Danfoss PK37, P4K0, PK75, P5K5, P7K5 Quick Manual

...
MAKING MODERN LIVING POSSIBLE
Quick Guide
VLT® HVAC Basic Drive
Cascade Controller
1 Quick Guide
2
1.1 Safety
2
1.1.1 Warnings 2
1.1.2 Safety Instructions 2
1.2 Introduction
2
1.2.1 Available Literature 2
1.2.2 Approvals 2
1.2.3 IT Mains 3
1.2.4 Avoid Unintended Start 3
1.2.5 Disposal Instruction 3
1.3 Installation
3
1.3.1 Before Starting Repair Work 3
1.3.2 Side-by-Side Installation 3
1.3.3 Mechanical Dimensions 4
1.3.4 Electrical Installation in General 5
1.3.5 Connecting to Mains and Motor 6
1.3.6 Fuses 7
1.3.7 EMC-Correct Electrical Installation 8
1.3.8 Control Terminals 10
1.3.9 Electrical Overview 11
1.4 Programming
12
1.4.1 Programming with the Local Control Panel (LCP) 12
1.4.3 The Start-up Wizard for Open Loop Applications 13
1.5 Cascade Controller
20
1.5.1 System Status and Operation 20
1.5.2 Start/Stop Conditions 21
1.6 Parameter Overview
22
1.7 Warnings and Alarms
28
1.8.1 Mains Supply 3x380-480 V AC 30
1.8.2 EMC Test Results 32
1.9 Special Conditions
35
1.9.1 Derating for Ambient Temperature and Switching Frequency 35
1.9.2 Derating for Low Air Pressure 35
Contents
VLT® HVAC Basic Drive Cascade Controller Quick Guide
MG18F202 - VLT® is a registered Danfoss trademark 1
1 Quick Guide
1.1 Safety
1.1.1 Warnings
WARNING
High Voltage Warning
The voltage of the frequency converter is dangerous whenever it is connected to mains. Incorrect installation of the motor or frequency converter may cause damage to the equipment, serious injury or death. Consequently, it is essential to comply with the instructions in this manual as well as local and national rules and safety regulations.
WARNING
Electrical Hazard
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains. Also make sure that other voltage inputs have been disconnected (linkage of DC intermediate circuit). Be aware that there may be high voltage on the DC link even when the LEDs are turned off. Before touching any potentially live parts of the frequency converter, wait at least as stated in the table below:
Voltage [V] Power range [kW] Minimum waiting time
[min] 3x400 0.37–7.5 4 3x400 11–90 15
CAUTION
Leakage Current: The earth leakage current from the frequency converter exceeds 3.5 mA. According to IEC 61800-5-1 a reinforced Protective Earth connection must be ensured by means of a min. 10 mm² Cu or an addtional PE wire - with the same cable cross section as the Mains wiring - must be terminated separately. Residual Current Device: This product can cause a DC current in the protective conductor. Where a residual current device (RCD) is used for extra protection, only an RCD of Type B (time delayed) shall be used on the supply side of this product. See also Danfoss Application Note on RCD, MN90GXYY. Protective earthing of the frequency converter and the use of RCDs must always follow national and local regulations.
Motor Thermal Protection: Motor overload protection is possible by setting 1-90 Motor Thermal Protection to the value Electronic Thermal Relay (ETR) trip.
WARNING
Installation at high altitudes
For altitudes above 2 km, please contact Danfoss regarding PELV.
1.1.2 Safety Instructions
Make sure the frequency converter is properly connected to earth.
Do not remove mains connections, motor connections or other power connections while the frequency converter is connected to power.
Protect users against supply voltage.
Protect the motor against overloading according to national and local regulations.
The earth leakage current exceeds 3.5 mA.
The [Off reset] key is not a safety switch. It does not disconnect the frequency converter from mains.
1.2
Introduction
1.2.1 Available Literature
This Quick Guide contains the basic information necessary for installing and running the frequency converter. If more information is needed, literature can be found on the enclosed cd or downloaded from: http://www.danfoss.com/Products/Literature/Technical +Documentation.htm
1.2.2
Approvals
Quick Guide
VLT® HVAC Basic Drive Cascade Controller Quick Guide
2 MG18F202 - VLT® is a registered Danfoss trademark
11
1.2.3 IT Mains
CAUTION
IT Mains
Installation on isolated mains source, i.e. IT mains. Max. supply voltage allowed when connected to mains: 440 V (3x380-480 V units).
On 380-480 V IP20 0,37-22 kW, open the RFI switch by removing the screw on the side of the frequency converter when at IT grid.
130BB612.10
1
Illustration 1.1 IP20 0,37-22 kW 380-480 V. 1: EMC screw
On all units, set 14-50 RFI filter to Off when operating in IT mains.
