Danfoss P348 Operating guide

OperatingGuide
ECLComfort310,applicationP348

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................12
2.4Placingthetemperaturesensors................................17
2.5Electricalconnections.............................................19
2.6InsertingtheECLApplicationKey..............................26
2.7Checklist............................................................32
2.8Navigation,ECLApplicationKeyP348.........................33
3.0Dailyuse.........................................................38
3.1Howtonavigate...................................................38
3.2Understandingthecontrollerdisplay..........................39
3.3Ageneraloverview:Whatdothesymbolsmean?...........43
3.4Monitoringtemperaturesandsystem
components........................................................44
3.5Influenceoverview................................................45
3.6Manualcontrol.....................................................46
3.7Schedule............................................................47
4.0Settingsoverview............................................48
5.0Settings...........................................................51
5.1IntroductiontoSettings..........................................51
5.2Flowtemperature..................................................52
5.3Roomlimit..........................................................55
5.5Flow/powerlimit.................................................64
5.6Optimization........................................................68
5.7Controlparameters................................................74
5.9Application.........................................................82
5.11Tanktemperature..................................................93
5.13Alarm................................................................98
5.14Alarmoverview..................................................102
6.0Commoncontrollersettings............................103
6.1Introductionto‘Commoncontrollersettings’..............103
6.2Time&Date.......................................................104
6.3Inputoverview...................................................105
6.4Log.................................................................106
6.5Outputoverride..................................................107
6.6Keyfunctions.....................................................108
6.7System.............................................................110
7.0Miscellaneous................................................117
7.1ECA30/31setupprocedures.................................117
7.2Overridefunction................................................125
7.3Severalcontrollersinthesamesystem......................128
7.4Frequentlyaskedquestions....................................131
7.5Definitions........................................................133
7.6Type(ID6001),overview.......................................137
7.7ParameterIDoverview..........................................138
©Danfoss|2018.11VI.LV.G3.02|1
OperatingGuideECLComfort310,applicationP348

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwiththeECLApplicationKey P348(codeno.087H3843).
TheECLApplicationKeyP348containsonesubtype,P348.1, whichisaheatingandanadvancedDomesticHotWater(DHW) application.
SeetheInstallationGuideforelectricalconnections.
DescribedfunctionsarerealizedinECLComfort310whichalso allowsM-bus,ModbusandEthernet(Internet)communication. TheApplicationKeyP348complieswithECLComfort310 controllersasoffirmwareversion1.11.Thefirmware(controller software)isvisibleatstart-upofthecontrollerandin'Common controllersettings'in'System'.
UptotwoRemoteControlUnits,ECA30orECA31,canbe connected.
TheapplicationP348workswithadditionalInternalI/Omodules:
TheextensionmoduleECA32gives0-10Voltsignalforspeed controlofDHWrelatedchargingandcirculationpump.
TheextensionmoduleECA35gives0-10Voltsignalforspeed controlofDHWrelatedchargingandcirculationpump.ECA35 canalsogivePWM*signalforspeedcontrolofthelistedpumps.
Acirculationpumpcanbeconsideredasacirculatortoo.
TheECLComfort310workswitheitheroneECA32oroneECA
35.TheInternalI/Omoduleinquestionisplacedinthebasepart
oftheECLComfort310.
*PWM=PulseWidthModulation
TogetherwiththeECLComfort310theadditionalInternalI/O modulescanalsobeusedforextradatacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Digitalinput
Theset-upofinputtypecanbedonebymeansoftheDanfoss Software"ECLTool". Navigation:Danfoss.com>Products&Solutions>Products> DistrictHeatingandCooling>Documentation>Tools&Software >ECLTool.
TheURLis:
https://www.danfoss.com/en/service-and-support/downloads
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(codeno.087H3040)
ECLComfort310B,230volta.c.(codeno.087H3050)
ECLComfort310,24volta.c.(codeno.087H3044)
TheB-typehasnodisplayanddial.
2|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
TheB-typeisoperatedbymeansoftheremotecontrolunit ECA30/31:
ECA30(codeno.087H3200)
ECA31(codeno.087H3201)
InternalI/Omodules:
ECA32(codeno.087H3202)
ECA35(codeno.087H3205)
BasepartforECLComfort310,230voltand24volt:Codeno. 087H3230.
AdditionaldocumentationforECLComfort210and310,modules andaccessoriesisavailableonhttp://heating.danfoss.com/.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
VI.LV.G3.02
©Danfoss|2018.11|3
OperatingGuideECLComfort310,applicationP348
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
1
-
Circuit1Parameterno.
2
Circuit2Parameterno.
174
4|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents sorted,ifpossible,invariousgroupsbeforerecycling ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.LV.G3.02
©Danfoss|2018.11|5
OperatingGuideECLComfort310,applicationP348

