Danfoss P330 Operating guide

Operating Guide

ECL Comfort 310, application P330

1.0 Table of Contents

1.0

Table of Contents ...............................................

1

1.1

Important safety and product information. . . . . . . . . . . . . . . . . . . .

. 2

2.0

Installation ........................................................

5

2.1

Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 5

2.2

Identifying the system type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12

2.3

Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

31

2.4

Placing the temperature sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

35

2.5

Electrical connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

37

2.6

Inserting the ECL Application Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

50

2.7

Check list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

57

2.8

Navigation, ECL Application Key P330 . . . . . . . . . . . . . . . . . . . . . . . . .

58

3.0

Daily use .........................................................

63

3.1

How to navigate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

63

3.2

Understanding the controller display . . . . . . . . . . . . . . . . . . . . . . . . . .

64

3.3

A general overview: What do the symbols mean? . . . . . . . . . . .

68

3.4Monitoring temperatures and system

components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 3.5 Influence overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 3.6 Manual control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 3.7 Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

4.0

Settings overview ............................................

73

5.0

Settings...........................................................

75

5.1

Introduction to Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 75

5.2

Flow temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 76

5.3

Room limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 79

5.4

Return limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 81

5.5

Flow / power limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 85

5.6

Optimization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 88

5.7

Control parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 93

5.8

Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 96

5.9

Tank temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

103

5.10

Anti-bacteria. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

109

5.11

Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

111

6.0 Common controller settings............................

113

6.1 Introduction to ‘Common controller settings’ . . . . . . . . . . . . . . 113 6.2 Time & Date. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 6.3 Holiday . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 6.4 Input overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 6.5 Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 6.6 Output override. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 6.7 Key functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 6.8 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

7.0 Miscellaneous................................................

130

7.1 ECA 30 / 31 setup procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 7.2 Override function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 7.3 Several controllers in the same system . . . . . . . . . . . . . . . . . . . . . . 141 7.4 Frequently asked questions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144 7.5 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147 7.6 Type (ID 6001), overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151 7.7 Automatic / manual update of firmware. . . . . . . . . . . . . . . . . . . . . 152 7.8 Parameter ID overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153

© Danfoss | 2021.06

AQ120086463710en-010501 | 1

Operating Guide ECL Comfort 310, application P330

1.1 Important safety and product information

1.1.1 Important safety and product information

This Operating Guide is associated with ECL Application Key P330 (order code no. 087H3840).

The functions are realized in ECL Comfort 310 for advanced solutions, e.g. M-bus, Modbus and Ethernet (Internet) communication.

P330 applications can communicate (via Modbus connections) with the DECS 2.0 system (Danfoss Energy Control System). Please see DECS 2.0 related literature on the Danfoss website: http://danfoss.com

Search for ‘DECS 2.0’.

The application P330 complies with ECL Comfort controllers 310 as of software version 1.40 (visible at start-up of the controller and in ‘Common controller settings’ in ‘System’).

Additional documentation for ECL Comfort 310, modules and accessories is available on www.danfoss.com.

Application keys might be released before all display texts are translated. In this case the text is in English.

Safety Note

To avoid injury of persons and damages to the device, it is absolutely necessary to read and observe these instructions carefully.

Necessary assembly, start-up, and maintenance work must be performed by qualified and authorized personnel only.

Local legislations must be respected. This comprises also cable dimensions and type of isolation (double isolated at 230 V).

A fuse for the ECL Comfort installation is max. 10 A typically.

The ambient temperature ranges for ECL Comfort in operation are:

ECL Comfort 210 / 310: 0 - 55 °C

ECL Comfort 296: 0 - 45 °C.

Exceeding the temperature range can result in malfunctions.

Installation must be avoided if there is a risk for condensation (dew).

The warning sign is used to emphasize special conditions that should be taken into consideration.

2 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

Automatic update of controller software (firmware):

The software of the controller is updated automatically when the key is inserted (as of controller version 1.11 (ECL 210 / 310) and version 1.58 (ECL 296)). The following animation will be shown when the software is being updated:

Progress bar

During update:

Do not remove the KEY

If the key is removed before the hour-glass is shown, you have to start afresh.

Do not disconnect the power

If the power is interrupted when the hour-glass is shown, the controller will not work.