CAUTION
If reinserted, only use M3x12 screw.
1.2.4 Avoid Unintended Start
While the frequency converter is connected to mains, the motor can be started/stopped using digital commands, bus commands, references or via the LCP.
Disconnect the frequency converter from mains whenever personal safety considerations make it necessary to avoid unintended start of any motors.
To avoid unintended start, always press [Off reset] before changing parameters.
1.2.5
Disposal Instruction
Equipment containing electrical components must not be disposed of together with domestic waste. It must be separately collected with electrical and electronic waste according to local and currently valid legislation.
1.3 Installation
1.3.1 Before Starting Repair Work
1. Disconnect FC 111 from mains (and external DC supply, if present.)
2. Wait as stated in the table below for discharge of the DC-link:
Voltage [V] Power range [kW] Minimum waiting time
[min] 3x400 0.37–7.5 4 3x400 11–90 15
3. Remove motor cable
1.3.2
Side-by-Side Installation
The frequency converter can be mounted side-by-side and requires the clearance above and below for cooling.
Power Clearance above/
below [mm/inch]
Frame IP class 3x380-480 V
H1 IP20 0.37-1.5 kW/
0.5-2 Hp
100/4
H2 IP20 2.2-4 kW/
3-5.4 Hp
100/4
H3 IP20 5.5-7.5 kW/
7.5-10 Hp
100/4
H4 IP20 11-15 kW/
15-20 Hp
100/4
H5 IP20 18.5-22 kW/
25-30 Hp
100/4
H6 IP20 30-45 kW/
40-60 Hp
200/7.9
H7 IP20 55-75 kW/
100-120 Hp
200/7.9
H8 IP20 90 kW/
125 Hp
225/8.9
NOTE
With IP21/Nema Type1 option kit mounted, a distance of 50 mm between the units is required.
Quick Guide
VLT® HVAC Basic Drive Cascade Controller Quick Guide
MG18F202 - VLT® is a registered Danfoss trademark 3
1 1
1.3.3 Mechanical Dimensions
A
a
b
B
C
D
130BB614.10
e
f
a
d
e
130BC205.10
e
f
a
e
130BC246.10
Power Height [mm/inch] Width [mm/inch] Depth [mm/
inch]
Hole [mm]
Frame IP class 3x380-480 V A A incl.
Decoupling
plate
A B b C D
H1 IP20 0.37-1.5 kW/
0.5-2 Hp
195/7.7 273/10.7 183/7.2 75/3 56/2.2 168/6.6 4.5
H2 IP20 2.2-4 kW/
3-5.4 Hp
227/8.4 303/11.9 212/8.3 90/3.5 65/2.6 190/7.5 5.5
H3 IP20 5.5-7.5 kW/
7.5-10 Hp
255/10 329/13 240/9.4 100/3.9 74/2.9 206/8.1 5.5
H4 IP20 11-15 kW/
15-20 Hp
296/11.7 359/14.1 275/10.8 135/5.3 105/4.1 241/9.5 7
H5 IP20 18.5-22 kW/
25-30 Hp
334/13.1 402/15.8 314/12.4 150/5.9 120/4.7 255/10 7
H6 IP20 30-45 kW/
40-60 Hp
518/20.4 595/23.4
635/25
495/19.5 239/31.5 200/7.9 242/9.5 8.5
H7 IP20 55-75 kW/
100-120 Hp
550/21.7 630/24.8
690/27.2
521/20.5 313/12.3 270/10.6 335/13.2 8.5
H8 IP20 90 kW/
120 Hp
660/26 800/31.5 631/24.8 375/14.8 330/13 335/13.2 8.5
Table 1.1 Mechanical Dimensions
Quick Guide
VLT® HVAC Basic Drive Cascade Controller Quick Guide
4 MG18F202 - VLT® is a registered Danfoss trademark
11
1.3.4 Electrical Installation in General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors required, (75°C) recommended.
