1.4.3 Danfoss Frequency Converter and CE Labelling5
1.4.4 Compliance with EMC Directive 2004/108/ECEMC Directive 2004/108/EC6
1.5.1 Air Humidity 6
1.5.2 Aggressive Environments 6
1.5.3 Vibration and Shock6
2 Introduction
2.1 Introduction
2.1.1 Modbus RTU Overview8
3
3
5
8
8
3 RS-485 Installation and Set-up
3.1.1 Overview9
3.1.2 Cable Specifications9
3.1.5 EMC Precautions11
4 Modbus RTU Message Framing Structure
4.1.1 Frequency Converter with Modbus RTU12
4.1.2 Timing Constraints12
4.1.3 Modbus RTU Message Structure13
4.1.4 Start/Stop Field13
4.1.5 Address Field13
4.1.6 Function Field13
4.1.7 Data Field13
4.1.8 CRC Check Field13
4.1.9 Coil and Register Addressing14
4.1.10 Function Codes Supported by Modbus RTU14
4.1.11 Coil Addresses14
4.1.12 Register Addresses16
9
12
4.1.13 Parameter Handling16
4.1.14 Storage of Data16
4.1.15 IND16
4.1.16 Text Blocks16
MG92B102 - VLT® is a registered Danfoss trademark1
ContentsModbus RTU Operating Instruction
4.1.17 Conversion Factor17
4.1.18 Parameter Values17
5 How to Control the Frequency Converter
5.1 How to Control the Frequency Converter
5.2 Parameter for Modbus RTU
5.2.1 Important Parameters for Modbus RTU18
5.2.2 Access via PCD write/read18
5.2.3 Mapping the Holding Registers to Drive Parameters19
5.2.4 Mapping the Holding Registers to Drive Parameters, 32 bits20
6 Function Code Examples
6.1 Examples
6.1.2 Force/Write Single Coil (05 HEX)21
6.1.3 Force/Write Multiple Coils (0F HEX)21
6.1.4 Read Holding Registers (03 HEX)22
6.1.5 Preset Single Register (06 HEX)22
6.1.6 Preset Multiple Registers (10 HEX)23
7 FC Control Profile
7.1.1 Control Word According to FC Profile (8-10 Protocol = FC profile)24
18
18
18
21
21
24
8 Parameters
8.1 Parameters: 8-** Communications and Options
8.1.3 8-3* FC Port Settings30
8.1.4 8-4* FC MC protocol set31
9 Troubleshooting
9.1.1 Modbus Exception Codes35
9.1.2 8-80 Bus Message count35
9.1.3 8-81 Bus Error Count35
9.1.4 8-82 Slave Messages Rcvd35
9.1.5 8-83 Slave Error36
Index
28
28
35
37
2MG92B102 - VLT® is a registered Danfoss trademark
Safety and ConformityModbus RTU Operating Instruction
1 Safety and Conformity
1.1 Safety Precautions
WARNING
The voltage of the frequency converter is dangerous
whenever connected to mains. Incorrect installation of the
motor, frequency converter or fieldbus may cause death,
serious personal injury or damage to the equipment.
Consequently, the instructions in this manual, as well as
national and local rules and safety regulations, must be
complied with.
Safety Regulations
1.The mains supply to the frequency converter
must be disconnected whenever repair work is to
be carried out. Check that the mains supply has
been disconnected and that the necessary time
has elapsed before removing motor and mains
supply plugs.
2.The [Off] button on the control panel of the
frequency converter does not disconnect the
mains supply and consequently it must not be
used as a safety switch.
3.The equipment must be properly earthed, the
user must be protected against supply voltage
and the motor must be protected against
overload in accordance with applicable national
and local regulations.
4.The earth leakage current exceeds 3.5 mA.
5.Protection against motor overload is not included
in the factory setting. If this function is desired,
set 1-90 Motor Thermal Protection to data value
ETR trip 1 [4] or data value ETR warning 1 [3].