Manual update of controller software (firmware):

See the section "Automatic / manual update of firmware"

This symbol indicates that this particular piece of information should be read with special attention.

As this Operating Guide covers several system types, special system settings will be marked with a system type. All system types are shown in the chapter: 'Identifying your system type'.

°C (degrees Celsius) is a measured temperature value whereas K (Kelvin) often is used for temperature differences.

The ID no. is unique for the selected parameter.

Example

First digit

Second digit

Last three digits

 

 

 

 

11174

1

1

174

 

 

 

 

 

-

Circuit 1

Parameter no.

 

 

 

 

 

 

 

 

 

 

12174

1

2

174

 

 

 

 

 

-

Circuit 2

Parameter no.

 

 

 

 

 

 

 

 

 

 

If an ID description is mentioned more than once, it means that there are special settings for one or more system types. It will be marked with the system type in question (e.g. 12174 - A266.9).

AQ120086463710en-010501

© Danfoss | 2021.06 | 3

Operating Guide ECL Comfort 310, application P330

Parameters indicated with an ID no. like "1x607" mean a universal parameter.

x stands for circuit / parameter group.

Disposal Note

This symbol on the product indicates that it may not be disposed of as household waste.

It must be handed over to the applicable take-back scheme for the recycling of electrical and electronic equipment.

Dispose of the product through channels provided for this purpose.

Comply with all local and currently applicable laws and regulations.

4 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

2.0 Installation

2.1 Before you start

The 14 different applications P330.1 ...P330.14 are heating and DHW applications in various combinations.

The basic principles for a heating circuit

(example referring to P330.1)

Typically, the flow temperature is adjusted according to your requirements.

The flow temperature sensor S3 is the most important sensor. The desired flow temperature at S3 is calculated in the ECL controller, based on the outdoor temperature (S1) and the desired room temperature. The lower the outdoor temperature, the higher the desired flow temperature.

By means of a week schedule (up to 3 'Comfort' periods / day), the heating circuit can be in 'Comfort' or 'Saving' mode (two different temperature values for the desired room temperature). The motorized control valve M1 is opened gradually when the flow temperature is lower than the desired flow temperature and vice versa.

The return temperature (S5) can be limited, for example not to be too high. If so, the desired flow temperature at S3 can be adjusted (typically to a lower value), thus resulting in a gradual closing of the motorized control valve. Furthermore, the return temperature limitation can be dependent on the outdoor temperature.

Typically, the lower the outdoor temperature, the higher the accepted return temperature. In boiler-based heating supply the return temperature should not be too low (same adjustment procedure as above).

A flow / power limitation can be arranged by using an M-bus based signal from a flow / heat meter. Furthermore, the limitation can be in relation to the outdoor temperature.

If the measured room temperature, S13 or via the remote control unit ECA 30 does not equal the desired room temperature, the desired flow temperature can be adjusted.

General information:

In’ Saving’ mode the heating can be reduced or totally switched off. The ‘Frost protection’ mode maintains a selectable flow temperature, for example 10 °C.

The circulation pump (P2) is ON at heat demand or at frost protection.

The heating can be switched OFF when the outdoor temperature is higher than a selectable value.

The desired flow temperature of heating circuit 1 can, via S8, be controlled by means of an external voltage in the range 0-10 volt.

Exercise of circulation pump and control valve can be arranged.

Application P330.1:

The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.

All named components are connected to the ECL Comfort controller.

List of components, for example heating circuit 1 (P330.1): S1 Outdoor temperature sensor

S3 Flow temperature sensor

S5 (Optional) Return temperature sensor

S8 (Optional) External temperature control, not illustrated

S13 (Optional) Room temperature sensor

M1 Motorized control valve

P2 Circulation pump

A1 Alarm

AQ120086463710en-010501

© Danfoss | 2021.06 | 5

Operating Guide ECL Comfort 310, application P330

The basic principles for a DHW circuit, type 1

(example referring to P330.4)

By means of a week schedule (up to 3 'Comfort' periods / day), the DHW circuit can be in 'Comfort' or 'Saving' mode (two different temperature values for the desired DHW temperature at S10).

