Page 1

OperatingGuide
TermixOneSolar
1.0TableofContents
1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotes–general............................................4
4.0Mounting........................................................5
4.1Mounting...........................................................5
4.2Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.2Schematicdiagram................................................9
6.0Controls..........................................................10
6.1DHWtemperaturecontrol........................................10
6.2Maintenance........................................................12
7.0Troubleshooting..............................................13
7.1Troubleshootingingeneral......................................13
7.2TroubleshootingDHW............................................14
7.3Disposal.............................................................15
8.0Declaration......................................................19
8.1Declarationofconformity........................................19
©Danfoss|2019.04VI.CW.K5.02/LUK38004|1
Page 2

OperatingGuideTermixOneSolar
2|©Danfoss|2019.04
VI.CW.K5.02/LUK38004
Page 3

OperatingGuideTermixOneSolar
2.0Functionaldescription
Domestichotwatermodulewithheatexchangerand
thermostaticcontrol.Designedforwall-mounting.
Application
TheTermixOneSolarisaninstantaneouswaterheater,featuring
superbheatextractionandhighperformance.TheTermixOne
Solarisapplicableforheatingsystemswithbufferaccumulators,
solarsystemsorforotherheatsources,whereaverylowreturn
temperatureispreferred.Thewaterheaterisavailableinthree
sizes,eitherfor1apartment,for1-4apartmentsorfor5upto10
apartments.Thelargeheatexchangercoolsoutthewaterinthe
primaryreturnlineveryefficiently,therebycreatingaverygood
operationeconomy.Aflowswitchincoldwatermainsiscontrolling
theprimaryheatingpump.Anoptionalcirculationpumptogether
withathermostatcanmaintainthecirculatingtemperatureata
desiredtemperature.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerand
thetemperatureisregulatedwithathermostaticcontrolvalve.
Thepatentedsensoracceleratoracceleratestheclosingofthe
thermostaticcontrolvalveandprotectstheheatexchangeragainst
overheatingandlimescaleformation.Thesensoracceleratorand
thethermostaticcontrolvalvealsoworksasabypasskeepingthe
heatexchangerandsupplylinewarm.Thisshortensthewaiting
periods.Thesensoracceleratorhelpstoensureastablehotwater
temperaturebyvaryingloads,flowtemperaturesanddifferential
pressurewithouttheneedforreadjustingthevalve.Thereisno
additionalpressurelossonthesecondarysideoftheDHWheat
exchangerwithathermostaticcontrol.Thereforethistypeof
regulationcanbeusedbylowpressureinthecoldwatermains.
VI.CW.K5.02/LUK38004
©Danfoss|2019.04|3
Page 4

OperatingGuideTermixOneSolar
3.0Safetynotes
3.1SafetyNotes–general
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualifiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheflowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualifiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’spermissiblesystempressureand
temperature.
Themaximumtemperatureoftheflowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis16bar.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-fire,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
REACH
AllDanfossA/SproductsfulfilltherequirementsinREACH.
OneoftheobligationsinREACHistoinformcustomersabout
presenceofCandidatelistsubstancesifany,weherebyinform
youaboutonesubstanceonthecandidatelist:Theproduct
containsbrasspartswhichcontainslead(CASno:7439-92-1)ina
concentrationabove0.1%w/w.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallflangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
4|©Danfoss|2019.04
VI.CW.K5.02/LUK38004
Page 5

OperatingGuideTermixOneSolar
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Domesticcoldwater(DCW)
2.Domestichotwater(DHW)
3.BufferTank(BT)supply
4.BufferTank(BT)return
5.Hotwatercirculation(HWC)-(Optional)
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualifiedandauthorizedpersonnelonly.
Connectionsizes:
BT:
DCW+DHW+HWC:
Dimensions(mm):
Withoutcirculationandcover:
H760xW312xD155
Withoutcirculationandwithcover:
H760xW315xD165
Withcirculationandwithoutcover:
H935xW410xD190
Weight(approx.):20kg
G¾”(int.thread)
G¾”(int.thread)
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
VI.CW.K5.02/LUK38004
©Danfoss|2019.04|5
Page 6

OperatingGuideTermixOneSolar
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Keyholeformounting.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbefittedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,flangedorweldedconnections.
6|©Danfoss|2019.04
VI.CW.K5.02/LUK38004
Page 7

OperatingGuideTermixOneSolar
4.2Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording
to60364-4-41:2007andIEC60364-5-54:2011.
Bondingpointonthemountingplatebelowrightcornermarked
withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
VI.CW.K5.02/LUK38004
©Danfoss|2019.04|7
Page 8

OperatingGuideTermixOneSolar
5.0Design
5.1Design
5.1.1DesignTermixOneSolar
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
M
Electricalwiringbox
O
Termixsensoraccelerator
7
Thermostaticcontroller,DHW
13
Chargingpump
8|©Danfoss|2019.04
35
Ballvalve/non-returnvalve
45
Flowswitch
48
Airvent,manual
63
Sieve
VI.CW.K5.02/LUK38004
Page 9