2.0Installation

2.1Beforeyoustart

TheECLapplicationkeyP348containsonesubtype,P348.1.
Thisapplicationforheatingtemperaturecontrolandadvanced DHWtemperaturecontrolisveryflexible.
Theheatingcircuit:
P348.1,ex.ashowstworadiatorcircuitsinparallel,eachcircuit withitsownreturntemperaturesensorformonitoringpurpose. P348.1,ex.bshowsoneradiatorcircuitwithitsownreturn temperaturesensorformonitoringpurpose. P348.1,ex.cshowstworadiatorcircuitsinparallel,eachcircuit withitsownreturntemperaturesensorformonitoringpurpose. P348.1,ex.dshowsoneradiatorcircuitwithitsownreturn temperaturesensorformonitoringpurpose.
Temperaturecontrolofheatingcircuit:
Theflowtemperatureisadjustedaccordingtoyourrequirements. TheflowtemperaturesensorS3isthemostimportantsensorand mustbeconnected.DesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperatureS1and thedesiredroomtemperature. Ingeneral,thelowertheoutdoortemperature,thehigherthe desiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein‘Comfort’ or‘Saving’mode(twovaluesforthedesiredroomtemperature).In Savingmodetheheatingcanbereducedorswitchedofftotally. ThemotorizedcontrolvalveM2isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa. ThereturntemperatureS5canbelimited,forexamplenottobe toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted (typicallytoalowervalue),whichresultsinagradualclosingof themotorizedcontrolvalve.Furthermore,thereturntemperature limitationcanbedependentontheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedreturntemperature. Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Ifthemeasuredroomtemperature(viaECA30/31)doesnotequal thedesiredroomtemperature,thedesiredflowtemperaturecan beadjusted.
Thecirculationpump,P2,isONatheatdemandoratfrost protection. TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
ReturntemperaturesensorsS11andS12areusedformonitoring purposeonly. PressuresensorsS15andS16areusedformonitoringpurpose. Furthermore,analarmcanbeactivatedifthepressuregetshigher thanasetvalueorlowerthananothersetvalue.
P348.1,ex.a,heating(circuitsAandB)andDHWtemperaturecontrol. PumpsinDHWcircuitcanbe0–10Voltcontrolled.
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents: ECL310 ECA32
S1 S2 S3 S4
S5Returntemperaturesensor,circuit1 S6 S7 S8 S9 S10 S11Returntemperaturesensor,circuit1A S12Returntemperaturesensor,circuit1B S15 S16 F1 P1 V1
P2 P3 V3 M1 M2 A1
ECLComfort310controller Built-inextensionmodule,0-10Voutputsfor
pumpspeedcontrol Outdoortemperaturesensor Supplytemperaturesensor (mandatory)Flowtemperaturesensor,circuit1 (mandatory)DHWflowtemperaturesensor,circuit
2
(mandatory)Upperbuffertemperaturesensor Bufferflowtemperaturesensor Lowerbuffertemperaturesensor DHWcirculationreturntemperaturesensor Bufferreturntemperaturesensor
Supplyreturnpressuresensor Supplyflowpressuresensor Flowmeter(signaltype:Pulse) DHWbufferchargingpump(ON-OFFcontrolled) SpeedcontrolofDHWbufferchargingpump(0-
10V) Circulationpump(ON-OFFcontrolled),circuit1 DHWcirculationpump(ON-OFFcontrolled) SpeedcontrolofDHWcirculationpump(0-10V) Motorizedcontrolvalve(ON-OFFcontrolled) Motorizedcontrolvalve(3-pointcontrolled) Alarm
6|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
AconnectedfloworenergymeterbasedonM-bussignalcanlimit thefloworenergytoasetmaximumvalue.Furthermore,the limitationcanbeinrelationtotheoutdoortemperature.Typically, thelowertheoutdoortemperature,thehighertheacceptedflow/ power.
Thefrostprotectionmodemaintainsaselectableflowtemperature, forexample10°C.
TheheatingcircuitcanactasmasterandviatheECL485 communicationbusfulfiltheheatdemandfromslavecircuits.
Exerciseofcirculationpumpandcontrolvalveinperiodswithout heatingdemandcanbearranged.
TheDHW(DomesticHotWater)circuit:
P348.1,ex.aandP348.1,ex.brunwiththeextensionmodule ECA32only.Thisallowsforspeedcontrolbymeansofvoltage signalofchargingpumpP1/V1andcirculationpumpP3/V3.
P348.1,ex.candP348.1,ex.dcanrunwiththeextension moduleECA32(speedcontrol(bymeansofvoltagesignal)ofthe pumpsP1/V1andP3/V3)—orrunwiththeextensionmodule ECA35forspeedcontrol(bymeansofvoltageorPWMsignal)of thepumpsP1/V1andP3/V3.
Temperaturecontrolofbuffer:
ThedesiredDHWtemperatureatS4determinesthebuffer chargingprocedure.TheDHWtemperaturesensorS4andupper buffertemperaturesensorS6arethemostimportantsensorsand mustbeconnected.
ThedesiredbuffertemperatureatS6isbasedonthedesired DHWtemperatureatS4andaset"Demandoffset"(=Charging difference).
P4hasanON/OFFfunction.M1followsP4tobeeitherfullyopen orfullyclosed.
Startbufferchargingprocess:
1.BuffertemperatureS6temperaturegetslowerthan('Desired DHWtemperature'+'Demandoffset'+'Startdiff. ').
Anexample:60°C+6K+(-2K)=64°C
2.P4isswitchedON;M1iscommandedtoopen
P348.1,ex.b,heating(circuitA)andDHWtemperaturecontrol.Pumpsin DHWcircuitcanbe0–10Voltcontrolled.
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents: ECL310 ECA32
ECLComfort310controller Built-inextensionmodule,0-10Voutputsfor
pumpspeedcontrol S1 S2 S3 S4
Outdoortemperaturesensor
Supplytemperaturesensor
(mandatory)Flowtemperaturesensor,circuit1
(mandatory)DHWflowtemperaturesensor,circuit
2 S5Returntemperaturesensor,circuit1 S6 S7 S8 S9 S10
(mandatory)Upperbuffertemperaturesensor
Bufferflowtemperaturesensor
Lowerbuffertemperaturesensor
DHWcirculationreturntemperaturesensor
Bufferreturntemperaturesensor S11Returntemperaturesensor,circuit1A S15 S16 F1 P1 V1
Supplyreturnpressuresensor
Supplyflowpressuresensor
Flowmeter(signaltype:Pulse)
DHWbufferchargingpump(ON-OFFcontrolled)
SpeedcontrolofDHWbufferchargingpump(0-
10V) P2 P3 V3 M1 M2 A1
Circulationpump(ON-OFFcontrolled),circuit1
DHWcirculationpump(ON-OFFcontrolled)
SpeedcontrolofDHWcirculationpump(0-10V)
Motorizedcontrolvalve(ON-OFFcontrolled)
Motorizedcontrolvalve(3-pointcontrolled)
Alarm
VI.LV.G3.02
©Danfoss|2018.11|7
OperatingGuideECLComfort310,applicationP348
Stopbufferchargingprocess:
1.a
S6connectedand'Stopdiff. 'hasanegativevalue
BuffertemperatureS6temperaturegetshigherthan('Desired DHWtemperature'+'Demandoffset').
Anexample:60°C+6K=66°C
1.b
S6connectedand'Stopdiff. 'hasa
positivevalue:
BuffertemperatureS6temperaturegetshigherthan('Desired DHWtemperature'+'Demandoffset'+'Stopdiff.').
Anexample:60°C+6K+4K=70°C
1.c
S6andS8connectedand'Stopdiff.'hasa
negativevalue:
BuffertemperatureS6temperaturegetshigherthan('Desired DHWtemperature'+'Demandoffset')ANDS8temperature getshigherthan('DesiredDHWtemperature'+'Demandoffset' +'Stopdiff. ').
Anexample:S6higherthan(60°C+6K=66°C)ANDS8higher than(60°C+6K+(-8K)=58°C).
1.d
S6andS8connectedand'Stopdiff.'hasapositivevalue:
BuffertemperatureS6temperaturegetshigherthan('Desired DHWtemperature'+'Demandoffset')ANDS8temperature getshigherthan('DesiredDHWtemperature'+'Demandoffset' +'Stopdiff. ').
Anexample:S6higherthan(60°C+6K=66°C)ANDS8higher than(60°C+6K+(8K)=74°C).
2.P4isswitchedOFF;M1iscommandedtoclose
P348.1,ex.c,heating(circuitsAandB)andDHWtemperaturecontrol. PumpsinDHWcircuitcanbe0–10VoltorPWMcontrolled.
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents: ECL310 ECA32
ECLComfort310controller Built-inextensionmodule,0-10Voutputsfor
pumpspeedcontrol
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputsforpumpspeedcontrol S1 S2 S3 S4
Outdoortemperaturesensor
Supplytemperaturesensor
(mandatory)Flowtemperaturesensor,circuit1
(mandatory)DHWflowtemperaturesensor,circuit
2 S5Returntemperaturesensor,circuit1 S6 S7 S8 S9 S10
(mandatory)Upperbuffertemperaturesensor
Bufferflowtemperaturesensor
Lowerbuffertemperaturesensor
DHWcirculationreturntemperaturesensor
Bufferreturntemperaturesensor S11Returntemperaturesensor,circuit1A S12Returntemperaturesensor,circuit1B F1 P1 V1
Flowmeter(signaltype:Pulse)
DHWbufferchargingpump(ON-OFFcontrolled)
SpeedcontrolofDHWbufferchargingpump(0-
10V) P2 P3 V3 M1 M2 A1
Circulationpump(ON-OFFcontrolled),circuit1
DHWcirculationpump(ON-OFFcontrolled)
SpeedcontrolofDHWcirculationpump(0-10V)
Motorizedcontrolvalve(ON-OFFcontrolled)
Motorizedcontrolvalve(3-pointcontrolled)
Alarm
8|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
TemperaturecontrolofDHW:
ThedesiredDHWtemperatureatS4determinesthetemperature control. Bymeansofaweekschedule(upto3'Comfort'periods/day),the DHWcircuitcanbein'Comfort'or'Saving'mode(twodifferent temperaturevaluesforthedesiredDHWtemperatureatS4). TheDHWflowtemperaturesensorS4andtheDHWcirculation returntemperaturesensorS9arethemostimportantsensorsand mustbeconnected.IfS4isnotconnected,thecontrolpumpP1/ V1willstop.IfS9isnotconnected,theDHWcirculationpumpwill operateat100%speed.
ThecontrolpumpP1/V1isgraduallyincreasedinspeedwhenthe DHWflowtemperatureislowerthanthedesiredDHWtemperature andviceversa. ThesupplytemperatureS7isusedtocompensatetheproportional bandXpinordertoimprovethetemperaturecontrolatdifferent supplytemperatures.
TemperaturecontroloftheDHWcirculationpipeatS9ensuresthe desiredtemperaturebymeansofspeedcontrolofP3/V3. Aweekschedule(upto3'Comfort'periods/day)controlsthe DHWcirculationpumptobeONorOFF .IfinOFFmode,theDHW temperaturecontrolwillbedisabled.
ThecoldwaterflowsignalfromF1canbeusedtooverridethe controlvalveinordertooptimizetheDHWtemperaturecontrol. Thispro-activefunctionalitycompensatesforthedelaybeforethe flowtemperaturesensorS4measuresachangeintemperature. Ananti-bacteriafunctionfortheDHWcircuitisavailablefor activationonselecteddaysoftheweek.Theanti-bacteriafunction canbesettoincludetheDHWcirculation.
P348.1,ex.d,heating(circuitA)andDHWtemperaturecontrol.Pumpsin DHWcircuitcanbe0–10VoltorPWMcontrolled.
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents: ECL310 ECA32
ECLComfort310controller Built-inextensionmodule,0-10Voutputsfor
pumpspeedcontrol
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputsforpumpspeedcontrol S1 S2 S3 S4
Outdoortemperaturesensor
Supplytemperaturesensor
(mandatory)Flowtemperaturesensor,circuit1
(mandatory)DHWflowtemperaturesensor,circuit
2 S5Returntemperaturesensor,circuit1 S6 S7 S8 S9 S10
(mandatory)Upperbuffertemperaturesensor
Bufferflowtemperaturesensor
Lowerbuffertemperaturesensor
DHWcirculationreturntemperaturesensor
Bufferreturntemperaturesensor S11Returntemperaturesensor,circuit1A F1 P1 V1
Flowmeter(signaltype:Pulse)
DHWbufferchargingpump(ON-OFFcontrolled)
SpeedcontrolofDHWbufferchargingpump(0-
10V) P2 P3 V3 M1 M2 A1
Circulationpump(ON-OFFcontrolled),circuit1
DHWcirculationpump(ON-OFFcontrolled)
SpeedcontrolofDHWcirculationpump(0-10V)
Motorizedcontrolvalve(ON-OFFcontrolled)
Motorizedcontrolvalve(3-pointcontrolled)
Alarm
VI.LV.G3.02
©Danfoss|2018.11|9
OperatingGuideECLComfort310,applicationP348
P348,ingeneral
UptotwoRemoteControlUnits,ECA30/31,canbeconnectedto oneECLcontrollerinordertocontroltheECLcontrollerremotely.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL 485businordertoutilizecommonoutdoortemperaturesignal, timeanddatesignals. TheECLcontrollersintheECL485systemcanworkinmaster­slavesystem.
Whenconnectinganoverrideswitchorarelaycontacttoan unusedinputtheECL310'sschedulecanbeoverriddento:
Comfortmode
Savingmode
Frostprotectionmodeor
Constanttemperaturemode(keepingasetdesiredflow temperature).
ModbuscommunicationtoaSCADAsystemcanbeestablished.
Heat-meters: Upto5heat-meterscanbeconnectedtotheM-busterminals. M-busdatacanbetransferredtotheSCADAsystemviaModbus andTCP/IPtotheECLPortal.
AlarmA1(=relay6)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow temperature.
Ifatemperaturesensororitsconnectiondisconnects/short circuits.(See:Commoncontrollersettings>System>Raw inputoverview).
Ameasuredtemperaturecanbeoffsetadjusted,ifneeded.
10|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
PWM(PulseWidthModulation)
A200HzfrequencyisappliedtothePWMcontrolledpump.The dutycycle(thepercentageoftheperiodtime)determinesthe pumpspeed.
Pumpspeed,PWMor0–10Voltcontrolled
Sometypesofspeedcontrolledpumpsarelimitedtoaminimum speed,forexample30%(PWMor3.0Volt).Eveniftheapplied control%getslowerthan30%,thepumpspeedremainsonthe minimumlevel*. Furthermore,whentheappliedcontrol%getsbelow,forexample, 10%,thepumpswitchesOFF.Inordertogetthepumpswitched ONagain,theappliedcontrol%mustexceed20%.
Thisbehaviorcan,atlowloadoratoobigpump,causeunstable temperatureregulation.Toavoidthis,theP348hasafunction wheretheappliedcontrolsignalisconvertedintoapulsedsignal. Thepumpisshortlystoppedandthenstartedagain.Theresultisa pumpspeedcontrolalsobelowtheminimumspeedlevel. Theparameters"PWMperiod"(ID12565)and"Adapttime"(ID
12065)areusedforthisfunctionality.
*)Seethepumpmanufacturer'sdatasheet
Commissioning
WhentheP348applicationhasbeenuploadedtheECLComfort 310controllerstartsinManualmode.Thiscanbeusedtoverify correctconnectionsoftemperature,pressureandflowsensors. Alsoverifyingthecontrolledcomponentsforcorrectfunctionality canbedone.
Dependingonsystemtype,itmightbenecessarytochangesome factorysettingsindividuallyinordertooptimizethefunctionality.
Theapplicationkeymustbeinsertedinordertochangesettings.
Important:
Setthecorrectrunningtime"Mrun"oftheMotorizedControl ValveM2.(Circuit1>MENU>Settings>Controlparameters >Mrun).
SetaminimumspeedofP1/V1andensurethatthepumpruns constantly.(Circuit2>MENU>Settings>Controlpar.1>Vout min.).Seepumpmanufacturer'smanual.
Verifyifthespeedcontrolledpumpsshouldbereversed controlled.(Circuit2/3>MENU>Settings>Controlpar.> Reverseout).Seepumpmanufacturer'smanual.
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
VI.LV.G3.02
©Danfoss|2018.11|11
OperatingGuideECLComfort310,applicationP348

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
12|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
VI.LV.G3.02
©Danfoss|2018.11|13
OperatingGuideECLComfort310,applicationP348
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
14|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
VI.LV.G3.02
©Danfoss|2018.11|15
OperatingGuideECLComfort310,applicationP348
2.3.3MountingtheinternalI/OmoduleECA32orECA35
TheECA32module(ordercodeno.087H3202)orECA35module (ordercodeno.087H3205)canbeinsertedintotheECLComfort 310/310Bbasepartforadditionalinputandoutputsignalsin relevantapplications.
ECA32
ECA35
16|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348

2.4Placingthetemperaturesensors

2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
VI.LV.G3.02
©Danfoss|2018.11|17
OperatingGuideECLComfort310,applicationP348
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
18|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
ECL210/310
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
Maximumloadratings:
VI.LV.G3.02
Relayterminals
Triac(=electronic relay)terminals
4(2)A/230Va.c. (4Aforohmicload,2Afor inductiveload)
0,2A/230Va.c.
©Danfoss|2018.11|19
OperatingGuideECLComfort310,applicationP348
Electricalconnections,ECA32/ECA35
Connections,ingeneral.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
Maximumloadratings:
Terminals
ECA32ECA35
PWMOut1(52)
PWMOut2(53)
PWMOut3(54)
PWMOut4(55)
AnalogOut1(59)AnalogOut1(59)47kΩ*
AnalogOut2(60)AnalogOut2(60)47kΩ*
AnalogOut3(61)AnalogOut3(61)47kΩ*
*Thevalueisaminimum.
5kΩ*
5kΩ*
5kΩ*
5kΩ*
20|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
2.5.2Electricalconnections,Pt1000temperaturesensors
SeetheInstallationGuide(deliveredwiththeapplicationkey)for sensorandinputconnections.
P348
Sensor
S1
S2
S3
S4
S5Returntemperature
S6
S7
S8
S9
S10
Description
Outdoortemperaure sensor
Supplytemperature sensor
Flowtemperature sensor(heating)*
Flowtemperature sensor(DHW)*
sensor(heating)
Upperbuffer-tank temperaturesensor*
Buffer-tankflow temperaturesensor
Lowerbuffer-tank temperaturesensor
DHWcirculation temperaturesensor
Buffer-tankreturn temperaturesensor
Recommendedtype
ESMT
ESM-11/ ESMB/ ESMC/ ESMU
ESM-11/ ESMB/ ESMC/ ESMU
ESMB/ ESMU
ESM-11/ ESMB/ ESMC/ ESMU
ESMB/ ESMU
ESM-11/ ESMB/ ESMC/ ESMU
ESMB/ ESMU
ESM-11/ ESMB/ ESMC/ ESMU
ESM-11/ ESMB/ ESMC/ ESMU
Temperaturesensorsmustbeconnectedinordertohavethe desiredfunctionality.
*
Ifthesensorisnotconnectedorthesensorcableis short-circuited,themotorizedcontrolvalveorcontrolpump closes/stops(safetyfunction).
VI.LV.G3.02
©Danfoss|2018.11|21
OperatingGuideECLComfort310,applicationP348
ECA32
Sensor
S11Returntemperature
Description
sensor,heatingcircuitA
Recommendedtype
ESM-11/ ESMB/ ESMC/ ESMU
S12Returntemperature
sensor,heatingcircuitB
ESM-11/ ESMB/ ESMC/ ESMU
S13
S14
S15
Notused
Notused
Supplyreturnpressure sensor
S16
Supplyreturnpressure sensor
Temperaturesensorsmustbeconnectedinordertohavethe desiredfunctionality.
ECA35
Sensor
S11Returntemperature
Description
sensor,heatingcircuitA
Recommendedtype
ESM-11/ ESMB/ ESMC/ ESMU
S12Returntemperature
sensor,heatingcircuitB
ESM-11/ ESMB/ ESMC/ ESMU
Temperaturesensorsmustbeconnectedinordertohavethe desiredfunctionality.
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus). Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
22|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
2.5.3Electricalconnections,ECA30/31
Terminal ECL
Terminal ECA30/31
30 31
4
1 322 333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature sensor*
Type (recomm.)
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible toconnectanECA30/31toeachcircuit.Theelectricalconnections aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller ortoECLComfort210/296/310controllersinamaster-slavesystem.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
VI.LV.G3.02
©Danfoss|2018.11|23
OperatingGuideECLComfort310,applicationP348
ECA32/35 S12
Connectionofvoltagesignal(0–10V)forexternalcontrolofdesired DHWtemperature. Theappliedvoltagemust,asaminimum,be1Volt.
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
24|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
2.5.4Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Terminal
Description
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
2.5.5Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310:GalvanicisolatedModbusconnections
Type (recomm.)
Cable2x twistedpair
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
2.5.6Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard ECLComfort310:Onboard
VI.LV.G3.02
©Danfoss|2018.11|25
OperatingGuideECLComfort310,applicationP348