The DHW heating temperature sensor S9 is the most important sensor. If the measured DHW temperature (S10) gets lower than the desired DHW temperature, the DHW heating pump (P7) is switched ON. The motorized control valve (M3) is controlled in order to maintain the DHW heating temperature at S9. The DHW heating temperature is determined by the desired DHW temperature at S10 plus the charging difference. When the DHW heating temperature is reached, the DHW charging pump P5 is switched ON. The DHW heating temperature at S9 is typically 5–10 degrees higher than the desired DHW temperature.

DHW tank with 1 temperature sensor (S10):

When the measured DHW temperature (S10) gets higher than the desired DHW temperature, the DHW heating pump (P7) and the DHW charging pump (P5) are switched OFF. The post-run time can be set individually.

DHW tank with 2 temperature sensors (S10, upper and S2, lower):

If the measured DHW temperature (S10) gets higher than the desired DHW temperature and the temperature (at S2) gets higher than the cut-out temperature, the DHW heating pump (P7) and the DHW charging pump (P5) are switched OFF. The post-run time can be set individually.

The DHW circulation can be through the DHW tank (connection A) or through the heat-exchanger (connection B). The solution with connection A results in closing of the motorized control valve after the DHW tank charging procedure. The solution with connection B is used to compensate for the heat loss in the DHW circulation pipe. Furthermore, after DHW tank charging, the DHW heating temperature (at S9) is controlled according to the desired DHW temperature.

The return temperature (S7) can be limited, for example not to be too high. If so, the desired flow temperature at S9 can be adjusted (typically to a lower value), thus resulting in a gradual closing of the motorized control valve. In boiler-based heating supply the return temperature should not be too low (same adjustment procedure as above).

A flow / power limitation can be arranged by using an M-bus based signal from a flow / heat meter.

General information:

The ‘Frost protection’ mode maintains a selectable temperature, for example 10 °C.

An anti-bacteria function is available for activation on selected days of the week.

The outdoor temperature sensor S1 is used to protect the circulation circuit against frost.

The DHW circulation pump (P8) has a week schedule for up to 3 ON periods per day.

Application P330.4:

The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.

All named components are connected to the ECL Comfort controller.

List of components, for example DHW circuit, type 1 (P330.4): S1 Outdoor temperature sensor

S2 (Optional) Lower DHW tank temperature sensor

S7 (Optional) Return temperature sensor

S9 Flow temperature sensor

S10 Upper DHW tank temperature sensorr

M3 Motorized control valve

P5 DHW charging pump

P7 DHW heating pump

P8 DHW circulation pump

A1 Alarm

6 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

The basic principles for a DHW circuit, type 2

(example referring to P330.5)

By means of a week schedule (up to 3 'Comfort' periods / day), the DHW circuit can be in 'Comfort' or 'Saving' mode (two different temperature values for the desired DHW temperature at S10).

When the measured DHW temperature (S10) gets lower than the desired DHW temperature, the DHW heating pump (P7) and the DHW charging pump (P5) are switched ON.

DHW tank with 1 temperature sensor (S10):

When the measured DHW temperature (S10) gets higher than the desired DHW temperature, the DHW heating pump (P7) and the DHW charging pump (P5) are switched OFF. The post-run time can be set individually.

DHW tank with 2 temperature sensors (S10, upper and S2, lower):

When the measured DHW temperature (S10) gets higher than the desired DHW temperature and the temperature (at S2) gets higher than the cut-out temperature, the DHW heating pump (P7) and the DHW charging pump (P5) are switched OFF. The post-run time can be set individually.

The DHW circulation can be through the DHW tank (connection A) or through the heat-exchanger (connection B). The solution with connection A results in closing of the motorized control valve after the DHW tank charging procedure. The solution with connection B is used to compensate for the heat loss in the DHW circulation pipe. After DHW tank charging, the DHW charging pump P5 stops. The heating pump P7 continues being switched ON.

An anti-bacteria function is available for activation on selected days of the week.

The outdoor temperature sensor S1 is used to protect the circulation circuit against frost.

The DHW circulation pump (P8) has a week schedule for up to 3 ON periods per day.

General information:

The ‘Frost protection’ mode maintains a selectable temperature, for example 10 °C.

Application P330.5:

The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.

All named components are connected to the ECL Comfort controller.

