Quick starting procedure
Optyma™ Plus
Control unit (mounted code 084B8080)
Caution:
The information contained herein is a summary of the
instructions available in the Danfoss documentation.
For further information, please consult the user guide or
other documents provided with the condensing unit.
© Danfoss | Produced by DCS | 2019.12 AN330833960600en-000101
Instructions
DI1 terminal block
Upper button
Central button
Lower button
The upper and lower buttons are used to navigate
the menu and change the values, while the central
button lets you access the parameters and conrm
the value
Step 1 - Removing the DI1 terminal block
1.1
1.2
1.3
If the condensing unit is powered up, cut o the power supply using the
switch.
Remove the DI1 terminal block.
This is the external stop start hard wired link for the controller & will stop
the compressor from running. You can access the controller by opening
the hinged door of the unit & then removing two screws on the cover
plate that covers the controller terminals.
Power the unit back on by turning the switch.
Step 2 - Settings mode
2.1
© Danfoss | Produced by DCS | 2019.12
Press the upper button for 5 seconds: r05 will appear.
AN330833960600en-000101