The S 22 variants offer capacities ranging from 55 to 100 kW heating (10 to 16 kW floor heating) and 40 to 110 kW domestic hot water. Please contact our sales department and together we shall find the optimum solution for your exact requirements.
Construction
The S 22 is supplied with a brazed plate heat ex­changer for domestic hot water heating, electro­nic actuators and valves, shut-off valves, non-re­turn and safety valve, pump, circulation pump, thermometers, strainers, sensor pockets as well as differential pressure controller. Actuators and pumps are electrically wired from factory and supplied with CEE plug for connection to 220 V. The electronic control is prepared for WebAc­cess, which enables remote control and remote monitoring via the internet/intranet. The sub­stations are delivered preassembled, electrically wired internally and the electronic control is te­sted for function and preset from factory.
The substation is supplied without fitting piece for heat meter. Fitting piece for heat meter is available as an option.
Design
The S 22 is designed for wall-mounting and during the construction much importance has been attached to a clear and user-friendly placement of all components. The S 22 can be supplied with a white-lacquered steel cover with door, which enables easy access for meter reading and service purposes.
Domestic hot water recirculation
As standard the S 22 is supplied with a low-ener­gy pump for domestic hot water recirculation and can easily be connected to existing systems with DHW recirculation. On new constructions it is recommended to establish domestic hot water recirculation, which ensures that hot water is produced immediately, when tapping starts. This ensures maximum DHW comfort og eliminates water wastage.
Heat exchanger for DHW heating
The heat exchanger used in the S 22 is a brazed, highly efficient Danfoss plate heat exchanger, which has been tested and approved according to the PED-directive.
FEATURES AND BENEFITS
• Substation for apartment houses and small properties
• Indirect heating - one or two heating circuits
• Connections for DHW cylinder on the secondary side
• Electronic control of heating (HE) tem­perature
• Capacity: 39 - 95 kW HE / 35 kW FH / 75 kW cylinder or radiator
• Pipes connection in top or bottom of substation = Savings in installations costs
• Pipes and plate heat exchanger made of stainless steel
• Electrical wiring from factory - Plug & Play
Reading and setting
All thermometers are placed so they are easy to read. Components, which can be adjusted, are easily accessible.
Maintenance
The substation is very service-friendly due to practical piping and assembly with nuts and gaskets. It is mounted on the wall and as all pipes are placed in pipe bracket distance, it is possible to establish a nice piping.
www.danfoss.com
CIRCUIT DIAGRAM  EXAMPLE
DHW
DCW
Circ.
DH Supply
DH Return
Design specifications:
Nominal pressure (prim/sec): PN 10 / PN 10 Max. supply temperature.: 120 °C Min. ΔP: 0,75 bar incl. differential pressure controller (alternatively 0,5 bar)
Weight: Max. 65 kg
Colour (cover): White RAL 9010
Electrical supply: 220 V AC
Dimensions (mm):
Without cover: H 1037 x W 545 x D 370 With cover: H 1037 x W 600 x D 400
Cover
2 Plate heat exchanger DHW 4 Diff. pressure controller 5 Strainer 6 Non-return valve 7 Ball valve 8 Pump HE 9 Circulation pump, DHW 10 Balancing valve, DHW 12 Safety valve DHW 13 Thermometer
Cover
Cover
Connections:
1. DH supply 5. DHW
2. DH return 6. HE return
3. DCW 7. HE supply
4. Circulation
Connections sizes:
DH, HE, DCW, DHW: G 1“ (int. thread) Circulation: G 1“ or ¾“ (int. thread)
14 Manometer w/shut-off valve 17 Air valve 23 Sensor pocket for heat meter (optional) 24 Fitting piece for heat meter, (optional) 25 Controller Danfoss ECL310/A266 26 Outdoor sensor 27 Sensor forward/return 28 Sensor, DHW 29 Actuator 2 30 Valve 2 31 Actuator 1 32 Valve 1
P, M and S refer to the Danfoss ECLinstruction manual
HE Supply
HE Return
Wall
Top view
Flow
l/h
Tot al (winter)
Pres. loss
Prim.
2)
total
bar
Flow
Primary
total
DHW: Capacity examples
CAPACITY, WEIGHT AND DIMENSIONS
Secondary
return/supply
°C
10/50 10/50
10/50 10/50
Tap load
l/min.
16.33 0.25 830 55 70/30 30/60 0.27 118 3 0.49 150 0
26.66 0.33 1350 100 70/30 30/60 0.44 2150 0.86 2590
36.83 0.57 1870 80 70/30 30/60 0.28 1720 0.74 2710
25.16 0.56 1340 65 90/40 40/74 0.24 1118 0.51 1640
34.00 0.54 1810 90 90/40 4 0/74 0.23 1548 0.54 2250
25.16 0.56 1340 10 70/30 30/35 0.05 215 0.67 1350
25.16 0.56 1340 16 70/30 30/35 0 .13 344 0.53 1750
Plate heat
exchanger
XB 37M-1 20 40
XB 37M-1 30 65
XB 37M-1 40 90
XB 37M-1 30 70 65/20.0 XB 37M-1 40 95 65/20.0
Varmt vand: Ydelseseks. med elektronisk styring, ECL 310, A266
DHW: Capacity examples HE: Capacity examples Tot al (winter)
XB 37M-1 30 70 65/20.0
XB 37M-1 30 70 65/20.0
Capacity
kW
supply/return
Primary
°C
60/18. 5 10/45 60/18. 5 10/45 60/18. 5 10/45
Pressure
loss prim.
1)
bar
HE: Capacity examples
Flow
Primary
l/h
Capacity
Primary
supply/return
kW
°C
HEATING: CAPACITY EXAMPLES
Secondary
return/supply
°C
Pressure loss
Primary
1)
bar
Primary
Danfoss Redan A/S · District Heating · Omega 7, Søften · DK-8382 Hinnerup · Denmark Tel.: +45 87 43 89 43 · Fax: +45 87 43 89 44 · redan@danfoss.com · www.redan.danfoss.dk
© Danfoss | DHS-SRMT/ PL | 2017 . 12
VL.HE.J2.02