List of components, for example DHW circuit, type 2 (P330.5): S1 Outdoor temperature sensor

S2 (Optional) Lower DHW tank temperature sensor

S10 Upper DHW tank temperature sensor

P5 DHW charging pump

P7 DHW heating pump

P8 DHW circulation pump

A1 Alarm

AQ120086463710en-010501

© Danfoss | 2021.06 | 7

Operating Guide ECL Comfort 310, application P330

The basic principles for the master circuit

(example referring to P330.10)

The desired flow temperature at S3 is adjusted according to the demand from the sub-circuits (heating and DHW circuits). The flow temperature sensor S3 is the most important sensor.

The motorized control valve M1 is opened gradually when the flow temperature is lower than the desired flow temperature and vice versa.

The return temperature (S5) can be limited, for example not to be too high. If so, the desired flow temperature at S3 can be adjusted (typically to a lower value), thus resulting in a gradual closing of the motorized control valve. Furthermore, the return temperature limitation can be dependent on the outdoor temperature.

Typically, the lower the outdoor temperature, the higher the accepted return temperature.

In boiler-based heating supply the return temperature should not be too low (same adjustment procedure as above).

The circulation pump (P1) is ON at heat demand or at frost protection.

General information:

The desired flow temperature of the master circuit can, via S8, be controlled by means of an external voltage in the range 0-10 volt.

Application P330.10:

The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.

All named components are connected to the ECL Comfort controller.

List of components, for example master circuit (P330.10): S1 Outdoor temperature sensor

S3 Flow temperature sensor

S5 (Optional) Return temperature sensor

S8 (Optional) External temperature control, not illustrated

M1 Motorized control valve

P1 Circulation pump

A1 Alarm

8 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

The basic principles for the master circuit with buffer

(example referring to P330.14)

The highest demand from the sub-circuits (heating and DHW circuits) plus a difference ('Demand offset') determine the desired buffer tank temperature at S11.

When the measured buffer tank temperature (S11) gets lower than the desired buffer tank temperature, the charging pump (P1) is switched ON.

The motorized control valve (M1) is controlled in order to maintain the buffer tank heating temperature at S3. The motorized control valve is opened gradually when the flow temperature is lower than the desired flow temperature and vice versa.

The flow temperature sensor S3 is the most important sensor.

The desired temperature at S3 is determined by the desired buffer tank temperature at S11 plus a charging temperature difference. The buffer tank heating temperature at S3 is typically 5–10 degrees higher than the desired buffer tank temperature.

Buffer tank with 1 temperature sensor (S11):

When the measured buffer tank temperature (S11) gets higher than the desired buffer tank temperature, the charging pump (P1) is switched OFF. The post-run time can be set.

Buffer tank with 2 temperature sensors (S11, upper and S12, lower):

When the measured upper buffer tank temperature (S11) gets higher than the desired buffer tank temperature and the measured lower buffer tank temperature (S12) gets higher than the cut-out temperature, the charging pump (P1) is switched OFF. The post-run time can be set.

If S12 is not connected, S11 will be used for ON and OFF control of the charging pump.

The return temperature (S5) can be limited, for example not to be too high. If so, the desired flow temperature at S3 can be adjusted (typically to a lower value), thus resulting in a gradual closing of the motorized control valve. Furthermore, the return temperature limitation can be dependent on the outdoor temperature.

Typically, the lower the outdoor temperature, the higher the accepted return temperature.

In boiler-based heating supply the return temperature should not be too low (same adjustment procedure as above).

When the measured buffer temperature (S11) gets higher than the desired buffer temperature, the desired temperature at S3 is lowered to typically 10 °C. Hereafter the charging pump (P1) is switched OFF. The post-run time can be set.

Application P330.14:

The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.

All named components are connected to the ECL Comfort controller.

List of components, for example master circuit with buffer (P330.14): S1 Outdoor temperature sensor

S3 Flow temperature sensor

S5 (Optional) Return temperature sensor

S8 (Optional) External temperature control, not illustrated

S11 Upper buffer tank temperature sensor

S12 (Optional) Lower buffer tank temperature sensor

M1 Motorized control valve

P1 Buffer tank charging pump

A1 Alarm

AQ120086463710en-010501

© Danfoss | 2021.06 | 9

Operating Guide ECL Comfort 310, application P330

Application P330.14:

In order to avoid a discharging of the DHW circuit (a higher DHW temperature goes to a lower buffer tank temperature) two parameters can be set:

*The parameter ("Tank start diff.", ID no 13192) determines an acceptable temperature difference between S10 and S11 in order to start the DHW charging.

