Danfoss RAE 5054, RAE 5154, RAE 5056 Data sheet

Data Sheet
Thermostatic Sensors Type RAE
Application
RAE 5054/5154 RAE 5056
RAE is a self-actuating proportional controller with a small P-band. The series includes:
• RAE 5056 with remote sensor.
• RAE 5154 with built-in sensor and positive shut-o feature
RAE Radiator thermostats are designed for use in 2-pipe domestic heating systems.
RAE sensors incorporate a frost protection setting and max/min limitation of the tempera­ture setpoint.
RAE sensors are equipped with a snap-lock mechanism which ensures quick, rm and long lasting mounting of the sensor to the valve body, without the use of tools.
RAE 5056 is equipped with 2 m of ultra-thin capillary tube, which is coiled up within the remote sensor housing. After sensor mounting capillary tube is pulled out to the required length.
The RAE construction is particularly robust, with both End-Stop strength limits and sensor bending force limits being substantially above the requirements of the European Standard EN 215.
Approved to EN 215
Data and Ordering
Thermostatic sensors RAE are manufactured to the highest standards, and are approved to the European standard EN 215.
Typ e Version Setting range
RAE 5054 Built-in sensor
RAE 5056 Remote sensor, 0-2 m
RAE 5154 Built-in sensor, positive shut-o feature 013G5154
1)
Temperatures stated for Xp = 2K, i.e. the valve is closed at 2 °C higher room temperature.
2)
The remote sensor is delivered with all of the capillary tube coiled up within the sensor. When mounting the sensor,
only the capillary tube required is uncoiled.
VDTTM402 © Danfoss 07/2014
2)
All Danfoss radiator thermostats are manufac­tured in factories, assessed and certied by BSI (British Standard Institution) against ISO 9000 and ISO 14001.
1)
8-28 °C
Code no.
013G505 4
013G5056
1
Data Sheet Thermostatic Sensors Type RAE
Accessories
Design
Accessories and spare parts Code no.
Angle adaptor for snap-lock sensors, for valves with Danfoss RA connection 013G1350
Angle adaptor for snap-lock sensors, for valves with M30x1.5 connection 013G1360
Anti-theft plugs (20 pcs.) 013G5245
Tool kit comprising Allen key & locking pin tool 013G1236
Manual setting knob for all RA valves (dierential pressure max. 0.6 bar) 013G5002
The RAE thermostatic sensor operates with a liquid lled bellows system, which is actuated by ambient temperature changes. The calibrated pressure in the bellows corre­sponds to the temperature. This pressure is bal­anced by the force of a regulating spring.
On a rise in ambient temperature, the pressure
increases in the bellows, moving the valve cone towards the “closed” position, until equilibrium exists between the bellows and spring.
On a drop inambient temperature, the pressure falls, allowing the bellows to contract and the valve cone to move towards the “open” position until a state of equilibrium is re-established.
1.
Socket
2.
Bellows
3.
Setting handle
4.
Setting mark
5.
Limiter tab
6.
Reset spring
7.
Sensor medium
8.
Spindle
9.
Spring
10.
Capillar tube
11.
Console
12.
Cover
Limiting and Locking the Settings
2
Locking and limitation of the temperature setpoint of RAE sensors are carried out using the limiter tabs as shown below.
VDTTM402 © Danfoss 07/2014
Example: Limiting max. setting to 4.
• Turn sensor left to max.
• Press and hold the right tab with a screwdriver while turning handle to 4.
• Remove the screwdriver.