6.Do not remove the plugs for the motor and
mains supply while the frequency converter is
connected to mains. Check that the mains supply
has been disconnected and that the necessary
time has elapsed before removing motor and
mains plugs.
7.Note that the frequency converter has more
voltage sources than L1, L2 and L3, when load
sharing (linking of DC intermediate circuit) or
external 24 V DC are installed. Check that all
voltage sources have been disconnected and that
the necessary time has elapsed before
commencing repair work.
1.1.1
Safety Precautions - Continued
Warning against unintended start
1.The motor can be brought to a stop with digital
commands, bus commands, references or a local
stop, while the frequency converter is connected
to mains. If personal safety considerations (e.g.
risk of personal injury caused by contact with
moving machine parts following an unintentional
start) make it necessary to ensure that no
unintended start occurs, these stop functions are
not sufficient. In such cases the mains supply
must be disconnected or the Safe Stop function
must be activated.
2.The motor may start while setting the
parameters. If this means that personal safety
may be compromised (e.g. personal injury caused
by contact with moving machine parts), motor
starting must be prevented, for instance by use
of the Safe Stop function or secure disconnection
of the motor connection.
3.A motor that has been stopped with the mains
supply connected, may start if faults occur in the
electronics of the frequency converter, through
temporary overload or if a fault in the power
supply grid or motor connection is remedied. If
unintended start must be prevented for personal
safety reasons (e.g. risk of injury caused by
contact with moving machine parts), the normal
stop functions of the frequency converter are not
sufficient. In such cases the mains supply must be
disconnected or the Safe Stop function must be
activated.
NOTE
When using the Safe Stop function, always follow the
instructions in the section Safe Stop of the Design Guide.
4.Control signals from, or internally within, the
frequency converter may in rare cases be
activated in error, be delayed or fail to occur
entirely. When used in situations where safety is
critical, e.g. when controlling the electromagnetic
brake function of a hoist application, these
control signals must not be relied on exclusively.
11
MG92B102 - VLT® is a registered Danfoss trademark3
Safety and ConformityModbus RTU Operating Instruction
11
WARNING
1.2.1 Caution
High Voltage
Touching the electrical parts may be fatal - even after the
equipment has been disconnected from mains.
Also make sure that other voltage inputs have been
disconnected, such as external 24 V DC, load sharing
(linkage of DC intermediate circuit), as well as the motor
connection for kinetic back up.
Systems where frequency converters are installed must, if
necessary, be equipped with additional monitoring and
protective devices according to the valid safety regulations,
e.g law on mechanical tools, regulations for the prevention
of accidents etc. Modifications on the frequency converters
by means of the operating software are allowed.
CAUTION
The DC link capacitors remain charged after power has
been disconnected. Be aware that there may be high
voltage on the DC link even when the Control Card LEDs
are turned off. A red LED is mounted on a circuit board
inside the frequency converter to indicate the DC bus
voltage. The red LED will stay lit until the DC link is 50 V
DC or lower. To avoid electrical shock hazard, disconnect
the frequency converter from mains before carrying out
maintenance. When using a PM-motor, make sure it is
disconnected. Before doing service on the frequency
converter wait at least the amount of time indicated
below:
NOTE
Hazardous situations shall be identified by the machine
builder/integrator who is responsible for taking necessary
preventive means into consideration. Additional
monitoring and protective devices may be included, always
according to valid national safety regulations, e.g. law on
mechanical tools, regulations for the prevention of
accidents.
NOTE
Crane, Lifts and Hoists:
The controlling of external brakes must always have a
redundant system. The frequency converter can in no
circumstances be the primary safety circuit. Comply with
relevant standards, e.g.
Hoists and cranes: IEC 60204-32
Lifts: EN 81
Protection Mode
Once a hardware limit on motor current or DC link voltage
is exceeded the frequency converter will enter “Protection
mode”. “Protection mode” means a change of the PWM
modulation strategy and a low switching frequency to
minimize losses. This continues 10 s after the last fault and
increases the reliability and the robustness of the
frequency converter while re-establishing full control of the
motor.
