Data Sheet
Differential pressure switch
Type MP 54, 55 and 55A
MP 54 and MP 55 are used in refrigerating systems
using HCFC and non-ammable HFC refrigerants.
MP 54 and MP 55 oil dierential pressure
switches are used as safety switches to protect
refrigeration compressors against low
lubricating oil pressure.
If the oil pressure fails, the oil dierential
pressure switch stops the compressor after a
certain time period.
MP 54 and MP 55 are used in refrigerating
systems using HCFC and non-ammable HFC
refrigerants.
MP 55A is used in refrigerating systems with
R717. MP 55A can also be used in systems with
HCFC and non-ammable HFC refrigerants.
MP 54 has a xed dierential pressure setting. It
also incorporates a thermal time relay with a
xed release time setting.
MP 55 and MP 55A have adjustable dierential
pressure and are available both with and
without thermal time relay.
Features
• Wide regulating range
• Can be used for deep freeze, refrigeration and
air conditioning plant
• Can be used for HCFC and non-ammable
HFC refrigerants
• Electrical connection at the front of the unit
• Suitable for both alternating and direct
current (AC and DC)
• Screwed cable entry for cables from 6 – 14
mm diameter
• Small contact dierential
AI211986438834en-000901
Danfoss
60B59.13
On start-up
Dierential pressure switch, Type MP 54, 55 and 55A
Functions
Figure 1: Electrical diagram
If there is no oil pressure on starting, or if the oil pressure falls below the set pressure during operation, the
compressor will stop after the release time has elapsed.
The electrical circuit is divided into two completely separate circuits: a safety circuit and an operational circuit.
The timer (e) in the safety circuit is activated when the eective lubricating oil pressure, the oil dierential pressure
(the dierence between the oil pump pressure and suction pressure), is lower than the set value.
The timer is deactivated when the oil dierential pressure is more than the set value plus the contact dierential.
Figure 2: Functions for During start
The two diagrams below explain the terms "oil dierential pressure" and "contact dierential". Both have to be
considered when using oil dierential pressure switches.
The rst diagram shows the function of the dierential switch during start; the second shows the function of the
switch during operation.
Pos. A: Normal start-up
The lubricating oil pressure is built up during start to the set/xed dierential plus the contact dierential, before
the timer cuts out (in this example, after 45 seconds).
At point A contacts T1-T2 open and timer (e) is stopped, i.e. normal lubricating oil conditions for the compressor
have been established.
Pos. B: The lubricating oil pressure does not reach the set/xed dierential plus the contact dierential before the
timer period elapses. At point B the timer cuts out operational circuit L-M and the compressor stops. If a signal
source is connected to terminal S, it will be activated. Restart can only be performed after about 2 minutes by
activation of the reset button, provided the cause of the fault has been determined.
© Danfoss | Climate Solutions | 2021.02 AI211986438834en-000901 | 2
Dierential pressure switch, Type MP 54, 55 and 55A
Figure 3: Functions for During operation
Pos. C: The lubricating oil pressure falls during operation to a value lower than the set/xed dierential. At point C,
safety circuit T1-T2 cuts in and the timer is activated.
Pos. D: The lubricating oil pressure reaches the set/xed dierential plus the contact dierential before the timer
period elapses. At point D, safety circuit T1-T2 cuts out and the timer is stopped, i.e. normal lubricating oil conditions
for the compressor have been established.
Pos. E: The lubricating oil pressure falls to a value lower than the set/xed dierential during operation. At point E,
safety circuit T1-T2 cuts in and the timer is activated.
Pos. F: The lubricating oil pressure remains lower than the set/xed dierential. At point F the timer cuts out
operational circuit L-M and the compressor stops. If a signal source is connected to terminal S, it will be activated.
Restart can only be performed after about 2 minutes by activation of the reset button, provided the cause of the
fault has been determined.
After start-up
It is important that a function check should be made to ensure that the dierential pressure control is operating as it
should.
This check can be made by pressing the test device (inside the unit on the left hand side).
When the test device is pressed down and held in this position, the compressor motor should stop after the release
time determined by the time relay has elapsed.
© Danfoss | Climate Solutions | 2021.02 AI211986438834en-000901 | 3