OperatingGuideTermixOneSolar
5.2Schematicdiagram
5.2.1SchematicdiagramT ermixOneSolarwithcirculation
BT
Supply
BT
ReturnDCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescriptionwithcirculation
DHW
HWC
B
Heatexchanger,DHW
M
Electricalwiringbox
O
Termixsensoraccelerator
1
Ballvalve
2
Singlecheckvalve
DHW:DomesticHotWater
DCW:
HWC:
BTSupply:
BTReturn:
5.2.2Technicalparameters
Technicalparameters
Nominalpressure:
Max.DHsupplytemperature:
Min.DCWstaticpressure:
Brazingmaterial(HEX):
Heatexchangerstestpressure:30bar
Soundlevel:≤55dB
DomesticColdWater
HotWaterCirculation
Buffertanksupply
Buffertankreturn
PN16
120°C
0.5bar
Copper
4
Safetyvalve
7
Thermostaticvalve
11A
DHWpump,withbuiltincheckvalve
13
Chargingpump
21
Tobeorderedseparately
35
Ballvalve/non-returnvalve
39
Connectionclosed
45
Flowswitch
48
Airvent,manual
63
Sieve
VI.CW.K5.02/LUK38004
©Danfoss|2019.04|9
Page 10

OperatingGuideTermixOneSolar
6.0Controls
6.1DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignificantly.
6.1.1AVTBcontroller(20–60°)
Thetemperaturesettingisasfollows:
1=20°C
2=35°C
3=50°C
4=60°C
5=70°C
Thevaluesareintendedasaguide.
TheAVTBoperatesatitsbestatDHsupplytemperaturesofupto
90°C.
Thermostaticcontrol
DHWtemperatureisadjustedasfollows:
Toincreasetemperature,turnthehandleonthethermostatic
controllertoselectahighernumber.
Todecreasetemperature,turnthehandleonthethermostatic
controllertoselectalowernumber.
6.1.2CirculatorpumpUPM3
UPM3Pumpscanbecontrolledinconstantpressure,proportional
pressureorconstantspeedmodedefinedbythemeansofasmart
userinterface.
Thevariablespeedmodulatingmodesallowthepumptomatchits
performancetothesystemrequirements,helpingtoreducenoise
whenthermostaticvalvesareclosingdown.
EnergylabellingclassA
10|©Danfoss|2019.04
VI.CW.K5.02/LUK38004
Page 11

OperatingGuideTermixOneSolar
6.1.3Domestichotwaterpump
Thedomestichotwaterpumpcanbeprogrammedwiththe
desiredtimeprogramme.
VI.CW.K5.02/LUK38004
©Danfoss|2019.04|11
Page 12

OperatingGuideTermixOneSolar
6.2Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualifiedandauthorizedpersonnelonly.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
12|©Danfoss|2019.04
VI.CW.K5.02/LUK38004
Page 13

OperatingGuideTermixOneSolar
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
•thesubstationisconnectedtoelectricity,
•thestrainerontheDHsupplypipeisclean,
•thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
•thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetwork–ifindoubt,ask
theDHplantsupervisor,
•pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualifiedandauthorizedpersonnelonly.
VI.CW.K5.02/LUK38004
©Danfoss|2019.04|13
Page 14

OperatingGuideTermixOneSolar
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
ToolittleornoDHW.
Taptemperaturetoohigh;DHWtapload
toohigh.
Temperaturedropduringtapping.
Thermostaticcontrolvalvedoesnotclose
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Defectiveorcloggednon-returnvalve.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
Scalingoftheplateheatexchanger.
Defectivemotorizedvalve.Check(usemanualfunction)–replace.
Defectivetemperaturesensors.
Defectivecontroller.
DCWisbeingmixedwiththeDHW,e.g.ina
defectivethermostaticmixingvalve.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Thermostaticvalveadjustedtoatoohigh
level.
Scalingoftheplateheatexchanger.
LargerDHWflowthanthesubstationhas
beendesignedfor.
TemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Checkcirculationpump.
Replace–clean.
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Replace–rinseout.
Check–replace.
Check–replace.
Check–replace. Hotwaterinsometapsbutnotinall.
Replace–clean.
Check–set.
Replace–rinseout.
ReduceDHWflow.
Lowerthesetpointtemperatureorincrease
theDHsupplytemperature.
14|©Danfoss|2019.04
VI.CW.K5.02/LUK38004
Page 15

OperatingGuideTermixOneSolar
7.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.CW.K5.02/LUK38004
©Danfoss|2019.04|15
Page 16

OperatingGuideTermixOneSolar
16|©Danfoss|2019.04
VI.CW.K5.02/LUK38004
Page 17

OperatingGuideTermixOneSolar
17|©Danfoss|2019.04
VI.CW.K5.02/LUK38004
Page 18

OperatingGuideTermixOneSolar
18|©Danfoss|2019.04
VI.CW.K5.02/LUK38004
Page 19

OperatingGuideTermixOneSolar
8.0Declaration
8.1Declarationofconformity
Category0withelectricalequipment
VI.CW.K5.02/LUK38004
©Danfoss|2019.04|19
Page 20

OperatingGuideTermixOneSolar
20|©Danfoss|2019.04
VI.CW.K5.02/LUK38004