In hoist applications “Protection mode” is not usable
because the frequency converter will usually not be able to
leave this mode again and therefore it will extend the time
before activating the brake – which is not recommendable.
The “Protection mode” can be disabled by setting
14-26 Trip Delay at Inverter Fault to zero which means that
the frequency converter will trip immediately if one of the
hardware limits is exceeded.
Voltage [V] Power [kW]Waiting Time [min]
380-5000.25-7.54
11-7515
90-20020
250-80040
525-69011-75 (frame
size B and C)
37-315 (frame
size D)
355-100030
15
20
1.2.2 Protection Mode
Equipment containing electrical
components may not be disposed of
together with domestic waste.
It must be separately collected with
electrical and electronic waste according
to local and currently valid legislation.
1.3.1 Software Version
Design Guide
Software version: 6.4x
This Design Guide can be used for all frequency converters with
software version 6.4x.
The software version number can be seen from 15-43 SoftwareVersion.
NOTE
It is recommended to disable protection mode in hoisting
applications (14-26 Trip Delay at Inverter Fault = 0)
4MG92B102 - VLT® is a registered Danfoss trademark
Safety and ConformityModbus RTU Operating Instruction
1.4 CE Labelling
1.4.1 CE Conformity and Labelling
The machinery directive (2006/42/EC)
Frequency converters do not fall under the machinery
directive. However, if a frequency converter is supplied for
use in a machine, Danfoss provide information on safety
aspects relating to the frequency converter.
What is CE Conformity and Labelling?
The purpose of CE labelling is to avoid technical trade
obstacles within EFTA and the EU. The EU has introduced
the CE label as a simple way of showing whether a
product complies with the relevant EU directives. The CE
label says nothing about the specifications or quality of
the product. Frequency converters are regulated by two EU
directives:
The low-voltage directive (2006/95/EC)
Frequency converters must be CE labelled in accordance
with the low-voltage directive of January 1, 1997. The
directive applies to all electrical equipment and appliances
used in the 50 - 1000 V AC and the 75 - 1500 V DC voltage
ranges. Danfoss CE-labels in accordance with the directive
and issues a declaration of conformity upon request.
The EMC directive (2004/108/EC)
EMC is short for electromagnetic compatibility. The
presence of electromagnetic compatibility means that the
mutual interference between different components/
appliances does not affect the way the appliances work.
The EMC directive came into effect January 1, 1996.
Danfoss CE-labels in accordance with the directive and
issues a declaration of conformity upon request. To carry
out EMC-correct installation, see the instructions in this
Design Guide. In addition, Danfoss specify which standards
our products comply with. Danfoss offer the filters
presented in the specifications and provide other types of
assistance to ensure the optimum EMC result.
The frequency converter is most often used by professionals of the trade as a complex component forming part
of a larger appliance, system or installation. The EMC
directive (2004/108/EC)
What Is Covered
1.4.2
The EU "Guidelines on the Application of Council Directive2004/108/EC" outline three typical situations of using a
frequency converter. See below for EMC coverage and CE
labelling.
1.The frequency converter is sold directly to the
end-consumer. The frequency converter is for
example sold to a DIY market. The end-consumer
is a layman. Installing the frequency converter for
use with a hobby machine, a kitchen appliance,
etc. For such applications, the frequency
converter must be CE labelled in accordance with
the EMC directive.
2.The frequency converter is sold for installation in
a plant. The plant is built up by professionals of
the trade. It could be a production plant or a
heating/ventilation plant designed and installed
by professionals of the trade. Neither the
frequency converter nor the finished plant has to
be CE labelled under the EMC directive. However,
the unit must comply with the basic EMC
requirements of the directive. This is ensured by
using components, appliances, and systems that
are CE labelled under the EMC directive.