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
26|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
VI.LV.G3.02
©Danfoss|2018.11|27
OperatingGuideECLComfort310,applicationP348
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes','Date', 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
28|©Danfoss|2018.11
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
VI.LV.G3.02
©Danfoss|2018.11|29
OperatingGuideECLComfort310,applicationP348
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296or310)mustbeconfiguredwiththesameapplicationbut user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
30|©Danfoss|2018.11
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Factorysettingscanalwaysberestored.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210or310). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
VI.LV.G3.02
©Danfoss|2018.11|31
OperatingGuideECLComfort310,applicationP348

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
32|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348

2.8Navigation,ECLApplicationKeyP348

Navigation,applicationP348.1,Heating,circuit1
Home MENU
ScheduleSchedule
Settings
Sub-menu
IDnos.
Flow temperature
Roomlimit
Returnlimit
Flow/Actual powerlimitActuallimit
Optimization
11178 11177 11004 11182 11183 11015 11031 11032 11033 11034 11035 11036 11037 11085 11029 11028
11119 11117 11118 11116 11112 11113 11109 11115 11011 11012 11013 11014 11026 11020 11021 11179
Function
Heatcurve Temp.max. Temp.min. DesiredT Infl.-max. Infl.-min. Adapt.time HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority DHW,ret.Tlimit Con.T,ret.Tlim.
HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Pre-stop Basedon Totalstop Summer,cut-out
P348.1
P348.1
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
VI.LV.G3.02
©Danfoss|2018.11|33
OperatingGuideECLComfort310,applicationP348
Navigation,applicationP348.1,Heating,circuit1,continued
Home MENU
Settings
HolidayHoliday
Alarm
InfluenceoverviewDes.flowTInfluencesource
Sub-menu
IDnos.
Controlpar.
Application
Heatcut-out
Temp.monitor
S15pressurePressure
S16pressurePressure
Alarmoverview
11174 11184 11185 11186 11187 11189 11010 11017 11050 11500 11022 11023 11052 11077 11078 11040 11093 11141 11142 11393 11392 11179 11395 11397 11396 11398 11399
11147 11148 11149 11150
12614 12615 12617
11614 11615 11617
Function
Motorpr Xp Tn Mrun Nz Min.act.time ECAaddr. Demandoffset Pdemand SenddesiredT Pexercise Mexercise DHWpriority PfrostT PheatT Ppost-run Frostpr.T Ext.input Ext.mode Sum.start,day Sum.start,month Summer,cut-out Summer,filter Winterstart,day Win.start,month Winter,cut-out Winter,filter
Upperdifference Lowerdifference Delay Lowesttemp.
Alarmhigh Alarmlow Alarmtime-out
Alarmhigh Alarmlow Alarmtime-out
P348.1
P348.1
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
34|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
Navigation,P348.1,circuits2and3(DHW)
Home
MENU
Schedule
Schedulecirc.P
Settings
Alarm
Influenceoverview
IDnos.
Tanktemperature
Controlpar.1Xpactual
FlowmeterActual
Application Anti-bacteria Controlpar.,Pcirc.
Temp.monitor
Alarmoverview
Des.DHWT
12017 12195 12194 12178 12177
12185 12187 12165 12167 12171 12354 12565 12065
12114 12115 12500
13370 13126 13184 13185 13187 13165 13167 13171
12147 12148 12149 12150
Function
Demandoffset Startdifference Stopdifference Temp.max. Temp.min.
Tn Nz Voutmax. Voutmin. Reverseout CWinfluence PWMperiod Adapttime
Pulse Units SenddesiredT
Max.returnT Anti-bac.ret.T Xp Tn Nz Voutmax. Voutmin. Reverseout
Upperdifference Lowerdifference Delay Lowesttemp.
Influencesource
P348.1
Circuit
23
(
(
( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( (
(
((
((
VI.LV.G3.02
©Danfoss|2018.11|35
OperatingGuideECLComfort310,applicationP348
Navigation,P348.1,Commoncontrollersettings
Home
MENU
Time&Date
Inputoverview
Log
Outputoverride
Commoncontrollersettings
IDno.
OutdoorTLogtoday
Heatingflow&des.
HeatreturnT&limitLog2days
DHWflow&des.
TankTup.&des.
TankTup.&low.
Circ.returnT
SupplyT
ChargeT
S16pressure
Function
Selectable
OutdoorT
Outdooracc.T
HeatflowT
HeatreturnT
DHWflowT
Circ.returnT
TankupperT
TanklowerT
SupplyT
ChargeT
DHWreturnT
ReturnT,A
ReturnT,B
S15pressure
S16pressure
Logyesterday
Log4days
M2
P2
P4
V1
P1
V3
P3
A1
36|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
Navigation,Commoncontrollersettings,continued
Home
MENU
Keyfunctions
SystemECLversion
Commoncontrollersettings
IDno.
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet(ECLComfort310only)
Portalconfig(ECLComfort310only)
Function
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
Codeno.
Hardware
Software
Serialno.
Productiondate
Addresstype
ECLportal
Portalstatus
Portalinfo
M-busconfig(ECLComfort310only)
EnergyMeters (ECLComfort310only)
Rawinputoverview
SensoroffsetS1-S10offset
Alarm
Display
Communication
Language
60058
60059
State
5998
Command
5997
Baud
6000
M-busaddress
6002
Scantime
6001
Type
EnergyMeter1....5
S1-S10(S1-S18whenECA32/35isinstalled)
32:
Tsensordefect
Backlight
Contrast
2048
ECL485addr.
38
Modbusaddr.
39
Baud
2150
Servicepin
2151
Ext.reset
2050
Language
VI.LV.G3.02
©Danfoss|2018.11|37
OperatingGuideECLComfort310,applicationP348

3.0Dailyuse

3.1Howtonavigate

Younavigateinthecontrollerbyturningthedialleftorrightto thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay( youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One heatingcircuit()andonedomestichot-water(DHW)circuit(). Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
38|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348

3.2Understandingthecontrollerdisplay

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault display.Thefavoritedisplaywillgiveyouaquickoverviewofthe temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay selector( turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
Heatingcircuit
Overviewdisplay1informsabout: actualoutdoortemperature,controllermode, actualroomtemperature,desiredroomtemperature.
Overviewdisplay2informsabout: actualoutdoortemperature,trendinoutdoortemperature, controllermode,max.andmin.outdoortemperaturessince midnightaswellasdesiredroomtemperature.
Overviewdisplay3informsabout: date,actualoutdoortemperature,controllermode,time,desired roomtemperatureaswellasshowsthecomfortscheduleofthe currentday.
Overviewdisplay4informsabout: stateofthecontrolledcomponents,actualflowtemperature, (desiredflowtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredflowtemperature.
ThevalueabovetheV2symbolindicates0–100%oftheanalogue signal(0–10V).
Note:
Anactualflowtemperaturevaluemustbepresent,otherwisethe circuit'scontrolvalvewillclose.
Overviewdisplay1:Overviewdisplay2:
Overviewdisplay3:Overviewdisplay4:
Exampleofoverviewdisplaywith Influenceindication:
Dependentonthechosendisplay,theoverviewdisplaysforthe heatingcircuitinformyouabout:
•actualoutdoortemperature(-0.5)
•controllermode()
•actualroomtemperature(24.5)
•desiredroomtemperature(20.7°C)
•trendinoutdoortemperature(
)
•min.andmax.outdoortemperaturessincemidnight(
•date(23.02.2010)
•time(7:43)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M2,P2)
•actualflowtemperature(49°C),(desiredflowtemperature(31))
•returntemperature(24°C)(limitationtemperature(50))
VI.LV.G3.02
)
©Danfoss|2018.11|39
OperatingGuideECLComfort310,applicationP348
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Ifthetemperaturevalueisdisplayedas
"--"
thesensorinquestionisnotconnected.
"---"
thesensorconnectionisshort-circuited.
DHWcircuit
Overviewdisplay1informsabout: actualDHWtemperature,controllermode,desiredDHW temperatureaswellasthecomfortscheduleofthecurrentday.
Overviewdisplay2informsabout: stateofthecontrolledcomponents,actualDHWtemperature, (desiredDHWtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredDHWtemperature.
Dependentonchosendisplay,theoverviewdisplaysfortheDHW circuitinformyouabout:
•actualDHWtemperature(50.3)
•controllermode(
)
•desiredDHWtemperature(50°C)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M1,P1)
•actualDHWtemperature(50°C),(desiredDHWtemperature(50))
•returntemperature(--°C)(limitationtemperature(30))
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe nextpageconcerningsymbols).
Overviewdisplay1:Overviewdisplay2:
Exampleofoverviewdisplaywith Influenceindication:
40|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
Settingthedesiredroomtemperature
Thedesiredroomtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheheatingcircuit.
Action:Purpose:
Desiredroomtemperature
Confirm
Adjustthedesiredroomtemperature
Confirm
Thisoverviewdisplayinformsaboutoutdoortemperature,actual roomtemperatureaswellasdesiredroomtemperature.
Thedisplayexampleisforcomfortmode.Ifyouwanttochange thedesiredroomtemperatureforsavingmode,choosethemode selectorandselectsaving.
Examples:
20.5
21.0
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
SettingthedesiredDHWtemperature
ThedesiredDHWtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheDHWcircuit.
Action:Purpose:
DesiredDHWtemperature
Confirm
AdjustthedesiredDHWtemperature
Confirm
InadditiontotheinformationaboutdesiredandactualDHW temperature,thetoday'sscheduleisvisible.
Thedisplayexampleindicatesthatthecontrollerisinscheduled operationandincomfortmode.
Examples:
50
55
VI.LV.G3.02
©Danfoss|2018.11|41
OperatingGuideECLComfort310,applicationP348
Settingthedesiredroomtemperature,ECA30/ECA31
Thedesiredroomtemperaturecanbesetexactlyasinthe controller.However,othersymbolscanbepresentinthedisplay (pleasesee'Whatdothesymbolsmean?').
WiththeECA30/ECA31youcanoverridethedesiredroom temperaturesetinthecontrollertemporarilybymeansoftheoverride
functions:
42|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348

3.3Ageneraloverview:Whatdothesymbolsmean?

Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+) Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses Actuator,analoguecontrol
signal Pump/fanspeed
DamperON
Circuit
Controlled component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
DamperOFF
VI.LV.G3.02
©Danfoss|2018.11|43
OperatingGuideECLComfort310,applicationP348

3.4Monitoringtemperaturesandsystemcomponents

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Heatingcircuit
Theoverviewdisplayintheheatingcircuitensuresaquick overviewoftheactualand(desired)temperaturesaswellasthe actualstateofthesystemcomponents.
Displayexample:
49°C
(31)
24°C
(50)
DHWcircuit
TheoverviewdisplayintheDHWcircuitensuresaquickoverview oftheactualand(desired)temperaturesaswellastheactualstate ofthesystemcomponents.
Displayexample(heatexchanger):
50°C
(50)
(30)
Flowtemperature
Desiredflowtemperature Returntemperature
Returntemperaturelimitation
Flowtemperature
Desiredflowtemperature
--
Returntemperature:sensornotconnected
Returntemperaturelimitation
Displayexamplewithheatexchanger:
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures isthe'Inputoverview'whichisvisibleinthecommoncontroller settings(howtoenterthecommoncontrollersettings,see ‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured actualtemperatures,itisread-only.
44|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Themenugivesanoverviewoftheinfluencesonthedesired flowtemperature.Itdiffersfromapplicationtoapplicationwhich parametersarelisted.Itcanbehelpfulinaservicesituationto explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor moreparameters,itisindicatedbyasmalllinewitharrow-down, arrow-upordouble-arrow:
Arrow-down: Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up: Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow: Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline: Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor 'Roomlim. ' .Thismeansthattheactualroomtemperatureis higherthanthedesiredroomtemperaturewhichagainresultsina decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
VI.LV.G3.02
©Danfoss|2018.11|45
OperatingGuideECLComfort310,applicationP348