*The parameter ("Tank stop diff.", ID no 13196) determines an acceptable temperature drop of the difference between S10 and S11 in order to stop the DHW charging.

General information:

The desired flow temperature of the master circuit can, via S8, be controlled by means of an external voltage in the range 0-10 volt.

10 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

Application P330.1 – P330.5:

Heating circuits 2, 3, 4 and DHW circuits can be connected after heating circuit 1. Circuit 1 acts as master and can react on the sub-circuits demand. If so, the desired flow temperature at S3 can be influenced by the desired flow temperature at S4, S9, S10 and DHW charging temperature respectively.

The desired flow temperature of heating circuit 1 can, via S8, be controlled by means of an external voltage in the range 0 - 10 volt.

Application P330.6 – P330.15:

Heating circuits and DHW circuits are typically connected after the master controlled circuit (M). When so, the desired flow temperature at S3 can be influenced by the desired flow temperature at S4, S9, S10 and DHW charging temperatures.

The desired flow temperature of the master circuit can, via S8, be controlled by means of an external voltage in the range 0 - 10 volt.

Application P330 in general:

Up to two Remote Control Units, the ECA 30 (one for each heating circuit) can be connected to one ECL controller in order to measure the room temperature and control the ECL controller remotely.

When the DHW circuit is active during the charging procedure, selected heating circuits can be closed in order to give higher priority to the DHW charging.

One or more connected flow or energy meters (based on M-bus signal) can limit the flow or energy to a set maximum (DHW circuits) and in relation to the outdoor temperature (heating and master circuits).

Unused input can, by means of an override switch, be used to override the schedule to a fixed 'Comfort' or 'Saving' mode.

Input S8 can be used to control the desired flow temperature of heating circuit 1 or the master circuit. The applied voltage signal in the range 0-10 volt is converted in the ECL controller to the desired flow temperature.

Modbus communication to a SCADA system can be established. The M-bus data can furthermore be transferred to the Modbus communication.

Alarm relay (R6) can be activated:

if the actual flow temperature differs from the desired flow temperature.

if a temperature sensor or its connection disconnects / short circuits. (See: Common controller settings > System > Raw input overview).

The controller is pre-programmed with factory settings that are shown in the ‘Parameter ID overview’ appendix.

AQ120086463710en-010501

© Danfoss | 2021.06 | 11

Operating Guide ECL Comfort 310, application P330

2.2 Identifying the system type

Sketch your application

The ECL Comfort controller series is designed for a wide range of heating, domestic hot-water (DHW) and cooling systems with different configurations and capacities. If your system differs from the diagrams shown here, you may want to make a sketch of the system about to be installed. This makes it easier to use the Operating Guide, which will guide you step-by-step from installation to final adjustments before the end-user takes over.

The ECL Comfort controller is a universal controller that can be used for various systems. Based on the shown standard systems, it is possible to configure additional systems. In this chapter you find the most frequently used systems. If your system is not quite as shown below, find the diagram which has the best resemblance with your system and make your own combinations.

See the Installation Guide (delivered with the application key) for application types / sub-types.

P330.1

Two heating circuits

12 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

Special settings for type P330.1:

Navigation:

Heating circuit (circuit 2)

Heating circuit 2 can be a sub-circuit to heating circuit 1. Settings for sub-circuit in order to send demand to circuit 1: MENU \ Settings \ Application: ‘Send desired T’

Heating circuit (circuit 1)

Settings for circuit 1 in order to react on demand in sub-circuit: MENU \ Settings \ Application: 'Demand offset'

* This value is added to the heat demand value from sub-circuit

ID no.:

Recommended setting:

1x500

ON

11017

3 K*

AQ120086463710en-010501

© Danfoss | 2021.06 | 13

Operating Guide ECL Comfort 310, application P330

P330.2

Three heating circuits

Special settings for type P330.2:

Navigation:

Heating circuit (circuit 2 and 3)

Heating circuit 2 and 3 can be sub-circuits to heating circuit 1. Settings for sub-circuit(s) in order to send demand to circuit 1: MENU \ Settings \ Application: 'Send desired T'

Heating circuit (circuit 1)

Settings for circuit 1 in order to react on demand in sub-circuit(s): MENU \ Settings \ Application: 'Demand offset'

ID no.:

Recommended setting:

1x500

ON

11017

3 K*

* This value is added to the heat demand value from sub-circuit(s)

14 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

P330.3

Four heating circuits. The MCV in circuit 4 is controlled by 0 – 10 V.