Power [kW] Torque [Nm]
Frame IP class 3x380-480 Line Motor DC connection Control
terminals
Earth Relay
H1 IP20 0.37-1.5 1.4 0.8 0.8 0.5 0.8 0.5 H2 IP20 2.2-4 1.4 0.8 0.8 0.5 0.8 0.5 H3 IP20 5.5-7.5 1.4 0.8 0.8 0.5 0.8 0.5 H4 IP20 11-15 1.2 1.2 1.2 0.5 0.8 0.5 H5 IP20 18.5-22 1.2 1.2 1.2 0.5 0.8 0.5 H6 IP20 30-45 4.5 4.5 - 0.5 3 0.5 H7 IP20 55 10 10 - 0.5 3 0.5 H7 IP20 75 14 14 - 0.5 3 0.5 H8 IP20 90
14
1
14
1
- 0.5 3 0.5
H8 IP20 90
24
2
24
2
- 0.5 3 0.5
1
Cable dimensions ≤95 mm
2
2
Cable dimensions >95 mm
2
Quick Guide
VLT® HVAC Basic Drive Cascade Controller Quick Guide
MG18F202 - VLT® is a registered Danfoss trademark 5
1 1
1.3.5 Connecting to Mains and Motor
The frequency converter is designed to operate all standard three-phased asynchronous motors. For maximum cross-section on wires please see 1.8.1 Mains Supply 3x380-480 V AC.
Use a shielded/armored motor cable to comply with EMC emission specifications, and connect this cable to both the decoupling plate and the motor metal.
Keep motor cable as short as possible to reduce the noise level and leakage currents.
For further details on mounting of the decoupling plate, please see instruction MI02QXYY
Also see EMC-Correct Installation in the Design Guide, MG18CXYY.
1. Mount the earth wires to earth terminal.
2. Connect motor to terminals U, V and W.
3. Mount mains supply to terminals L1, L2 and L3 and tighten.
130BB634.10
1
2
2
3
4
Motor
U
V
W
-DC +DC
MAINS
Illustration 1.2 IP20 380-480 V 0.37-22 kW.
1
Line 2 Earth 3 Motor 4 Relays
Quick Guide
VLT® HVAC Basic Drive Cascade Controller Quick Guide
6 MG18F202 - VLT® is a registered Danfoss trademark
11
IP20 380-480 V 30-45 kW
1
95
99
L1 91 / L2 92 / L3 93
U 96 / V 97 / W 98
03 02 01
06 05 04
2
3
4
130BB762.10
1 Line 2 Motor 3 Earth 4 Relays
IP20 380-480 V 55-75 kW
1
2
3
4
130BB763.10
1
Line 2 Relays 3 Earth 4 Motor
IP20 380-480 V 90 kW
130BB764.10
1
2
3
4
98
97
96
99
95
93
92
91 L1
L1
L1
U
V
w
1 Line 2 Relays 3 Earth 4 Motor
1.3.6 Fuses
Branch circuit protection In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuit and overcurrent protected according to national/international regulations.
Short circuit protection Danfoss recommends using the fuses mentioned in the following tables to protect service personnel or other equipment in case of an internal failure in the unit or short-circuit on DC-link. The frequency converter provides full short circuit protection in case of a short-circuit on the motor.
Overcurrent protection Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be carried out according to national regulations. Fuses must be designed for protection in a circuit capable of supplying a maximum of 100,000 A
rms
(symmetrical),
480 V maximum.
Quick Guide
VLT® HVAC Basic Drive Cascade Controller Quick Guide
MG18F202 - VLT® is a registered Danfoss trademark 7
1 1
Non UL compliance If UL/cUL is not to be complied with, use the fuses mentioned in Table 1.2, which will ensure compliance with IEC 61800-5-1: In case of malfunction, not following the fuse recommen­dation may result in damage to the frequency converter.
UL Non
UL
Bussmann Bussmann Bussmann Bussmann Max.
Fuse Power [kW]
Type RK5 Type RK1 Type J Type T Type
gG
3x380-480 V
0.37 FRS-R-10 KTS-R10 JKS-10 JJS-10 10
0.75 FRS-R-10 KTS-R10 JKS-10 JJS-10 10
1.5 FRS-R-10 KTS-R10 JKS-10 JJS-10 10
2.2 FRS-R-15 KTS-R15 JKS-15 JJS-15 16 3 FRS-R-15 KTS-R15 JKS-15 JJS-15 16 4 FRS-R-15 KTS-R15 JKS-15 JJS-15 16
5.5 FRS-R-25 KTS-R25 JKS-25 JJS-25 25
7.5 FRS-R-25 KTS-R25 JKS-25 JJS-25 25 11 FRS-R-50 KTS-R50 JKS-50 JJS-50 50 15 FRS-R-50 KTS-R50 JKS-50 JJS-50 50
18.5 FRS-R-80 KTS-R80 JKS-80 JJS-80 65 22 FRS-R-80 KTS-R80 JKS-80 JJS-80 65 30 FRS-R-80 KTS-R80 JKS-R80 JJS-R80 80 37 FRS-R-100 KTS-R100 JKS-R100 JJS-R100 100 45 FRS-R-125 KTS-R125 JKS-R125 JJS-R125 125 55 FRS-R-150 KTS-R150 JKS-R150 JJS-R150 150 75 FRS-R-200 KTS-R200 JKS-R200 JJS-R200 200 90 FRS-R-250 KTS-R250 JKS-R250 JJS-R250 250
Table 1.2 Recommended fuses
1.3.7
EMC-Correct Electrical Installation
General points to be observed to ensure EMC-correct electrical installation.
