Quick starting procedure
Optyma™ Plus
Control unit (mounted code 084B8080)
Caution:
The information contained herein is a summary of the instructions available in the Danfoss documentation.
For further information, please consult the user guide or other documents provided with the condensing unit.
© Danfoss | Produced by DCS | 2019.12 |
AN330833960600en-000101 |
Instructions
DI1 terminal block
Upper button
Central button
Lower button
The upper and lower buttons are used to navigate the menu and change the values, while the central button lets you access the parameters and confirm the value
Step 1 - Removing the DI1 terminal block
1.1 |
If the condensing unit is powered up, cut off the power supply using the |
|
switch. |
Remove the DI1 terminal block.
1.2 This is the external stop start hard wired link for the controller & will stop the compressor from running. You can access the controller by opening the hinged door of the unit & then removing two screws on the cover plate that covers the controller terminals.
1.3 |
Power the unit back on by turning the switch. |
Step 2 - Settings mode
2.1 |
Press the upper button for 5 seconds: r05 will appear. |