Special settings for type P330.3

Navigation:

Heating circuit (circuit 2, 3 and 4)

Heating circuit 2, 3 and 4 can be sub-circuits to heating circuit 1. Settings for sub-circuit(s) in order to send demand to circuit 1: MENU \ Settings \ Application: 'Send desired T'

Heating circuit (circuit 1)

Settings for circuit 1 in order to react on demand in sub-circuit(s): MENU \ Settings \ Application: 'Demand offset'

ID no.:

Recommended setting:

1x500

ON

11017

3 K*

* This value is added to the heat demand value from sub-circuit(s)

AQ120086463710en-010501

© Danfoss | 2021.06 | 15

Danfoss P330 Operating guide

Operating Guide ECL Comfort 310, application P330

P330.4

Two heating circuits and one DHW charging circuit with controlled heating temperature.

Special settings for type P330.4:

Navigation:

ID no.:

Recommended setting:

Heating circuit 2 and DHW circuit

Heating circuit 2 and the DHW circuit can be sub-circuits to heating circuit 1. Settings for sub-circuit(s) in order to send demand to circuit 1:

MENU \ Settings \ Application: 'Send desired T'

Heating circuit (circuit 1)

Settings for circuit 1 in order to react on demand in sub-circuit(s): MENU \ Settings \ Application: 'Demand offset'

* This value is added to the heat demand value from sub-circuit(s)

DHW circulation pipe

The DHW circulation pipe can be connected to the DHW tank at 'A' for internal circulation or to the heat exchanger at 'B' for external circulation.

1x500

ON

11017

3 K*

(Internal DHW circulation) MENU \ Settings \ Application: 'Cont. T control'

1x054

OFF

(External DHW circulation) MENU \ Settings \ Application: 'Cont. T control'

1x054

ON

16 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

P330.5

Three heating circuits and one DHW charging circuit.

Special settings for type P330.5

Navigation:

Heating circuit 2 and 3 and DHW circuit

Heating circuit 2 and 3 and the DHW circuit can be sub-circuits to heating circuit 1.

Settings for sub-circuit(s) in order to send demand to circuit 1:

MENU \ Settings \ Application: 'Send desired T'

Heating circuit (circuit 1)

Settings for circuit 1 in order to react on demand in sub-circuit(s): MENU \ Settings \ Application: 'Demand offset'

* This value is added to the heat demand value from sub-circuit(s)

DHW circulation pipe

The DHW circulation pipe can be connected to the DHW tank at 'A' for internal circulation or to the heat exchanger at 'B' for external circulation.

(Internal DHW circulation) MENU \ Settings \ Application: 'Cont. T control'

ID no.:

Recommended setting:

1x500

ON

11017

3 K*

1x054

OFF

(External DHW circulation) MENU \ Settings \ Application: 'Cont. T control'

1x054

ON

AQ120086463710en-010501

© Danfoss | 2021.06 | 17

Operating Guide ECL Comfort 310, application P330

P330.6

One master circuit and one heating circuit as sub-circuit.

Special settings for type P330.6:

Navigation:

The master circuit reacts on demand in the sub-circuit.

Sub-circuit

Settings for sub-circuit in order to send demand to master circuit: MENU \ Settings \ Application: 'Send desired T'

Master circuit

Settings for master circuit in order to react on demand in sub-circuit: MENU \ Settings (M) \ Application: 'Demand offset'

ID no.:

Recommended setting:

1x500

ON

1x017

3 K*

* This value is added to the heat demand value from sub-circuit

18 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

P330.7

One master circuit and two heating circuits as sub-circuits.

Special settings for type P330.7

Navigation:

The master circuit reacts on demand in the sub-circuit(s).

Sub-circuit(s)

Settings for sub-circuit(s) in order to send demand to master circuit: MENU \ Settings \ Application: 'Send desired T'

Master circuit

Settings for master circuit in order to react on demand in sub-circuit(s): MENU \ Settings (M) \ Application: 'Demand offset'

ID no.:

Recommended setting:

1x500

ON

1x017

3 K*

* This value is added to the heat demand value from sub-circuit(s)

AQ120086463710en-010501

© Danfoss | 2021.06 | 19

Operating Guide ECL Comfort 310, application P330

P330.8

One master circuit and three heating circuits as sub-circuits. The MCV in circuit 3 is controlled by 0 – 10 V.