3.6Manualcontrol

Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich thesymbolsforthecontrolledcomponents(valve,pumpetc.)are visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe installation.Thecontrolledcomponents,valve,pumpetc.,canbe controlledforcorrectfunction.
Whenmanualcontrolisselectedforonecircuit,itisautomatically selectedforallcircuits!
Manualcontrolof0–10Volt/PWMcontrolledpumpspeed:
TheV1,V2andV3symbolshaveavalue(in%)whichcanbechanged. The%valueiscorrespondingtoavoltage/PWMintherange0–10 Volt/0-100%PWM.
46|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348

3.7Schedule

3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.Insomeapplications,however,theremightbemore thanoneschedule.Additionalschedulescanbefoundin‘Common controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose: Choose'MENU'inanyoftheoverview
displays Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays (inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort periodbysettingstartandstoptimestothesamevalue.
VI.LV.G3.02
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto 'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
©Danfoss|2018.11|47
OperatingGuideECLComfort310,applicationP348

4.0Settingsoverview

Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” . ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Heatcurve
Actual(actualfloworpower)
Actuallimit
Xpactual
Actual
Extendedheatcut-outsetting
Extendedwintercut-outsetting
Day
Starttime
Duration
DesiredT
DesiredT(Desiredflowtemperature)
ECAaddr.(ECAaddress,choiceofRemoteControlUnit)
Autosaving(savingtemp.dependentonoutdoortemp.)
Boost
Ramp(referenceramping)
Optimizer(optimizingtimeconstant)
Adapt.time(adaptiontime)
Demandoffset
Demandoffset(fortank(buffer)temperature)
Basedon(optimizationbasedonroom/outdoortemp.)
Totalstop
Pexercise(pumpexercise)
Mexercise(valveexercise)
Pre-stop(optimizedstoptime)
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
DHW,ret.Tlimit
HighToutX1(returntemp.limitation,highlimit,X-axis)
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
LowToutX2(returntemp.limitation,lowlimit,X-axis)
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
Ppost-run
Pdemand
DHWpriority(closedvalve/normaloperation)
Adapt.time(adaptationtime)
1x00453
1x01082
1x01168
1x01269
1x01370
1x01470
1x015
1x01782
1x01793
1x020
1x021
1x02283
1x02383
1x02672
1x02860
1x02961
1x03161
1x03261
1x03361
1x03462
1x03562
1x03662
1x03762
1x04084
1x05084
1x05284
1x065
Factorysettingsincircuit(s)
1
52
64
64
75
80
91
91
96
97
97
97
55
71
71
75
23
48|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
SettingIDPage
PfrostT(circulationpump,frostprotectiontemp.)
PheatT(heatdemand)
Priority(priorityforreturntemp.limitation)
Frostpr.T(frostprotectiontemp.)
Inputtype
Adapt.time(adaptationtime)
Filterconstant
Pulse
Units
Units
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Anti-bac.ret.T(Anti-bacteria,returntemperature)
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Upperdifference
Lowerdifference
Delay,example
Lowesttemp.
Voutmax.
Voutmin.
Reverseout
Motorpr.(motorprotection)
Temp.min.
Temp.min.(Minimumtemperature)
Temp.max.
Temp.max.(Maximumtemperature)
Summer,cut-out(limitforheatingcut-out)
Infl.-max.(roomtemp.limitation,max.)
Infl.-min.(roomtemp.limitation,min.)
Xp(proportionalband)
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
Min.act.time(min.activationtimegearmotor)
Stopdifference
Startdifference
CWinfluence(ColdWaterinfluence)
Max.returnT
SenddesiredT
1x07785
1x07885
1x08563
1x09385
1x10965
1x11265
1x11365
1x114
1x115
1x115
1x11666
1x117
1x11866
1x11966
1x126
1x141
1x14286
1x147
1x14899
1x149100
1x150100
1x165
1x16776
1x171
1x174
1x17754
1x177
1x178
1x17893
1x17972
1x18256
1x18356
1x18476
1x185
1x186
1x187
1x18978
1x19493
1x19594
1x35478
1x37078
1x50088
Factorysettingsincircuit(s)
1
80
65
80
66
75
85
99
75
76
76
93
54
77
77
77
23
VI.LV.G3.02
©Danfoss|2018.11|49
OperatingGuideECLComfort310,applicationP348
PWMperiod
Alarmhigh
Alarmlow
Alarmtime-out
SettingIDPage
1x56579
1x614100
1x615101
1x617101
Factorysettingsincircuit(s)
1
23
50|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348

5.0Settings

5.1IntroductiontoSettings

Descriptionsofsettings(parameter'sfunctions)aredividedinto groupsasusedintheECLComfort210/296/310controller's menustructure.Examples:"Flowtemperature" ,"Roomlimit"and soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto theparameter'sIDnumbers.Youmightcomeacrossdifferences betweentheorderinthisOperatingGuideandtheECLComfort 210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication subtypes.Thismeansthatyoumightnotseetherelatedparameter intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof thisOperatingGuide,whereparameter'ssettingrangesandfactory settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit …)covermultiplesubtypes.
SomeparameterdescriptionsrefertoDuctorFloworInlet temperaturebecausetheparametersinquestionareusedinother applicationstoo.
VI.LV.G3.02
©Danfoss|2018.11|51
OperatingGuideECLComfort310,applicationP348

5.2Flowtemperature

TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtotheoutdoortemperature.Thisrelationship iscalledtheheatcurve. Theheatcurveissetbymeansof6coordinatepoints.Thedesired flowtemperatureissetat6pre-definedoutdoortemperature values. Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Desiredflowtemperature
Outdoor
temp.
Desiredflowtemp.
A
BC
Your
settings
-30°C45°C75°C95°C
-15°C40°C60°C90°C
-5°C35°C50°C80°C 0°C32°C45°C70°C 5°C30°C40°C60°C
15°C25°C28°C35°C
A:Exampleforfloorheating B:Factorysettings C:Exampleforradiatorheating(highdemand)
MENU>Settings>Flowtemperature
Heatcurve
1
0.1...4.01.0
Theheatcurvecanbechangedintwoways:
1.Thevalueoftheslopeischanged(seeheatcurveexamples onnextpage)
2.Thecoordinatesoftheheatcurvearechanged
Changethevalueoftheslope:
Pushthedialtoenter/changetheslopevalueoftheheatcurve (example:1.0). Whentheslopeoftheheatcurveischangedbymeansoftheslope value,thecommonpointforallheatcurveswillbeadesiredflow temperature=24.6°Catanoutdoortemperature=20°Canda desiredroomtemperature=20.0°C.
Slopechanges
Coordinatechanges
Changethecoordinates:
Pushthedialtoenter/changethecoordinatesoftheheatcurve (example:-30,75). Theheatcurverepresentsthedesiredflowtemperaturesat differentoutdoortemperaturesandatadesiredroomtemperature of20°C. Ifthedesiredroomtemperatureischanged,thedesiredflow temperaturealsochanges: (DesiredroomT-20)×HC×2.5 where"HC"istheHeatCurveslopeand"2.5"isaconstant.
52|©Danfoss|2018.11
Thecalculatedflowtemperaturecanbeinfluencedbythe‘Boost’and ‘Ramp’functionsetc.
Example:
Heatcurve: Desiredflowtemp.:
Desiredroomtemp.: Calculation(22–20)×1.0×2.5=
Result:
Thedesiredflowtemperaturewillbecorrectedfrom50°Cto55°C.
1.0 50°C
22°C 5
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
Choosingaheatcurveslope
Theheatcurvesrepresentthedesiredflowtemperatureatdifferentoutdoortemperaturesandatadesiredroomtemperatureof20°C.
Thesmallarrows()indicate6differentoutdoortemperaturevaluesatwhichyoucanchangetheheatcurve.
TheECLComfort210/296/310controlstheDHWtemperature accordingtothedesiredflowtemperatureforexampleunderthe influenceofthereturntemperature.
ActualDHWtemp.
ThedesiredDHWtemperatureissetintheoverviewdisplay.
50.3:
50:
ActualDHWtemperature
DesiredDHWtemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DesiredDHW temp.
VI.LV.G3.02
©Danfoss|2018.11|53
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Flowtemperature
DesiredT(Desiredflowtemperature)
WhentheECLComfortisinoverridemode,type"Const.T",thedesiredflow temperaturecanbeset. A"Const.T"relatedreturntemperaturelimitationcanalsobeset.SeeMENU >Settings>Returnlimit>'Con.T,ret.Tlim. '
1x004
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flowtemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow temperaturewillnotbelowerthanthissetting.Adjustthefactory setting,ifrequired.
Overridemode
WhenECLComfortisinScheduledmode,acontact(switch)signalcan beappliedtoaninputinordertooverridetoComfort,Saving,Frost ProtectionorConstanttemperature.Aslongasthecontact(switch) signalisapplied,theoverrideisactive.
The"DesiredT"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor 'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn temperaturelimitation(see'Priority').
MENU>Settings>Flowtemperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired temperaturewillnotbehigherthanthissetting.Adjustthefactory setting,ifrequired.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
54|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348

5.3Roomlimit

Thissectionisonlyrelevantifyouhaveinstalledaroom temperaturesensororaRemoteControlUnit. Thecontrolleradjuststhedesiredflowtemperaturetocompensate forthedifferencebetweenthedesiredandtheactualroom temperature. Iftheroomtemperatureishigherthanthedesiredvalue,the desiredflowtemperaturecanbereduced. The'Infl.-max.'(Influence,max.roomtemp.)determineshow muchthedesiredflowtemperatureshouldbereduced. Usethisinfluencetypetoavoidatoohighroomtemperature.The controllerwillallowforfreeheatgains,i.e.solarradiationetc. Iftheroomtemperatureislowerthanthedesiredvalue,thedesired flowtemperaturecanbeincreased. The'Infl.-min.'(Influence,min.roomtemperature)determines howmuchthedesiredflowtemperatureshouldbeincreased. Usethisinfluencetoavoidatoolowroomtemperature. Atypicalsettingwillbe-4.0for'Infl.-max.'and4.0for'Infl.-min. '
Influence
‘Infl.-min.’(min.limitation)
Desiredroomtemperature Actualroomtemperature
‘Infl.-max. ’(max.limitation)
The‘Infl.-max.’and'Infl.-min. 'determinehowmuchtheroom temperatureshouldinfluencethedesiredflowtemperature.
Ifthe‘Infl. ’factoristoohighand/orthe‘ Adapt.time’toolow,thereis ariskofunstablecontrol.
Example1:
Theactualroomtemperatureis2degreestoohigh. The‘Infl.-max.’issetto-4.0. The‘Infl.-min.’issetto3.0. Result: Thedesiredflowtemperatureisdecreasedby2x-4.0=8.0degrees.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
Example2:
Theactualroomtemperatureis3degreestoolow. The‘Infl.-max.’issetto-4.0. The‘Infl.-min.’issetto3.0. Result: Thedesiredflowtemperatureisincreasedby3x3.0=9.0degrees.
VI.LV.G3.02
©Danfoss|2018.11|55
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Roomlimit
Adapt.time(adaptiontime)
Controlshowfasttheactualroomtemperatureadaptstothedesiredroom temperature(Icontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe'Adapt. time'.
Minor
Thedesiredroomtemperatureisadaptedquickly.
value: Major
Thedesiredroomtemperatureisadaptedslowly.
value:
MENU>Settings>Roomlimit
Infl.-max.(roomtemp.limitation,max.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (decreased)iftheactualroomtemperatureishigherthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
0.0:
-2.0:
-5.0:
-9.9:
Noinfluence Minorinfluence Mediuminfluence Maximuminfluence
1x015
Theadaptationfunctioncancorrectthedesiredroomtemperature withmax.8Kxheatcurveslopevalue.
1x182
=
X
#1#
#2#
#3#
Roomtemperature
=
Desiredroomtemperature
=
Negativeinfluence(1x082)whenactualroomtemp.getshigher thandesiredroomtemp.
=
Positiveinfluence(1x083)whenactualroomtemp.getslowerthan desiredroomtemp.
The‘Infl.-max.’and'Infl.-min. 'determinehowmuchtheroom temperatureshouldinfluencethedesiredflowtemperature.
Ifthe‘Infl. ’factoristoohighand/orthe‘ Adapt.time’toolow,thereis ariskofunstablecontrol.
Example
Theactualroomtemperatureis2degreestoohigh. The‘Infl.-max.’issetto-4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x-4.0x1.8) –14.4degrees.
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x-4.0x1): –8.0degrees.
56|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Roomlimit
Infl.-min.(roomtemp.limitation,min.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (increased)iftheactualroomtemperatureislowerthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
9.9:
5.0:
2.0:
0.0:
Maximuminfluence Mediuminfluence Minorinfluence Noinfluence
Example
1x183
Theactualroomtemperatureis2degreestoolow. The‘Infl.-min.’issetto4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x4.0x1.8)
14.4degrees.
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x4.0x1):
8.0degrees.
VI.LV.G3.02
©Danfoss|2018.11|57
OperatingGuideECLComfort310,applicationP348

