Data Sheet
Thermostatic Radiator Sensor, Type RAW5014
Application
Quality
Coefficient de Variation
Temporelle
Features
RAW 5014
The raw series is a programme of radiator thermostats which covers all central and district heating
systems.
RAW is a self-acting proportional controller with a
small P-band.
RAW radiator thermostats are designed for use in
2-pipe domestic heating systems. They are equipped with snap connection.
Thermostatic sensors RAW are manufactured
to the highest standards, and are
approved to the European standard EN
215.
RAW 5014: Vt = 0,2 K
- Thermostatic valves functioning
autonomously without auxiliary power
- With maximum limits stops plant
and minimum of the range of adjustment for
as a blocking of the adjusting
- High control accuracy and long-term
life through a unique system of bellows and
gland low friction body valve
- Comfort in heating and very good recovery
(energy saving)
RAW 5012
The RAW sensor incorporates a frost protection
setting for maximum user flexibility, and provides
also the option to limit the temperature range.
The RAW desig is particularly robust, with both
End-Stop strength limits and sensor bending
force limits being substantially above the requirements of the European Standard EN215.
All Danfoss radiator thermostats are manufactured in factories, assessed and certified by BSI
(British Standards Institution) against ISO 9000
and ISO14001.
- Capillary tube of very easy remote probe
unwind
- Aesthetic that integrates with any interior (RAL
color 9016)
- Wide choice of valve body
- Thermostatic head quick snap ensuring
precise and secure mounting
- Theft tab
Ordering and
Specifications
1) Xp= 2K (the valve closes at 2 °C higher room temperature)
2)The remote sensor is equipped with 2 m of ultra-thin capillary tube, which is coiled up within the
remote sensor housing. After sensor mounting capillary tube is pulled out to the required length.
Danfoss Heating Solutions VDJPA202 © Danfoss 03/2016 1
Type Version Colour Setting range 1) Code No.
RAW5014 Built-in sensor
RAW5012 Remote sensor 0-2m
RAL 9016 8-28 °C
2
013G5014
013G5012
10 14 18 22 26 30 °C
1
2
• • • 3 • • • 4
5
8 12 16 20 24 28 °C
Datasheet Thermostatic Radiator Sensor, Type RAW
Setting the Temperature
* = Frost protection setting
Mounting
The required room temperature is set by turning
the setting dial. The temperature scales show the
correlation between scale values and the room
temperature. The temperature values stated are
for guidance only as the obtained room temperature
will often be influenced by installation conditions.
The temperature scales are stated according to
European standards at Xp = 2°C. This means that
the radiator thermostats close at a sensor temperature which is 2°C higher than stated on the
temperature scales.
Setting the upper and lower limit
The thermostat features two tabs with which the
temperature setting area can be decreased. If 4
should be max. setting, turn the thermostat to
max. position (3) and press and hold right tab
while turning the thermostat to 4 (3), now release
tab. With the left tab the lower temperature must
be turned to min. position (4).
The mounting of the sensor onto the valve is
simply and is carried out without the use of tools.
Place the sensor onto the valve and push and it
The snapp ring fixes the sensor automatically
onto the valve. The snapp mechnisme is active
ex works and ready for mounting.
snaps onto the valve.
Removing the sensor, the ring back is to be
turned to activate the mechanisme again.
Danfoss Heating Solutions VDJPA202 © Danfoss 03/2016 2