Danfoss OBC 82.12 Data sheet

0 (0)

Data sheet

Electronic Oil Burner Control OBC 82.12

Description

The microprocessor based control OBC 82.12 offers stable and precise timings independent of variations in supply voltage and ambient temperature.

The control is undervoltage protected.

In case of undervoltage the control will prevent the burner from starting and simultaneously show a flash code. Besides this, up to five other fault types can be read out as flash codes when the control is in lockout.

The design complies with the requirements of the RoHS and WEEE directive.

Application and features

For 2 stage burners up to 30 kg/h

For burners with or without preheater

Precise and reproducible timings

Limitation at 3 restarts by flame failure within the same operating period

Limitation of 10 min. on preheating time

Remote alarm output

Indication of reason for lockout

Indication of preheating and operation

Function

The OBC 82.12 controls the cut-in and cut-out of

 

the oil burner’s components and monitors that

 

the combustion cycle is performed safely.

 

When the boiler thermostat (TR) cuts in, heating

 

of the oil in the oil preheater (OFV) will begin.

 

Once the release temperature is reached and the

 

oil preheater’s thermostat (OTR) cuts in, the

 

burner motor will start the pre-purge and power

 

will simultaneously be applied to the ignition

 

(TT). Following the pre-ignition and pre-purge

 

time, the oil will be released by valve V1 being

 

opened and subsequently V2 will be opened.

 

When the boiler thermostat opens after the

 

heating period power will be cut off and all

 

relays at the outputs will open and be ready for

 

the next start-up cycle.

 

Operating information

 

OBC 82.12 is equipped with a two-coloured LED

 

which displays both the operating status and can

 

indicate the causes of errors leading to lockout.

 

In the event of operating lockout, the cause of

 

error can be read out as a flash code by holding

 

down the reset button for at least 5 seconds and

 

then releasing it. Undervoltage will, however, be

 

displayed automatically. Reset can be performed

 

directly in alarm mode (constant red light) or in

 

flash code mode by pressing the reset button for

 

at least 0.5 seconds, but no more than 3 seconds.

 

In flash code mode it is possible to return to

 

alarm mode by holding down the reset button

 

again for at least 5 seconds.

Normal operation

When the boiler thermostat (TR) cuts in, the reset button flashes green. As soon as the preheater thermostat (OTR) cuts in, the reset button lights up constant green. When the boiler thermostat cuts out, the green light turns off.

Errors during operation (flash codes):

If the mains voltage falls below 176 V before start-up, the control will be blocked from starting. If the mains voltage falls below 165 V during operation, the oil supply and burner will be stopped. In both cases, the reset button will automatically flash 8 times. When the mains voltages reaches 176 V, the control will restart as normal. Please note that the control cannot be reset if the mains voltage is below 165 V.

If the mains voltage exceeds 264 V, the control will automatically enter alarm mode.

The purpose of the overvoltage cut out is not simply to protect the electronics in the control, but also the other components in the burner.

If light is registered in the final stage of the pre-purge time, the control will not release oil and will enter alarm mode.

If no flame is established at the start, i.e. by the end of the safety time, the control will enter alarm mode.

© Danfoss | 2019.10

VD.HN.C1.02 | 1

Danfoss OBC 82.12 Data sheet

Data sheet

Electronic Oil Burner Control OBC 82.12

In the event of a flame failure during operation, the oil supply will be cut off after no more than 1 second and the control will restart the burner. If flame failure occurs more than three times in the same operating period (TR connected), the control will enter alarm mode.

If the release temperature in the preheater is not reached within 10 minutes, the control will enter alarm mode.

The OBC 82.12 processor also monitors the outputs at TT, V1 and V2. If errors like electrical noise (EMC) are registered at the outputs, the control will enter alarm mode.

Note:

OBC 82.12 can only be reset while the supply voltage is connected.

Flash codes

Event

Code

False light

2 flashes

 

 

No flame when safety time elapses

3 flashes

More than three restarts in the same

4 flashes

cycle

 

Max. waiting time on preheater overrun

5 flashes

(10 min)

 

Supply voltage above 264 V a.c.

6 flashes

 

 

Undervoltage <170 V (automatic)

8 flashes

Application failure (EMC)

constant

flashes

 

Symbols

Boiler thermostat

High temperature cutout

Ignition unit

Burner motor

Solenoid valve

Photo unit or UV sensor

External alarm

L Phase wire

N Neutral wire

Oil preheater / Oil preheater thermostat

Hold relay

 

Time function/explanation

 

 

 

Output signals of control

 

 

 

Required input signals

A’

Initiation of burners with oil preheater OFV

AInitiation of burners without oil preheater

BFlame formation

COperation position

DBurner stop

tw

Heating of oil preheater until OTR switches on

 

 

t1

Pre-purge 13 s

t2

Safety time 10 s

 

 

t3*

Pre-ignition 13 s

 

 

t4

Interval V1-V2 15 s

 

 

t3n

Post-ignition 15 s

* Due to the initialisation of the electronics, it may take up to two seconds before ignition is enabled.

2 | © Danfoss | 2019.10

VD.HN.C1.02

Loading...
+ 2 hidden pages