5.4Returnlimit

Thereturntemperaturelimitationisbasedontheoutdoor temperature.Typicallyindistrictheatingsystemsahigherreturn temperatureisacceptedatadecreaseinoutdoortemperature.The relationshipbetweenthereturntemperaturelimitsandoutdoor temperatureissetintwocoordinates. Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .Thereturntemperaturecoordinatesaresetin 'HighlimitY2'and'LowlimitY1' . Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthecalculatedlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
X Y #X1# #X2# #Y1# #Y2#
=
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
DHWcircuit
Thereturntemperaturelimitationisbasedonaconstant temperaturevalue. Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthesetlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay. Seethesection"Monitoringtemperaturesandsystemcomponents" .
=
X #1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp. Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp. Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp. Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
58|©Danfoss|2018.11
Ifthe‘Infl. ’factoristoohighand/orthe‘ Adapt.time’toolow,thereis ariskofunstablecontrol.
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
Example,maximumreturntemperaturelimitation; returntemperaturegetshigherthanlimit
Whentheanti-bacteriaprocessisactive,thereturntemperature limitationisdisabled.
=
T
Y
X
#1#
#2#
#3#
#4#
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
VI.LV.G3.02
©Danfoss|2018.11|59
OperatingGuideECLComfort310,applicationP348
Example,minimumreturntemperaturelimitation; returntemperaturegetslowerthanlimit
=
T
Y
X
#1#
#2#
#3#
#4#
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
ThereturntemperaturelimitationfortheDHWcircuitisbasedonthe settingin'Limit(returntemp.limitation)' .
Theinfluencefactorsaresetintheheatingcircuit.
Ifthereturntemperaturelimitationvalueintheheatingcircuitis higherthanthereturntemperaturelimitationvalueintheDHWcircuit, thehighestvalueisused.
60|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Returnlimit
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
The"Con.T ,ret.Tlimit"isthereturntemperaturelimitationvaluewhenthe circuitissettooverridemodetype"Const.T"(=Constanttemperature).
SeeAppendix“ParameterIDoverview”
Value:Setthereturntemperaturelimitation
MENU>Settings>Returnlimit
DHW,ret.Tlimit
WhenanaddressedslaveisactiveinDHW-tankheating/charging,the returntemperaturelimitationinthemastercanbeset. Notes:
Themastercircuitmustbesettoreactonthedesiredflowtemperature intheslave(s).See"Demandoffset"(ID11017).
Theslave(s)mustbesettosendits/theirdesiredflowtemperatureto themaster.See"SenddesiredT"(ID1x500).
SeeAppendix“ParameterIDoverview”
OFF:
Noinfluencefromslaves.Thereturntemperature limitationisrelatedtosettingsin"Returnlimit" .
Value:
Returntemperaturelimitationvaluewhenslaveisin DHWtankheating/chargingoperation.
1x028
1x029
#1#=Master,exampleA266,address15 #2#=Slave,exampleA237,address9 #3#=Slave,exampleA367,address6
MENU>Settings>Returnlimit
HighToutX1(returntemp.limitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowreturntemperaturelimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Returnlimit
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'HighToutX1' .
SeeAppendix“ParameterIDoverview”
SomeexamplesofapplicationswithDHW-tankheating/chargingare:
•A217,A237,A247,A367,A377
1x031
1x032
ThecorrespondingXcoordinateissetin'HighToutX1' .
VI.LV.G3.02
©Danfoss|2018.11|61
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Returnlimit
LowToutX2(returntemp.limitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighreturntemperature limitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Returnlimit
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureishigherthanthecalculatedlimit.
1x033
1x034
1x035
Ifthe‘Infl. ’factoristoohighand/orthe‘ Adapt.time’toolow,thereis ariskofunstablecontrol.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetshigherthanthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetshigherthanthecalculatedlimit.
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Example
Thereturnlimitisactiveabove50°C. Theinfluenceissetto-2.0. Theactualreturntemperatureis2degreestoohigh. Result: Thedesiredflowtemperatureischangedby-2.0x2=-4.0degrees.
Normally,thissettingislowerthan0indistrictheatingsystemsto avoidatoohighreturntemperature.
Typically,thissettingis0inboilersystemsbecauseahigherreturn temperatureisacceptable(seealso'Infl.-min. ').
Example
1x036
Thereturnlimitisactivebelow50°C. Theinfluenceissetto-3.0. Theactualreturntemperatureis2degreestoolow. Result: Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo lowreturntemperature(seealso'Infl.-max.').
62|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled. Themin.flowtemperaturelimitisoverruled.
1x037
Theadaptationfunctioncancorrectthedesiredflowtemperature withmax.8K.
1x085
IfyouhaveaDHWapplication: Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication: Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
VI.LV.G3.02
©Danfoss|2018.11|63
OperatingGuideECLComfort310,applicationP348

5.5Flow/powerlimit

Heatingcircuit
Afloworenergymetercanbeconnected(M-bussignal)totheECL controllerinordertolimitthefloworconsumedpower.
Theflow/powerlimitationcanbebasedontheoutdoor temperature.Typically,indistrictheatingsystemsahigherflowor powerisacceptedatloweroutdoortemperatures.
Therelationshipbetweenthefloworpowerlimitsandtheoutdoor temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2'.
Thefloworpowercoordinatesaresetin'LowlimitY1'and'High limitY2' .Basedonthesesettings,thecontrollercalculatesthe limitationvalue.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyreducesthedesiredflowtemperaturetoobtain anacceptablemax.floworpowerconsumption.
X
Y
#X1#
#X2# #Y1#
#Y2#
=
Outdoortemperature
=
Limitation,floworpower
=
HighTout(1x119)
=
LowTout(1x118)
=
Lowlimit(1x117)
=
Highlimit(1x116)
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy meter.
=
X
Y
#1#
#2#
#3#
Ifthe‘Adapt.time’istoohigh,thereisariskofunstablecontrol.
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
64|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Flow/powerlimit
Actuallimit
Thevalueistheactualfloworpowerlimitation,basedonoutdoor temperatureandthesettingsin"HighToutX1","LowlimitY1" ,"LowTout X2"and"HighlimitY2".
MENU>Settings>Flow/powerlimit
Inputtype
Choiceofinputtypefromflow/energymeter
SeeAppendix“ParameterIDoverview”
OFF:
EM1-
Noinput
Flow/energymetersignalfromM-bus.
EM5:
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired limitation.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
1x109
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
MENU>Settings>Flow/powerlimit
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured value. Thehigherthevalue,themoredampening. Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value: Major
Higherdampening
value:
VI.LV.G3.02
1x113
©Danfoss|2018.11|65
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Flow/powerlimit
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Flowvaluesareexpressedasl/horm³/h PowervaluesareexpressedaskW,MWorGW.
MENU>Settings>Flow/powerlimit
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperatureset in'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Flow/powerlimit
1x115
Listforsettingrangeof'Units': l/h m³/h kW MW GW
1x116
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperaturesetin 'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Flow/powerlimit
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighflow/powerlimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Flow/powerlimit
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowflow/powerlimitation.
1x117
Thelimitationfunctioncanoverruletheset'Temp.min'ofthedesired flowtemperature.
1x118
1x119
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
66|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
VI.LV.G3.02
©Danfoss|2018.11|67
OperatingGuideECLComfort310,applicationP348

5.6Optimization

Thesection"Optimization"describesspecificapplicationrelated issues. Theparameters'Autosaving' ,'Boost','Optimizer','Totalstop'areall relatedtoheatingmodeonly. 'Summer,cut-out'determine,atrisingoutdoortemperature,the stopofheating.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
68|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Optimization
Autosaving(savingtemp.dependentonoutdoortemp.)
Belowthesetvaluefortheoutdoortemperature,thesavingtemperature settinghasnoinfluence.Abovethesetvaluefortheoutdoortemperature, thesavingtemperaturerelatestotheactualoutdoortemperature.The functionisrelevantindistrictheatinginstallationsinordertoavoidabig changeinthedesiredflowtemperatureafterasavingperiod.
SeeAppendix“ParameterIDoverview”
OFF:
Thesavingtemperaturedoesnotdependonthe outdoortemperature;thereductionis100%.
Value:Thesavingtemperaturedependsontheoutdoor
temperature.Whentheoutdoortemperatureisabove 10°C,thereductionis100%.Thelowertheoutdoor temperature,thelessthetemperaturereduction. Belowthesetvalue,thesavingtemperaturesetting hasnoinfluence.
Comforttemperature:
Thedesiredroomtemperaturein Comfortmode
Savingtemperature:
ThedesiredroomtemperatureinSaving mode
ThedesiredroomtemperaturesforComfortandSavingmodes aresetinthedisplayoverviews.
1x011
=
X
Y
#1#
#2#
#3#
Example:
Actualoutdoortemperature(T.out):
DesiredroomtemperaturesettinginComfortmode:
DesiredroomtemperaturesettinginSavingmode:
Settingin‘Autosaving’:
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
=
Desiredroomtemperature(°C),Comfortmode
=
Desiredroomtemperature(°C),Savingmode
=
Autosavingtemperature(°C),ID11011
–5°C
22°C
16°C
–15°C
Theconditionfortheoutdoortemperatureinfluence:
T.out.influence=(10-T.out)/(10-setting)= (10-(-5))/(10-(-15))= 15/25=0,6
ThecorrecteddesiredroomtemperatureinSavingmode: T.room.ref.Saving+(T.out.influencex(T.room.ref.Comfort­T.room.ref.Saving)) 16+(0,6x(22-16))=19,6°C
=
X
Y
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
VI.LV.G3.02
©Danfoss|2018.11|69
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Optimization
Boost
Shortenstheheating-upperiodbyincreasingthedesiredflowtemperature bythepercentageyouset.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theboostfunctionisnotactive. Thedesiredflowtemperatureisincreasedtemporarily
withthesetpercentage.
Inordertoshortentheheating-upperiodafterasaving temperatureperiod,thedesiredflowtemperaturecanbeincreased temporarily(max.1hour).Atoptimizingtheboostisactiveinthe optimizationperiod('Optimizer'). IfaroomtemperaturesensororanECA30/31isconnected,the booststopswhentheroomtemperatureisreached.
MENU>Settings>Optimization
Ramp(referenceramping)
Thetime(minutes)inwhichthedesiredflowtemperatureincreases graduallytoavoidloadpeaksintheheatsupply.
SeeAppendix“ParameterIDoverview”
1x012
1x013
OFF:
Value:
Therampingfunctionisnotactive. Thedesiredflowtemperatureisincreasedgraduallywith
thesetminutes.
Inordertoavoidloadpeaksinthesupplynetwork,theflow temperaturecanbesettoincreasegraduallyafteraperiodwith savingtemperature.Thiscausesthevalvetoopengradually.
X Y #1#
=
Time
=
Desiredflowtemperature
=
Rampingtime
=
Comforttemperature
=
Savingtemperature
70|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Optimization
Optimizer(optimizingtimeconstant)
Optimizesthestartandstoptimesforthecomforttemperatureperiodto obtainthebestcomfortatthelowestenergyconsumption. Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower theoutdoortemperature,thelatertheheatingcut-out. Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The calculatedstartandstoptimesarebasedonthesettingoftheoptimizing timeconstant.
SeeAppendix“ParameterIDoverview”
Adjusttheoptimizingtimeconstant.
Thevalueconsistsofatwodigitnumber.Thetwodigitshavethe followingmeaning(digit1=TableI,digit2=TableII).
OFF:
Nooptimization.Theheatingstartsandstopsatthe timessetintheschedule.
10...59:
SeetablesIandII.
TableI:
1x014
Systemtype
LeftdigitHeataccumulationofthe
building
Radiator
1-light
systems
2-medium
3-heavy
Floorheating
4-medium
systems
5-heavy
TableII:
RightdigitDimensioningtemperatureCapacity
-0-50°Clarge
·
-1
-45°C
···
-5
-25°C
normal
···
MENU>Settings>Optimization
Basedon(optimizationbasedonroom/outdoortemp.)
Theoptimizedstartandstoptimecanbebasedoneitherroomoroutdoor temperature.
SeeAppendix“ParameterIDoverview”
OUT:
Optimizationbasedonoutdoortemperature.Usethis settingiftheroomtemperatureisnotmeasured.
ROOM:
Optimizationbasedonroomtemperature,ifmeasured.
-9
Dimensioningtemperature:
Thelowestoutdoortemperature(usuallydeterminedbyyoursystem designerinconnectionwiththedesignoftheheatingsystem)atwhich theheatingsystemcanmaintainthedesignedroomtemperature.
Example
Thesystemtypeisradiator,andtheheataccumulationofthebuilding ismedium.
Theleftdigitis2. Thedimensioningtemperatureis-25°C,andthecapacityisnormal. Therightdigitis5. Result: Thesettingistobechangedto25.
1x020
-5°C
small
VI.LV.G3.02
©Danfoss|2018.11|71
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Optimization
Totalstop
Decidewhetheryouwantatotalstopduringthesavingtemperatureperiod.
1x021
SeeAppendix“ParameterIDoverview”
OFF:
Nototalstop.Thedesiredflowtemperatureisreduced accordingto:
•desiredroomtemperatureinsavingmode
•autosaving
ON:
Thedesiredflowtemperatureisloweredtothesetvalue in‘Frostpr. ’Thecirculationpumpisstoppedbutfrost protectionisstillactive,see'PfrostT' .
Totalstop=OFF
Totalstop=ON
X Y
=
Time
=
Desiredflowtemperature
=
Comforttemperature
=
Savingtemperature
=
Frostprotection
MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
Disabletheoptimizedstoptime.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Theoptimizedstoptimeisdisabled. Theoptimizedstoptimeisenabled.
Themin.flowtemperaturelimitation('Temp.min.')isoverruledwhen 'Totalstop'isON.
1x026
Example:OptimizationofComfortfrom07:00-22:00
=
X #1# #2# #3# #4# #5#
Time
=
Schedule
=
Prestop=OFF
=
Prestop=ON
=
Optimizedstart
=
Optimizedstop
72|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Optimization
Summer,cut-out(limitforheatingcut-out)
1x179
SeeAppendix“ParameterIDoverview”
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanthesetvalue.Thevalveclosesandafterthepost-run time,theheatingcirculationpumpstops.‘Temp.min.’willbe overruled.
TheheatingsystemswitchesONagainwhentheoutdoor temperatureandtheaccumulated(filtered)outdoortemperature becomelowerthanthesetlimit.
Thisfunctioncansaveenergy.
Setthevalueforoutdoortemperatureatwhichyouwantthe heatingsystemtoswitchOFF .
Summer,cut-out
=
X
Y
#1#
#2#
#3#
#4#
#5#
Time
=
Temperature
=
Actualoutdoortemperature
=
Cut-outtemperature(1x179)
=
Accummulated(filtered)outdoortemperature
=
Heatingenabled
=
Heatingdisabled
Theheatingcut-outisonlyactivewhenthecontrollermodeisin scheduledoperation.Whenthecut-outvalueissettoOFF,thereis noheatingcut-out.
VI.LV.G3.02
©Danfoss|2018.11|73
OperatingGuideECLComfort310,applicationP348