3.The frequency converter is sold as part of a
complete system. The system is being marketed
as complete and could e.g. be an air-conditioning
system. The complete system must be CE labelled
in accordance with the EMC directive. The
manufacturer can ensure CE labelling under the
EMC directive either by using CE labelled
components or by testing the EMC of the system.
If only CE labelled components are used, it is
unneccessary to test the entire system.
Danfoss Frequency Converter and CE
1.4.3
Labelling
CE labelling is a positive feature when used for its original
purpose, i.e. to facilitate trade within the EU and EFTA.
However, CE labelling may cover many different specifications. Check what a given CE label specifically covers.
The covered specifications can be very different and a CE
label may therefore give the installer a false feeling of
security when using a frequency converter as a component
in a system or an appliance.
Danfoss CE labels the frequency converters in accordance
with the low-voltage directive. This means that if the
frequency converter is installed correctly, we guarantee
compliance with the low-voltage directive. Danfoss issues a
declaration of conformity that confirms our CE labelling in
accordance with the low-voltage directive.
The CE label also applies to the EMC directive provided
that the instructions for EMC-correct installation and
filtering are followed. On this basis, a declaration of
conformity in accordance with the EMC directive is issued.
The Design Guide offers detailed instructions for installation to ensure EMC-correct installation. Furthermore,
11
MG92B102 - VLT® is a registered Danfoss trademark5
Safety and ConformityModbus RTU Operating Instruction
11
Danfoss specifies which our different products comply
with.
Danfoss provides other types of assistance that can help to
obtain the best EMC result.
1.4.4 Compliance with EMC Directive
2004/108/ECEMC Directive
IP54/55. As an extra protection, coated printed circuit
boards can be ordered as an option.
Airborne Particles such as dust may cause mechanical,
electrical, or thermal failure in the frequency converter. A
typical indicator of excessive levels of airborne particles is
dust particles around the frequency converter fan. In very
dusty environments, use equipment with enclosure rating
IP54/55 or a cabinet for IP00/IP20/TYPE 1 equipment.
2004/108/EC
In environments with high temperatures and humidity,
As mentioned, the frequency converter is mostly used by
professionals of the trade as a complex component
forming part of a larger appliance, system, or installation.
Note that the responsibility for the final EMC properties of
the appliance, system or installation rests with the installer.
As an aid to the installer, Danfoss has prepared EMC installation guidelines for the Power Drive system. The standards
and test levels stated for Power Drive systems are
complied with, provided that the EMC-correct instructions
for installation are followed, see the section EMC Immunity
in the Design Guide.
Air Humidity
1.5.1
The frequency converter has been designed to meet the
IEC/EN 60068-2-3 standard, EN 50178 pkt. 9.4.2.2 at 50° C.
corrosive gases such as sulphur, nitrogen, and chlorine
compounds cause chemical processes on the frequency
converter components.
Such chemical reactions rapidly affect and damage the
electronic components. In such environments, mount the
equipment in a cabinet with fresh air ventilation, keeping
aggressive gases away from the frequency converter.
An extra protection in such areas is a coating of the
printed circuit boards, which can be ordered as an option.
NOTE
Mounting frequency converters in aggressive environments
increases the risk of stoppages and considerably reduces
the life of the converter.
Aggressive Environments
1.5.2
A frequency converter contains a large number of
mechanical and electronic components. All are to some
extent vulnerable to environmental effects.
CAUTION
The frequency converter should not be installed in
environments with airborne liquids, particles, or gases
capable of affecting and damaging the electronic
components. Failure to take the necessary protective
measures increases the risk of stoppages, thus reducing
the life of the frequency converter.
Degree of protection as per IEC 60529
The Safe Stop function may only be installed and operated
in a control cabinet with degree of protection IP54 or
higher (or equivalent environment). This is required to
avoid cross faults and short circuits between terminals,
connectors, tracks and safety-related circuitry caused by
foreign objects.