Special settings for type P330.8

Navigation:

The master circuit reacts on demand in the sub-circuit(s).

Sub-circuit(s)

Settings for sub-circuit(s) in order to send demand to master circuit: MENU \ Settings \ Application: 'Send desired T'

Master circuit

Settings for master circuit in order to react on demand in sub-circuit(s): MENU \ Settings (M) \ Application: 'Demand offset'

ID no.:

Recommended setting:

1x500

ON

1x017

3 K*

* This value is added to the heat demand value from sub-circuit(s)

20 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

P330.9

One master circuit, a heating circuit and a DHW charging circuit with controlled heating temperature as sub-circuits.

AQ120086463710en-010501

© Danfoss | 2021.06 | 21

Operating Guide ECL Comfort 310, application P330

Special settings for type P330.9

Navigation:

The master circuit reacts on demand in the sub-circuit(s).

Sub-circuit(s)

Settings for sub-circuit(s) in order to send demand to master circuit: MENU \ Settings \ Application: 'Send desired T'

Master circuit

Settings for master circuit in order to react on demand in sub-circuit(s): MENU \ Settings (M) \ Application: 'Demand offset'

* This value is added to the heat demand value from sub-circuit(s)

DHW circulation pipe

The DHW circulation pipe can be connected to the DHW tank at 'A' for internal circulation or to the heat exchanger at 'B' for external circulation.

(Internal DHW circulation) MENU \ Settings \ Application: 'Cont. T control' (External DHW circulation) MENU \ Settings \ Application: 'Cont. T control'

ID no.:

Recommended setting:

1x500

ON

1x017

3 K*

1x054

OFF

1x054

ON

22 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

P330.10

One master circuit, one heating circuit, one DHW charging circuit with controlled heating temperature and one DHW charging circuit as sub-circuits.

Special settings for type P330.10

Navigation:

The master circuit reacts on demand in the sub-circuit(s).

Sub-circuit(s)

Settings for sub-circuit(s) in order to send demand to master circuit: MENU \ Settings \ Application: 'Send desired T'

Master circuit

Settings for master circuit in order to react on demand in sub-circuit(s): MENU \ Settings (M) \ Application: 'Demand offset'

* This value is added to the heat demand value from sub-circuit(s)

DHW circulation pipe

The DHW circulation pipe can be connected to the DHW tank at 'A' for internal circulation or to the heat exchanger at 'B' for external circulation.

(Internal DHW circulation) MENU \ Settings \ Application: 'Cont. T control' (External DHW circulation) MENU \ Settings \ Application: 'Cont. T control'

ID no.:

Recommended setting:

1x500

ON

1x017

3 K*

1x054

OFF

1x054

ON

AQ120086463710en-010501

© Danfoss | 2021.06 | 23

Operating Guide ECL Comfort 310, application P330

P330.11

One master circuit, two heating circuits and one DHW charging circuit as sub-circuits.

Special settings for type P330.11

Navigation:

The master circuit reacts on demand in the sub-circuit(s).

Sub-circuit(s)

Settings for sub-circuit(s) in order to send demand to master circuit: MENU \ Settings \ Application: 'Send desired T'

Master circuit

Settings for master circuit in order to react on demand in sub-circuit(s): MENU \ Settings (M) \ Application: 'Demand offset'

* This value is added to the heat demand value from sub-circuit(s)

DHW circulation pipe

The DHW circulation pipe can be connected to the DHW tank at 'A' for internal circulation or to the heat exchanger at 'B' for external circulation.

(Internal DHW circulation) MENU \ Settings \ Application: 'Cont. T control' (External DHW circulation) MENU \ Settings \ Application: 'Cont. T control'

ID no.:

Recommended setting:

1x500

ON

1x017

3 K*

1x054

OFF

1x054

ON

24 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

P330.12

One master circuit, three heating circuits and one DHW charging circuit as sub-circuits. The MCV in circuit 4 is controlled by 0 – 10 V.

AQ120086463710en-010501

© Danfoss | 2021.06 | 25

Operating Guide ECL Comfort 310, application P330

Special settings for type P330.12

Navigation:

The master circuit reacts on demand in the sub-circuit(s).