5.7Controlparameters

ControlofvalvesM1andM2
Themotorizedcontrolvalvesarecontrolledbymeansof3-point controlsignal. M1isanON/OFFvalve. M2isacontrolvalve.
Thewaterflowthroughthecontrolvalveismanagedbymeans ofanelectricactuator.Thecombination"actuator"and"control valve"isalsocalledmotorizedcontrolvalve.Theactuatorcanin thiswaygraduallyincreaseordecreasetheflowinordertochange thesuppliedenergy.Differenttypesofactuatorsareavailable.
Controlvalve Themotorizedcontrolvalveisopenedgraduallywhentheflow temperatureislowerthanthedesiredflowtemperatureandvice versa.
3-pointcontrolledactuator: Theelectricactuatorcontainsareversiblegear-motor.Electric "open"and"close"signalscomefromtheelectronicoutputsofthe ECLComfortcontrollerinordertomanagethecontrolvalve.The signalsareintheECLComfortcontrollerexpressedas"Arrow-up" (open)and"Arrow-down"(close)anddisplayedatthevalvesymbol. Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,shortopen-signalscomefromtheECL Comfortcontrollerinordertograduallyincreasetheflow.Bythis, theflowtemperaturewillalignwiththedesiredtemperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,shortclose-signalscomefromtheECLComfort controllerinordertograduallyreducetheflow.Again,theflow temperaturealignswiththedesiredtemperature. Neitheropen-signalsnorclose-signalswillcomeaslongastheflow temperaturecorrespondstothedesiredtemperature.
74|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Controlparameters
Xpactual
‘Xpactual’istheread-outoftheactualXp(proportionalband)basedon thesupplytemperature.Xpisdeterminedbysettingsrelatedtothesupply temperature.Typically,thehigherthesupplytemperature,thehighertheXp mustbeinordertoachieveastabletemperaturecontrol.
Xpsettingrange:
5...250K
Fixedsupplytemperaturesettings:65°Cand90°C Factorysettings:
(65,40)and(90,120)
Thismeansthatthe‘Xp’is40Kat65°Csupplytemperature,and ‘Xp’is120Kat90°C.
SetthedesiredXpvaluesatthetwofixedsupplytemperatures.
Ifthesupplytemperatureisnotmeasured(thesupplytemperature sensorisnotconnected),theXpvalueatthesetting65°Cisused.
MENU>Settings>Controlparameters
Adapt.time(adaptationtime)
Whenthepumpiscontrolledatlowspeed(inpulsedmode)theregulation canbedampened.Atoolowdampeningcanresultinunstabletemperature regulation.
1x065
SeeAppendix“ParameterIDoverview”
Low
Lowdampening
value: High
Highdampening
value:
MENU>Settings>Controlparameters
Anti-bac.ret.T(Anti-bacteria,returntemperature)
Whenanti-bacteriamodeisactiveintheDHWcircuit,theDHWcirculation circuitcanrunatasettemperature.Thesettingof'Anti-bac.ret.T'willnot causeachangeofthe'DesiredT'asanti-bacteriatemperature.
SeeAppendix“ParameterIDoverview”
VI.LV.G3.02
1x126
©Danfoss|2018.11|75
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Controlparameters
Voutmax.
Theoutputvoltagecanbelimitedtoamaximumvalue.
SeeAppendix“ParameterIDoverview”
Thevaluein%expressesthemaximumvoltagefortheoutputin question.
MENU>Settings>Controlparameters
Voutmin.
Theoutputvoltagecanbelimitedtoaminimumvalue.
SeeAppendix“ParameterIDoverview”
Thevaluein%expressestheminimumvoltagefortheoutputin question.
MENU>Settings>Controlparameters
1x165
Example
Asettingof60%meansthattheoutputvoltagewillbe6voltasa maximum.
1x167
Example:
Asettingof20%meansthattheoutputvoltagewillbe2voltasa minimum.
Thesetting'Reverseout'hasnoinfluenceonthe'Voutmax’or‘V outmin'settings.
The'Voutmin'settinghashigherprioritythan'Voutmax' .
Reverseout
Theanalogoutput(0-10volt)canbearisingorafallingvoltageforrising coolingdemand.
SeeAppendix“ParameterIDoverview”
OFF:
Theanalogoutputvoltagewillfallatarisingcooling demand.
ON:
Theanalogoutputvoltagewillriseatarisingcooling demand.
MENU>Settings>Controlparameters
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection increasesthelifetimeofallinvolvedcomponents.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation delayinminutes.
1x171
1x174
Recommendedforductsystemswithvariableload.
76|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Controlparameters
Xp(proportionalband)
1x184
SeeAppendix“ParameterIDoverview”
Settheproportionalband.Ahighervaluewillresultinastablebut slowcontroloftheflowtemperature.
Whenusingtheparameterforpumpspeedcontrol: Ahighervaluewillresultinastable,butslowcontrolofthespeed.
MENU>Settings>Controlparameters
Tn(integrationtimeconstant)
1x185
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast butwithlessstability.
Whenusingtheparameterforpumpspeedcontrol: Setahighervalue(inseconds)toobtainaslow,butstablereaction todeviations. Alowintegrationtimeconstantwillmakethecontrollerreactfast, butwithlessstability.
MENU>Settings>Controlparameters
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning timebymeansofastopwatch.
1x186
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Thesetting"Mrun"isnotpresentwhenthevalveiscontrolledby meansofa0-10voltsignal.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
VI.LV.G3.02
©Danfoss|2018.11|77
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Controlparameters
Nz(neutralzone)
Whentheactualflowtemperatureiswithintheneutralzone,thecontroller doesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh variationinflowtemperature.
Whenusingtheparameterforpumpspeedcontrol: Settheacceptabletemperaturedeviation. Whentheactualtemperatureiswithintheneutralzone,the controllerdoesnotchangethepumpspeed. .
MENU>Settings>Controlparameters
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear motor.
SeeAppendix“ParameterIDoverview”
1x187
Theneutralzoneissymmetricalaroundthedesiredflowtemperature value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis temperature.
SettingexampleValuex20ms
1x189
240ms 10200ms 501000ms
MENU>Settings>Controlparameters
CWinfluence(ColdWaterinfluence)
Thecoldwaterflow(measuredbyColdWatermeterF1)caninfluencethe DHWtemperaturecontrolbyoverridingthecontrolofthemotorizedcontrol valve.Bythis,thetemperaturecontrolispro-activeandcompensatesfor thedelaybeforetheflowtemperaturesensorS4measuresachangein temperature. Thevalueexpresseshowmany%of100liters/hourwilldoaninfluenceon themotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Low
Minorinfluence
value: High
Majorinfluence
value:
Thesettingshouldbekeptashighasacceptabletoincreasethe lifetimeoftheactuator(gearmotor).
1x354
78|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Controlparameters
Max.returnT
SettingthemaximumreturntemperaturevaluefortheDHWreturn circulationatS9. Whenthereturntemperaturegetslowerthanthesetvalue,thespeedofthe DHWcirculationpumpcanbeincreased.
1x370
SeeAppendix“ParameterIDoverview”
Value:Desiredmax.returntemperature.
MENU>Settings>Controlparameters
PWMperiod
Whenthepumpiscontrolledatlowspeed(inpulsedmode)thesetvalue reflectsthereactiontimeofthepump,thewaterflowandthetemperature sensor.Atoolowvaluecanresultinunstabletemperatureregulation.
1x565
SeeAppendix“ParameterIDoverview”
Value:
Reactiontime
IfyouwanttotunethePIregulationprecisely,youcanusethefollowingmethod:
Setthe‘Tn’(integrationtimeconstant)toitsmax.value(999sec.).
Decreasethevalueforthe‘Xp’(proportionalband)untilthesystemstartshunting(i.e.getsunstable)withaconstantamplitude(it mightbenecessarytoforcethesystembysettinganextremelowvalue).
Findthecriticaltimeperiodonthetemperaturerecorderoruseastopwatch.
Temp.
Criticaltimeperiod
Time
Thiscriticaltimeperiodwillbecharacteristicforthesystem,andyoucanevaluatethesettingsfromthiscriticalperiod. ‘Tn’=
0.85xcriticaltimeperiod
‘Xp’=
2.2xproportionalbandvalueinthecriticaltimeperiod
Iftheregulationseemstobetooslow,youcandecreasetheproportionalbandvalueby10%.Makesurethereisaconsumption whenyousettheparameters.
VI.LV.G3.02
©Danfoss|2018.11|79
OperatingGuideECLComfort310,applicationP348

5.8Flowmeter

Aflowmeter,F1,measurestheColdWaterflowtothe heat-exchanger.Thesignalformispulses.Thepulsesareapplied to"Pulsein1"ontheECA32/35module. Thewaterflowcanbedisplayedinl/h(liters/hour)orm3/h (cubicmeters/hour).
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flowmeter
Actual
Actualcoldwaterflow. Thevalueisbasedonthesetting"Pulse"(1x114)andappliedpulsesignal.
MENU>Settings>Flowmeter
Pulse
Thevaluetellshowmanypulsesfromtheflowmeterarerelatedtooneml (milli-liter)orl(liter). Thesettingdeterminestheread-outvaluein"Actual" . Anexample:Value20meansthat20pulsesrepresent1milli-literor1liter.
1-9999:
Numberofpulsestorepresentonemilli-literoroneliter
1x114
80|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Flowmeter
Units
Settingtheunit(milli-literorliter)forthepulsebasisanddesiredunit(l/hor m3/h)fortheread-outofactualflow.
Example1for"Pulse"and"Unit"settings:
1x115
Pulse
Units
75
ml,l/h
75pulsesfromflowmeterrepresents1ml(milli-liter) Read-outofactualflowwillbeexpressedasl/h(litersperhour) Ifappliedpulseshaveafrequencyof8Hz(8pulsespersecond) theread-outofactualflowwillbe: Literx3600x8/75=384l/h
Example2for"Pulse"and"Unit"settings:
Pulse
Units
75
l,l/h
75pulsesfromflowmeterrepresents1l(liter) Read-outofactualflowwillbeexpressedasl/h(litersperhour) Ifappliedpulseshaveafrequencyof8Hz(8pulsespersecond) theread-outofactualflowwillbe: Milli-literx3600x8/75=384ml/h=0.384l/h
Example3for"Pulse"and"Unit"settings:
Pulse
Units
75
ml,m3/h
75pulsesfromflowmeterrepresents1ml(milli-liter) Read-outofactualflowwillbeexpressedasm3/h(cubic metersperhour) Ifappliedpulseshaveafrequencyof8Hz(8pulsespersecond) theread-outofactualflowwillbe: Milli-literx3600x8/75=384ml/h =0.384l/h =0.000384m3/h =0.0m3/h
Example4for"Pulse"and"Unit"settings:
Pulse
Units
75
l,m3/h
75pulsesfromflowmeterrepresents1l(liter) Read-outofactualflowwillbeexpressedasm3/h(cubic metersperhour) Ifappliedpulseshaveafrequencyof8Hz(8pulsespersecond) theread-outofactualflowwillbe: Literx3600x8/75=384l/h =384l/h =0.384m3/h =0.4m3/h
VI.LV.G3.02
©Danfoss|2018.11|81
OperatingGuideECLComfort310,applicationP348