Liquids can be carried through the air and condense in the
frequency converter and may cause corrosion of
components and metal parts. Steam, oil, and salt water
may cause corrosion of components and metal parts. In
such environments, use equipment with enclosure rating
Before installing the frequency converter, check the
ambient air for liquids, particles, and gases. This is done by
observing existing installations in this environment. Typical
indicators of harmful airborne liquids are water or oil on
metal parts, or corrosion of metal parts.
Excessive dust particle levels are often found on installation cabinets and existing electrical installations. One
indicator of aggressive airborne gases is blackening of
copper rails and cable ends on existing installations.
D and E enclosures have a stainless steel back-channel
option to provide additional protection in aggressive
environments. Proper ventilation is still required for the
internal components of the frequency converter. Contact
Danfoss for additional information.
1.5.3
Vibration and Shock
The frequency converter has been tested according to the
procedure based on the shown standards:
The frequency converter complies with requirements that
exist for units mounted on the walls and floors of
production premises, as well as in panels bolted to walls or
floors.
6MG92B102 - VLT® is a registered Danfoss trademark
Safety and ConformityModbus RTU Operating Instruction
IEC/EN 60068-2-6: Vibration (sinusoidal) - 1970
•
IEC/EN 60068-2-64: Vibration, broad-band random
•
11
MG92B102 - VLT® is a registered Danfoss trademark7
IntroductionModbus RTU Operating Instruction
2 Introduction
22
confirming the action taken, any data to be returned, and
2.1 Introduction
This manual explains how to physically establish and
configure communication between the Danfoss FC Series
and a controller using the Modbus RTU protocol.
This instruction is intended to be used for both instruction
and reference. It only briefly touches on the basics of the
Modbus protocol whenever necessary to gain an
understanding of the Modbus RTU. This instruction is also
intended to serve as a guideline to specify and optimise
the communication system. Even experienced Modbus
programmers, should read these entire operating
instructions before starting programming since important
information can be found in all sections.
Modbus RTU Overview
2.1.1
Regardless of the type of physical communication
networks, the Modbus RTU Overview describes the process
a controller uses to request access to another device. This
process includes how the Modbus RTU responds to
requests from another device, and how errors are detected
and reported. It also establishes a common format for the
layout and contents of message fields.
During communications over a Modbus RTU network, the
protocol determines:
an error-checking field. If an error occurs in receipt of the
message, or if the slave is unable to perform the requested
action, the slave constructs an error message, and sends it
in response, or a time-out occurs.
How each controller learns its device address
Recognizes a message addressed to it
Determines which actions to take
Extracts any data or other information contained
in the message
If a reply is required, the controller constructs the reply
message and sends it.
Controllers communicate using a master-slave technique in
which only one device (the master) can initiate
transactions (called queries). The other devices (slaves)
respond by supplying the requested data to the master, or
by taking the action requested in the query.
The master can address individual slaves, or can initiate a
broadcast message to all slaves. Slaves return a message
(called a response) to queries that are addressed to them
individually. No responses are returned to broadcast
queries from the master. The Modbus RTU protocol
establishes the format for the master’s query by placing
into it the device (or broadcast) address, a function code
defining the requested action, any data to be sent, and an
error-checking field. The slave’s response message is also
constructed using Modbus protocol. It contains fields
8MG92B102 - VLT® is a registered Danfoss trademark
Wire # 1
Wire # 2
Data InData Out
175ZB021.10
Wire #1
Wire #2
175ZB028.10
130BA060.11
68 6968 6968 69
RS 485
RS 232
USB
+
-
RS-485 Installation and Set...Modbus RTU Operating Instruction
3 RS-485 Installation and Set-up
3.1.1 Overview
The Modbus RTU protocol is based on the built-in RS-485
(EIA-485) interface on the FC Drive series control card.
