Data sheet Non-Electric Thermostatic Sensor for ABQM
RAE-K, FEV-Z
Ordering:
Setting Range:
The RAE-K and FEV-Z styles of thermostatic
operators provide an effective use of pressure
independent flow control with a non-electric
control valve. By using the ABQM pressure
independent control valve (PICV) proper
flow is maintained to the emitter. With the
thermostatic operator mounted to the valve, a
cost effective method of control is used to
maintain the room temperature.
The RAE-K thermostatic operators are a
series of valve mounted non-electric
operators that are capable of mounting to the
ABQM valve body. These operators are an
alterative to a motorized actuator providing a
temperature regulating within the room
either via built-in sensor or remote sensor.
Code No. Style Description Sensor Capillary
013G5034 RAE-K Valve mounted dial and sensor Built-in -
013G5036 RAE-K Valve mounted dial with remote sensor Remote
013G5458 FEV-Z
003Z0248 -
Thermostatic operators used only with ½” & ¾” ABQM valve bodies and limited to 30% of maximum flow rate
Combined remote mounted dial and
sensor
Required spindle extension adapter when installing thermostatic
operators onto ABQM, 5 pcs.
Type RAE-K FEV-Z
Setting temperature range
RAE-K
The FEV-Z climate sensor is a
proportional controller which opens or
closes an AB-QM valve body as a function
of the temperature deviation. The wall
mounted non-electric operator can be
applied in climate systems with i.e.
ceiling-, floor- or radiator heating. The 6ft
capillary tube allows the placement of the
flush mounted setting/ sensing dial away
from the valve body.
When selecting these thermostatic
operators for an application, there is a
limitation in the ability of the thermostatic
operators to control the ABQM valve
body. The thermostatic operator is limited
to 30% of the maximum flow rate for the
ABQM valve sizes of ½” to ¾”.
46…82°F (8…28°C) 62…80°F (17…27°C)
FEV-Z
Remote
6.5ft
(2m)
26ft
(8m)
VD.CV.U1.22©Danfoss 1/2012
1
Data sheet Non-Electric Thermostatic Sensor for ABQM
RAE-K, FEV-Z
Temperature
control
with FEV-Z
Dimensions:
The FEV-Z sensor has been developed for heating regulation of water-based systems. The
FEV-Z sensor is based on the self-acting principle. The liquid-filled wall mounted sensor
control the valves via capillary tube.
When the knob has been set in the middle position the valve will open at temperatures
lower than 71°F (22°C). A setting in the red zone means the valve will open at a higher
room temperature. A setting in the blue zone means the room temperature will be kept at a
value lower then 71°F (22°C).
17 18 19 20 21 22 23 24 25 26 27
°C
62.6 64.4 66.2 68.0 69.8 71.6 73.4 75.2 77.0 78.8 80.6
3.1in
(80mm)
2.2in
(50mm)
°F
(85mm)
3.3in
Danfoss can accept no responsibi lity for possible errors in printed materials and reserves the right to alter its products without notice. All trademarks in this material are property of the
respective companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All right reserved.
Head Office: USA Office:
Danfoss Inc. Danfoss Inc.
Mississauga, ON CANADA Baltimore, MD USA
Tel: 866-375-4822 Fax: 905.285.2055 Tel: 866-375-4822 Fax: 443.512.0270
www.na.heating.danfoss.com
VD.CV.U1.22©Danfoss 1/2012
(80mm)
3.1in