5.9Application

Thesection"Application"describesspecificapplicationrelated issues. Someoftheparameterdescriptionsareuniversalfordifferent applicationkeys.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Application
ECAaddr.(ECAaddress,choiceofRemoteControlUnit)
Decidestheroomtemperaturesignaltransferandcommunicationwiththe RemoteControlUnit.
SeeAppendix“ParameterIDoverview”
OFF:
NoRemoteControlUnit.Onlyroomtemperaturesensor, ifany.
A:
B:
RemoteControlUnitECA30/31withaddressA. RemoteControlUnitECA30/31withaddressB.
1x010
TheRemoteControlUnitmustbesetaccordingly(AorB).
82|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Application
Demandoffset
Thedesiredflowtemperatureinheatingcircuit1canbeinfluencedbythe demandforadesiredflowtemperaturefromanothercontroller(slave)or anothercircuit.
SeeAppendix“ParameterIDoverview”
OFF:
Thedesiredflowtemperatureincircuit1isnot influencedbythedemandofanyothercontroller(slave orcircuit2).
Value:
Thedesiredflowtemperatureisincreasedbytheset valuein‘Demandoffset’ ,ifthedemandoftheslave/ circuit2ishigher.
Heatingapplication
1x017
=
X
Y
#1#
#2#
#3#
Time
=
Desiredflowtemperatures
=
Demandoffset
=
Desiredflowtemperature,master
=
Desiredflowtemperature,slave
MENU>Settings>Application
Pexercise(pumpexercise)
Exercisesthepumptoavoidblockinginperiodswithoutheating/cooling demand.
Thefunctionof‘Demandoffset’cancompensateforheatlosses betweenmasterandslavecontrolledsystems.
'Demandoffset'withavalueistobeusedintheMastercontrolleronly.
Whensetting"Demandoffset"toavalue,thereturntemperature limitationwillreactaccordingtothehighestlimitationvalue(Heating /DHW).
1x022
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thepumpexerciseisnotactive.
ThepumpisswitchedONfor1minuteeverythirddayat noon(12:14hours).
VI.LV.G3.02
©Danfoss|2018.11|83
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Application
Mexercise(valveexercise)
Exercisesthevalvetoavoidblockinginperiodswithoutheating/cooling demand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thevalveexerciseisnotactive.
Thevalveopensfor7minutesandclosesfor7minutes everythirddayatnoon(12:00hours).
MENU>Settings>Application
Ppost-run
Heatingapplications:
ThecirculationpumpintheheatingcircuitcanbeONforanumberof minutes(m)afterheatingstop.Heatingstopiswhenthedesiredflow temperaturegetslowerthanthesettingin'PheatT'(IDno.1x078).
Coolingapplications:
ThecirculationpumpinthecoolingcircuitcanbeONforanumberof minutes(m)aftercoolingstop.Coolingstopiswhenthedesiredflow temperaturegetshigherthanthesettingin'PcoolT'(IDno.1x070). ThisPpost-runfunctioncanutilizetheremainingenergyinforexamplea heatexchanger.
SeeAppendix“ParameterIDoverview”
1x023
1x040
0:
Thecirculationpumpstopsimmediatelyafterheating orcoolingstop.
Value:
ThecirculationpumpisONforthesettimeafterheating orcoolingstop.
MENU>Settings>Application
Pdemand
Thecirculationpumpinthemastercircuitcanbecontrolledinrelationto themastercircuit'sdemandorslavecircuit'sdemand.
SeeAppendix“ParameterIDoverview”
Heatingapplications:
OFF:
ThecirculationpumpisONwhenthedesiredflow temperatureintheheatingcircuitishigherthanthe valuesetin'PheatT'.
ON:
ThecirculationpumpisONwhenthedesiredflow temperaturefromslavesishigherthanthevaluesetin 'PheatT'.
Coolingapplications:
OFF:
ThecirculationpumpisONwhenthedesiredflow temperatureinthecoolingcircuitislowerthanthevalue setin'PcoolT'.
ON:
ThecirculationpumpisONwhenthedesiredflow temperaturefromslavesislowerthanthevaluesetin 'PcoolT'.
1x050
Thecirculationpumpisalwayscontrolledaccordingtofrostprotection conditions.
84|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Application
DHWpriority(closedvalve/normaloperation)
Theheatingcircuitcanbeclosedwhenthecontrolleractsasslaveandwhen DHWheating/chargingisactiveinthemaster.
SeeAppendix“ParameterIDoverview”
OFF:
Theflowtemperaturecontrolremainsunchanged duringactiveDHWheating/charginginthemaster controller.
ON:
Thevalveintheheatingcircuitisclosed*duringactive DHWheating/charginginthemastercontroller.
*Thedesiredflowtemperatureissettothevaluesetin ‘Frostpr.T’
MENU>Settings>Application
PfrostT(circulationpump,frostprotectiontemp.)
Frostprotection,basedontheoutdoortemperature. Whentheoutdoortemperaturegetsbelowthesettemperaturevaluein‘P frostT’ ,thecontrollerautomaticallyswitchesONthecirculationpump(for exampleP1orX3)toprotectthesystem.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Nofrostprotection. CirculationpumpisONwhentheoutdoortemperature
isbelowthesetvalue.
1x052
Thissettingmustbeconsideredifthiscontrollerisaslave.
1x077
Undernormalconditions,yoursystemisnotfrostprotectedifyour settingisbelow0°CorOFF.
Forwater-basedsystems,asettingof2°Cisrecommended.
Iftheoutdoortemperaturesensorisnotconnectedandthefactory settinghasnotbeenchangedto'OFF' ,thecirculationpumpisalways ON.
MENU>Settings>Application
PheatT(heatdemand)
Whenthedesiredflowtemperatureisabovethesettemperaturein‘PheatT’ , thecontrollerautomaticallyswitchesONthecirculationpump.
1x078
SeeAppendix“ParameterIDoverview”
Value:
ThecirculationpumpisswitchedONwhenthedesired flowtemperatureisabovethesetvalue.
MENU>Settings>Application
Frostpr .T(frostprotectiontemp.)
SetthedesiredflowtemperatureattemperaturesensorS3toprotectthe systemagainstfrost(atheatingcut-out,totalstopetc.). WhenthetemperatureatS3getslowerthanthesetting,themotorized controlvalveopensgradually.
1x093
SeeAppendix“ParameterIDoverview”
Thevalveisfullyclosedaslongasthepumpisnotswitchedon.
Thefrostprotectiontemperaturecanalsobesetinyourfavorite displaywhenthemodeselectorisinfrostprotectionmode.
VI.LV.G3.02
©Danfoss|2018.11|85
OperatingGuideECLComfort310,applicationP348
Overridemodefunctions:
ThefollowingsettingsdescribethefunctioningeneralfortheECL Comfort210/296/310series.Theexplainedmodesaretypical andnotapplicationrelated.Theymightdifferfromtheoverride modesinyourapplication.
MENU>Settings>Application
Ext.input(externaloverride)
Choosetheinputfor'Ext.input'(externaloverride).Bymeansofaswitch thecontrollercanbeoverriddento‘Comfort’,'Saving' ,'Frostprotection'or 'Constanttemperature'mode.
1x141
SeeAppendix“ParameterIDoverview”
OFF:
S1...S16:
Noinputshavebeenselectedforexternaloverride. Inputselectedforexternaloverride.
IfS1...S6ischosenasoverrideinput,theoverrideswitchmusthave gold-platedcontacts. IfS7...S16ischosenasoverrideinput,theoverrideswitchcanbea standardcontact.
Seethedrawingsforconnectionexamplesofoverrideswitchand overriderelaytoinputS8.
S7...S16arerecommendedforoverrideswitch.
Example:Connectionofanoverrideswitch
Example:Connectionofanoverriderelay
IfECA32ismounted,also11...S16canbeused.
IfECA35ismounted,alsoS11orS12canbeused.
Chooseonlyanunusedinputforoverride.Ifanalreadyusedinputis appliedforoverride,thefunctionalityofthisinputisalsoneglected.
Seealso‘Ext.mode’.
86|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Application
Ext.mode(externaloverridemode)
ThemodeoverridecanbeactivatedforSaving,Comfort,Frostpr.or ConstantTmode. Foroverride,thecontrollermodemustbeinscheduledmode.
SeeAppendix“ParameterIDoverview”
Chooseanoverridemode:
SAVING:
Thecircuitinquestionisinsavingmodewhenthe overrideswitchisclosed.
COMFORT:
Thecircuitinquestionisincomfortmodewhenthe overrideswitchisclosed.
FROSTPR.:
TheheatingorDHWcircuitcloses,butisstillfrost protected.
CONSTANTT:
Thecircuitinquestioncontrolsaconstant temperature*)
*)
Seealso'DesiredT'(1x004),settingofdesiredflow temperature(MENU>Settings>Flowtemperature) Seealso'Con.T,ret.Tlim. '(1x028),settingofreturn temperaturelimitation(MENU>Settings>Return limit)
Theprocessdiagramsshowthefunctionality.
1x142
Seealso‘Ext.input’.
Example:OverridetoComfortmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Comfort) #3#=Time
Example:OverridetoSavingmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Saving) #3#=Time
Theresultofoverrideto'Saving'modedependsonthesettingin 'Totalstop'.
Totalstop=OFF:Heatingreduced Totalstop=ON:Heatingstopped
VI.LV.G3.02
©Danfoss|2018.11|87
OperatingGuideECLComfort310,applicationP348
Example:OverridetoFrostprotectionmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Frostpr.) #3#=Time
Example:OverridetoConstanttemperaturemode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Const.T) #3#=Time
The"Const.T"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
88|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Application
SenddesiredT
Whenthecontrolleractsasaslavecontrollerinamaster/slavesystem, informationaboutthedesiredflowtemperaturecanbesenttothemaster controllerviatheECL485bus. Stand-alonecontroller: Sub-circuitscansendthedesiredflowtemperaturetothemastercircuit.
SeeAppendix“ParameterIDoverview”
OFF:
Informationaboutthedesiredflowtemperatureisnot senttothemastercontroller.
ON:
Informationaboutthedesiredflowtemperatureissent tothemastercontroller.
1x500
Inthemastercontroller,'Demandoffset'mustbesettoavalueinorder toreactonadesiredflowtemperaturefromaslavecontroller.
Whenthecontrolleractsasaslave,itsaddressmustbe1,2,3...9in ordertosendthedesiredtemperaturetothemaster(seethesection ‘Miscellaneous’ ,‘Severalcontrollersinthesamesystem’).
VI.LV.G3.02
©Danfoss|2018.11|89
OperatingGuideECLComfort310,applicationP348