Use only screened/armoured motor cables and screened/armoured control cables.
Connect the screen to earth at both ends.
Avoid installation with twisted screen ends (pigtails), since this ruins the screening effect at high frequencies. Use the cable clamps provide­dinstead.
It is important to ensure good electrical contact from the installation plate through the installation screws to the metal cabinet of the frequency converter.
Use starwashers and galvanically conductive installation plates.
Do not use unscreened/unarmoured motor cables in the installation cabinets.
Quick Guide
VLT® HVAC Basic Drive Cascade Controller Quick Guide
8 MG18F202 - VLT® is a registered Danfoss trademark
11
L1
L2
L3
PE
Min. 16 mm
2
Equalizing cable
Control cables
All cable entries in
one side of panel
Earthing rail
Cable insula­tion stripped
Output con­tactor etc.
Motor cable
Motor, 3 phases and
PLC etc.
Panel
Mains-supply
Min. 200mm between control cable, mains cable and between mains motor cable
PLC
Protective earth
Reinforced protective earth
130BB761.10
Illustration 1.3 EMC-correct Electrical Installation
For North America use metal conduits instead of shielded cables.
Quick Guide
VLT® HVAC Basic Drive Cascade Controller Quick Guide
MG18F202 - VLT® is a registered Danfoss trademark 9
1 1
1.3.8 Control Terminals
IP20 380-480 V 0.37-22 kW:
130BB622.10
Illustration 1.4 Location of Control Terminals
1. Place a screwdriver behind the terminal cover to activate snap.
2. Tilt the screwdriver outwards to open the cover.
IP20 380-480 V 30-90 kW.
130BB624.10
1. Place a screwdriver behind the terminal cover to activate snap.
2. Tilt the screwdriver outwards to open the cover.
Digital input 18, 19 and 27 mode is set in 5-00 Digital Input Mode (PNP is default value) and digital input 29 mode is set in 5-03 Digital Input 29 Mode (PNP is default value).
Control terminals: Illustration 1.5 shows all control terminals of the frequency converter. Applying Start (term. 18), connection between terminal 12-27 and an analog reference (term. 53 or 54 and 55) make the frequency converter run.
18
19
12 20 55
27 29 42 45 50 53 54
DIGI IN/OUT
DIGI IN/OUT
DIGI IN
DIGI IN
61 68 69
N
P
COMM. GND
+24V
0/4-20mA A OUT / DIG OUT 0/4-20mA A OUT / DIG OUT
COM A IN
COM DIG IN
10V/20mA IN
10V/20mA IN
10V OUT
130BB985.10
BUS TER.
OFF ON
Illustration 1.5 Control Terminals
Quick Guide
VLT® HVAC Basic Drive Cascade Controller Quick Guide
10 MG18F202 - VLT® is a registered Danfoss trademark
11
1.3.9 Electrical Overview
24V
0V
24V
0V
L1 L2 L3
3 Phase power input
PE
PE
+10Vdc
0-10Vdc-
0-10Vdc-
50 (+10V OUT)
54 (A IN)
53 (A IN)
55 (COM A IN/OUT)
0/4-20 mA
0/4-20 mA
42 0/4-20mA A OUT / DIG OUT
45 0/4-20mA A OUT / DIG OUT
18 (DIGI IN)
19 (DIGI IN)
27 (DIGI IN/DIGI OUT)
29 (DIGI IN/ DIGI OUT)
12 (+24V OUT)
24V (NPN)
20 (COM D IN)
OV (PNP)
24V (NPN) OV (PNP)
24V (NPN) OV (PNP)
24V (NPN) OV (PNP)
Bus ter.
Bus ter.
RS-485 Interface
RS-485
(N PS-485) 69
(P RS-485) 68
(Com RS-485 ) 61
(PNP)-Source (NPN)-Sink
ON=Terminated
OFF=Unterminated
ON
1 2
240V AC 3A
Not present on all power sizes
Do not connect shield to 61 on 116,117 and 118 unites
01
02
03
relay1
relay2
UDC+
UDC-
Motor
U
V
W
130BB984.10
06
05
04
240V AC 3A
NOTE
There is no access to UDC- and UDC+ on the following units: IP20 380-480 V 30-90 kW
Quick Guide
VLT® HVAC Basic Drive Cascade Controller Quick Guide
MG18F202 - VLT® is a registered Danfoss trademark 11
1 1
Loading...
+ 25 hidden pages