Sub-circuit(s)

Settings for sub-circuit(s) in order to send demand to master circuit: MENU \ Settings \ Application: 'Send desired T'

Master circuit

Settings for master circuit in order to react on demand in sub-circuit(s): MENU \ Settings (M) \ Application: 'Demand offset'

* This value is added to the heat demand value from sub-circuit(s)

DHW circulation pipe

The DHW circulation pipe can be connected to the DHW tank at 'A' for internal circulation or to the heat exchanger at 'B' for external circulation.

(Internal DHW circulation) MENU \ Settings \ Application: 'Cont. T control' (External DHW circulation) MENU \ Settings \ Application: 'Cont. T control'

ID no.:

Recommended setting:

1x500

ON

1x017

3 K*

1x054

OFF

1x054

ON

26 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

P330.13

One master circuit, two heating circuits and two DHW charging circuits as sub-circuits.

AQ120086463710en-010501

© Danfoss | 2021.06 | 27

Operating Guide ECL Comfort 310, application P330

Special settings for type P330.13

Navigation:

The master circuit reacts on demand in the sub-circuit(s).

Sub-circuit(s)

Settings for sub-circuit(s) in order to send demand to master circuit: MENU \ Settings \ Application: 'Send desired T'

Master circuit

Settings for master circuit in order to react on demand in sub-circuit(s): MENU \ Settings (M) \ Application: 'Demand offset'

* This value is added to the heat demand value from sub-circuit(s)

DHW circulation pipe

The DHW circulation pipe can be connected to the DHW tank at 'A' for internal circulation or to the heat exchanger at 'B' for external circulation.

(Internal DHW circulation) MENU \ Settings \ Application: 'Cont. T control' (External DHW circulation) MENU \ Settings \ Application: 'Cont. T control'

ID no.:

Recommended setting:

1x500

ON

1x017

3 K*

1x054

OFF

1x054

ON

28 | © Danfoss | 2021.06

AQ120086463710en-010501

Operating Guide ECL Comfort 310, application P330

P330.14

One master circuit with buffer tank , two heating circuits and one DHW charging circuits as sub-circuits.

Special settings for type P330.14

Navigation:

The master circuit reacts on demand in the sub-circuit(s).

Sub-circuit(s)

Settings for sub-circuit(s) in order to send demand to master circuit: MENU \ Settings \ Application: 'Send desired T'

Master circuit

Settings for master circuit in order to react on demand in sub-circuit(s): MENU \ Settings (M) \ Application: 'Demand offset'

* This value is added to the heat demand value from sub-circuit(s)

DHW circulation pipe

The DHW circulation pipe can be connected to the DHW tank at 'A' for internal circulation or to the heat exchanger at 'B' for external circulation.

(Internal DHW circulation) MENU \ Settings \ Application: 'Cont. T control' (External DHW circulation) MENU \ Settings \ Application: 'Cont. T control'

ID no.:

Recommended setting:

1x500

ON

1x017

3 K*

1x054

OFF

1x054

ON

AQ120086463710en-010501

© Danfoss | 2021.06 | 29

Operating Guide ECL Comfort 310, application P330

P330.15

One master circuit. One heating circuit and one DHW charging circuits as sub-circuits.

Special settings for type P330.15

Navigation:

The master circuit reacts on demand in the sub-circuit(s).

Sub-circuit(s)

Settings for sub-circuit(s) in order to send demand to master circuit: MENU \ Settings \ Application: 'Send desired T'

Master circuit

Settings for master circuit in order to react on demand in sub-circuit(s): MENU \ Settings (M) \ Application: 'Demand offset'

* This value is added to the heat demand value from sub-circuit(s)

DHW circulation pipe

The DHW circulation pipe can be connected to the DHW tank at 'A' for internal circulation or to the heat exchanger at 'B' for external circulation.

(Internal DHW circulation) MENU \ Settings \ Application: 'Cont. T control' (External DHW circulation) MENU \ Settings \ Application: 'Cont. T control'

ID no.:

Recommended setting:

1x500

ON

1x017

3 K*

1x054

OFF

1x054

ON

30 | © Danfoss | 2021.06

AQ120086463710en-010501

Loading...
+ 136 hidden pages