5.10Heatcut-out

MENU>Settings>Heatcut-out
Thesetting“Summercut-out”under“Optimization”fortheheating circuitinquestiondeterminesaheatingcut-outwhentheoutdoor temperatureexceedsthesetvalue.
Afilteringconstantforcalculatingtheaccumulatedoutdoor temperatureisinternallysettoavalueof"250".Thisfiltering constantrepresentsanaveragebuildingwithsolidouterandinner walls(bricks).
Anoptionfordifferentiatedcut-outtemperatures,basedona setsummerperiod,canbeutilizedinordertoavoiddiscomfort atfallingoutdoortemperature.Furthermore,separatefiltering constantscanbeset.
ThefactorysetvaluesforSummerperiodstartandWinterperiod startaresettosamedate:May,20(Date=20,Month=5). Thismeans:
"Differentiatedcut-outtemperatures"aredisabled(notactive)
Separate"Filteringconstant"valuesaredisabled(notactive)
Inordertoenabledifferentiated
cut-outtemperaturebasedonsummer/winterperiod
filteringconstants
thestartdatesfortheperiodsmustbedifferent.
90|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
5.10.1Differentiatedheatcut-out
Tosetdifferentiatedcut-outparametersforaheatingcircuitfor “Summer”and“Winter”goto“Heatcut-out”: (MENU>Settings>Heatcut-out) Thisfunctionisactivewhenthedatesfor“Summer”and“Winter” aredifferentinthe“Heatcut-out”menu.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Heatcut-out
Extendedheatcut-outsetting
ParameterIDSettingrange
Summerday
Summermonth
Summercut-out
Summerfilter
1x393
1x392
1x179
1x395
**
**
**
**
Factory
setting
SeeAppendix“ParameterIDoverview”
MENU>Settings>Heatcut-out
Extendedwintercut-outsetting
ParameterIDSettingrange
Winterday
Wintermonth
Wintercut-out
Winterfilter
1x397
1x396
1x398
1x399
**
**
**
**
Factory
SeeAppendix“ParameterIDoverview”
Theabovesettingsofthedatesforthecut-outfunctionareonly tobedoneintheheatingcircuit1andarevalidforotherheating circuitsinthecontrolleraswell,ifapplicable.
Thecut-outtemperaturesaswellasthefilterconstantaretobeset individuallyperheatingcircuit.
setting
Theheatingcut-outisonlyactivewhenthecontrollermodeisin scheduledoperation.Whenthecut-outvalueissettoOFF,thereis noheatingcut-out.
VI.LV.G3.02
©Danfoss|2018.11|91
OperatingGuideECLComfort310,applicationP348
5.10.2Summer/winterfilterconstant
Thefilterconstantof250isapplicableforaveragebuildings.A filterconstantof1iscloseswitchingaccordingtoactualoutdoor temperaturemeaninglowfiltering(very“light”building).
Afilterconstantof300isthentobechosenifabigfilteringis needed(veryheavybuilding).
Forheatingcircuitswheretheheatcut-outisdemandedaccording tothesameoutdoortemperatureforthewholeyear,butdifferent filteringiswanted,differentdateshavetobesetinthe“Heat cut-out”menuenablingaselectionofafilterconstantdifferent fromthefactorysetting. Thesedifferentvalueshavetobesetinboththe“Summer”and “Winter”menu.
92|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348

5.11Tanktemperature

MENU>Settings>Tanktemperature
Demandoffset(fortank(buffer)temperature)
ThedesiredtanktemperatureatS6isincreasedwithanumberofdegrees, basedonthedesiredDHWtemperatureatS4.
SeeAppendix“ParameterIDoverview”
Value:
Setthenumberofdegreestoincreasethedesiredtank (buffer)temperature.
MENU>Settings>Tanktemperature
Temp.min.(Minimumtemperature)
Settingthemin.tank(buffer)temperatureforthesystem.Thedesiredtank temperaturewillnotbelowerthanthissetting.
SeeAppendix“ParameterIDoverview”
Value:
Minimumtank(buffer)temperature
MENU>Settings>Tanktemperature
Temp.max.(Maximumtemperature)
Settingthemax.tank(buffer)temperatureforthesystem.Thedesiredtank temperaturewillnotbehigherthanthissetting.
1x017
1x177
1x178
SeeAppendix“ParameterIDoverview”
Value:
Maximumtank(buffer)temperature
VI.LV.G3.02
©Danfoss|2018.11|93
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Tanktemperature
Stopdifference
Settingthenumberofdegreesbelowthedesiredtank(buffer)temperature, andmeasuredbythelowertanktemperaturesensor,thatwillstopthetank charging. NOTE:Whenconditionforstop,relatedtothelowertanktemperature sensor,ispresent,thechargingstopisdonewhentheuppertank temperaturesensormeasuresahighertemperaturethanthestartdifference level.
SeeAppendix“ParameterIDoverview”
Value:
Differenceforcharging-stop
1x194
=
X
#1#
#2#
#3#
#4#
#5#
#6#
Example:
Desiredtank(buffer)temp.=
Desiredtank(buffer)temp.=
Stopdifference:
Result: Thetankchargingstopswhenthetemperaturemeasuredbythe lowertanktemperaturesensorS8getshigherthan51°C.
Time
=
Startdifference(ID12195)
=
DesiredDHWtemperature
=
Stopdifference(ID12194)
=
Actualtanktemperature,upper(S6)
=
Actualtanktemperature,lower(S8)
=
Tankchargingactivity
DesiredDHWtemp.+ 'Demandoffset'
55°C+4K=59°C
-8K
Whenonlyonetanktemperaturesensor(S6)isused,the'Stop difference'valueshouldtypicallybeapositivevalue.
94|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Tanktemperature
Startdifference
Settingthenumberofdegreesbelowthedesiredtank(buffer)temperature, andmeasuredbytheuppertanktemperaturesensor,thatwillstartthe tankcharging.
SeeAppendix“ParameterIDoverview”
Value:
Differenceforcharging-start
1x195
=
X
#1#
#2#
#3#
#4#
#5#
Example:
Desiredtank(buffer)temp.=
Desiredtank(buffer)temp.=
Startdifference:
Time
=
Demandoffset(ID12017)
=
DesiredDHWtemperature
=
Startdifference(ID12195)
=
Actualtanktemperature(S6)
=
Tankchargingactivity
DesiredDHWtemp.+ 'Demandoffset'
55°C+4K=59°C
-3K
Result: Thetankchargingstartswhenthetemperaturemeasuredbythe tanktemperaturesensor(upper)islowerthan56°C.
VI.LV.G3.02
©Danfoss|2018.11|95
OperatingGuideECLComfort310,applicationP348

5.12Anti-bacteria

OnselecteddaysduringtheweektheDHWtemperaturecan beincreasedinordertoneutralizebacteriaintheDHWsystem. ThedesiredDHWtemperature'DesiredT'(typically80°C)willbe presentfortheselectedday(s)andduration. Theanti-bacteriafunctionisnotactiveinfrostprotectionmode.
=
X Y #1# #2# #3# #4# #5#
Time
=
DesiredDHWtemperature
=
Duration
=
DesiredAnti-bacteriatemperaturevalue
=
DesiredAnti-bacteriatemperature
=
DesiredDHWtemperaturevalue
=
Starttime
TheDHWcirculationcircuitcanalsobesettocontrolan Anti-bacteriatemperature.Thiscontrolisactiveinparalleltothe DHWrelatedAnti-bacteriafunction.
Duringtheanti-bacteriaprocess,thereturntemperaturelimitationis notactive.
96|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Anti-bacteria
Day
Select(mark)theday(s)oftheweekwheretheanti-bacteriafunctionmust beactive.
=
Monday
M
=
Tuesday
T
=
Wednesday
W
=
Thursday
T
=
Friday
F
=
Saturday
S
=
Sunday
S
MENU>Settings>Anti-bacteria
Starttime
Setthestarttimefortheanti-bacteriafunction.
MENU>Settings>Anti-bacteria
Duration
Settheduration(minutes)fortheanti-bacteriafunction.
MENU>Settings>Anti-bacteria
DesiredT
SetthedesiredDHWtemperaturefortheanti-bacteriafunction.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theanti-bacteriafunctionisnotactive. DesiredDHWtemperatureduringtheanti-bacteria
functionperiod.
VI.LV.G3.02
©Danfoss|2018.11|97
OperatingGuideECLComfort310,applicationP348

5.13Alarm

Thesection"Alarm"describesspecificapplicationrelatedissues. ApplicationP348offersdifferenttypesofalarms:
Type:
1
1
2
2
Thealarmfunctionsactivatethealarmbellsymbol. ThealarmfunctionsactivateA1,whichisrelay6intheECLComfort 310controller:
Thealarmrelaycanactivatealamp,ahorn,aninputtoanalarm transmittingdeviceetc.
Thealarmsymbol/relayisactivated:
(type1)aslongasthealarmreasonispresent(automaticreset).
(type2)evenifthealarmreasondisappearsagain(manual reset).
Alarmtype1(flowtemperature): Iftheflowtemperaturedeviatesmorethanthesetdifferencesfrom thedesiredflowtemperature,thealarmsymbol/relaywillbe activatedafterasetdelay. Iftheflowtemperaturebecomesacceptable,thealarmsymbol/ relaywillbede-activated.
Description:
Actualflowtemperaturediffersfromthe desiredflowtemperature.
ActualpressureatS15and/orS16exceeds asethigh/lowlevel.
Anti-bacteriatemperatureisnotreached withinthe"Duration"time.
Disconnectionorshort-circuitingofa temperaturesensororitsconnection.
Alarmtype1(pressure): IfthepressureatS15and/orS16goesbeloworabovesetlevels, thealarmsymbol/relaywillbeactivatedafterasetdelay. Ifthepressurebecomesacceptable,thealarmsymbol/relaywill bede-activated.
Alarmtype2(Anti-bacteria): Iftheanti-bacteriatemperaturewasnotachievedwithinthe "Duration",thealarmsymbol/relaywillbeactivated.Thealarm mustbemanuallyreset.
Alarmtype2(temperaturesensors): Selectedtemperaturesensorscanbemonitored. Shouldtheconnectiontothetemperaturesensorbedisconnected, short-circuitedorthesensorgetsdefective,thealarmsymbol /relaywillbeactivated.Inthe"Rawinputoverview"(MENU> Commoncontrollersettings>System>Rawinputoverview)the sensorinquestionismarkedandthealarmcanbereset.
98|©Danfoss|2018.11
VI.LV.G3.02
OperatingGuideECLComfort310,applicationP348
Alarmoverview,list:
Alarm no.:
2
3
7
8
9
32
Description:
Temp.monitor,circuit1
Temp.monitor,circuit2
Pressure
Anti-bacteria,circuit3
Pressure
Tsensordefect
Alarm type:
1
1
1
1
1
2
Sensor ref.:
S3
S4
S15
S9
S16
all
Tofindthereasonforanalarm:
selectMENU
select‘Alarm’
select‘Alarmoverview’ .A"bell"willbeshownatthealarmin question.
Alarmoverview(example): 2:Max.temp. 3:Temp.monitor 32:Tsensordefect
Thenumbersinthe'Alarmoverview'refertothealarmnumber intheModbuscommunication.
Toresetanalarm: Whenthe"bell"ispresenttotherightofthealarmline,placethe cursoratthealarmlineinquestionandpressthedial.
Toresetalarm32: MENU>Commoncontrollersettings>System>Rawinput overview:Thesensorinquestionismarkedandthealarmcanbe reset.
MENU>Settings>Alarm
Upperdifference
Thealarmisactivatediftheactualflow/ducttemperatureincreasesmore thanthesetdifference(acceptabletemperaturedifferenceabovethedesired flow/ducttemperature).Seealso'Delay' .
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Therelatedalarmfunctionisnotactive. Thealarmfunctionisactiveiftheactualtemperature
getsabovetheacceptabledifference.
1x147
Upperdifference
=
X
=
Y
=
#1#
=
#2#
Time Temperature
Upperdifference Desiredflowtemperature
VI.LV.G3.02
©Danfoss|2018.11|99
OperatingGuideECLComfort310,applicationP348
MENU>Settings>Alarm
Lowerdifference
Thealarmisactivatediftheactualflow/ducttemperaturedecreasesmore thanthesetdifference(acceptabletemperaturedifferencebelowthedesired flow/ducttemperature).Seealso'Delay' .
SeeAppendix“ParameterIDoverview”
1x148
Lowerdifference
OFF:
Value:
Therelatedalarmfunctionisnotactive. Thealarmfunctionisactiveiftheactualtemperature
getsbelowtheacceptabledifference.
MENU>Settings>Alarm
Delay,example
Ifanalarmconditionfromeither'Upperdifference'or'Lowerdifference'is presentforalongertimethanthesetdelay(inminutes),thealarmfunction isactivated.
SeeAppendix“ParameterIDoverview”
Value:
Thealarmfunctionwillbeactivatedifthealarm conditionremainsafterthesetdelay.
=
X Y #1# #2#
1x149
Time
=
Temperature
=
Lowerdifference
=
Desiredflowtemperature
Delay,example
MENU>Settings>Alarm
Lowesttemp.
Thealarmfunctionwillnotbeactivatedifthedesiredflow/duct temperatureislowerthanthesetvalue.
SeeAppendix“ParameterIDoverview”
=
X Y #1# #2# #3# #4#
1x150
Ifthecauseofthealarmdisappears,thealarmindicationandoutput alsodisappear.
Time
=
Temperature
=
Lowerdifference
=
Desiredflowtemperature
=
Actualflowtemperature
=
Delay(ID1x149)
100|©Danfoss|2018.11
VI.LV.G3.02
Loading...