RS-485 is a two-wire bus-interface that allows multi-drop
network topology i.e. nodes can be connected as a bus
(daisy chain), or via drop cables from a common trunk line.
Danfoss uses the two-wire system where the communication between master and slave is half-duplex, i.e. it
cannot transmit and receive at the same time.
Each signal uses one twisted-pair line — two wires twisted
around themselves. This is known as balanced data
transmission or differential voltage transmission (see
Illustration 3.1). The signal on one wire is ideally the exact
opposite of the signal on the second wire. In other words,
if one wire is transmitting a high, the other wire transmits
a low, and vice versa (see Illustration 3.2).
Since RS-485 is a multipoint communication system, all
devices are connected to the single twisted-pair cable.
3.1.2 Cable Specifications
When choosing a transmission line for RS-485, it is
necessary to examine the required distance of the cable
and the data rate of the system. Losses in a transmission
line are a combination of AC losses (skin effect), DC
conductor loss, leakage, and AC losses in the dielectric. In
high-quality cable, the conductor losses and the dielectric
losses are on the same order of magnitude.
The recommended maximum Modbus cable length
between the frequency converter and the Controller must
not exceed 30 m (100 feet). While the RS-485 specification
does not specify cabling, the recommendation is 0.25
mm2/24 AWG shielded twisted-pair cable with a shunt
capacitance of 16 pF/ft and 100 Ω impedance. Another
choice is the same cable commonly used in the twistedpair Ethernet cabling. This cable is commonly referred to
as Category 5 cable. The cable has a maximum capacitance
of 17 pF/ft (14.5 pF/ft typical) and characteristic impedance
of 100 Ω.
Network Connection
3.1.3
3
3
Illustration 3.1 Balanced Data Transmission
Illustration 3.2 Differential Concept
The Modbus RTU uses master/slave architecture, where
each slave device has its unique address and responds
only to packets addressed to this device.
The packets are generated by the master (Controller),
which periodically polls all connected slave devices. Data
travels over the single line in both directions.
According to the EIA-485 specification a total number of
32 nodes can be connected to one Modbus RTU network
segment, and a total of 247 nodes in a network are
supported. Network segments are divided with repeaters.
NOTE
Each repeater counts for a node in each segment it is
installed. Every node connected to the same network must
have a unique nodes address, across all segments.
One or more frequency converters can be connected to a
control (or master) using the RS-485 standardized interface.
Terminal 68 is connected to the P signal (TX+, RX+), while
terminal 69 is connected to the N signal (TX-,RX-).
If more than one frequency converter is connected to a
master, use parallel connections.
MG92B102 - VLT® is a registered Danfoss trademark9
130BB021.10
12 13 18 19 27 29 32
33 20 37
Remove jumper to enable Safe Stop
61 68 6939 42 50 53 54 55
130BT310.10
1
2
N O
V LT
BUS TER.
OFF-ON
A53 A54
U- I U- I
3
RS-485 Installation and Set...Modbus RTU Operating Instruction
Illustration 3.3 Control Card Terminals
RS-485 Bus Termination
3.1.4
The RS-485 bus terminate by a resistor network at both
ends only. For this purpose, set switch S801 on the control
card for "On".
10MG92B102 - VLT® is a registered Danfoss trademark
Fieldbus cable
Min.200mm
90° crossing
130BA080.11
RS-485 Installation and Set...Modbus RTU Operating Instruction
3.1.5 EMC Precautions
The following EMC precautions are recommended to
achieve interference-free operation of the RS-485 network.
Relevant national and local regulations, for example
regarding protective earth connection, must be observed.
The RS-485 communication cable must be kept away from
motor and brake resistor cables to avoid coupling of high
frequency noise from one cable to another. Normally a
distance of 200 mm (8 inches) is sufficient, but keeping the
greatest possible distance between the cables is generally
recommended, especially where cables run in parallel over
long distances. When crossing is unavoidable, the RS-485
cable must cross motor and brake resistor cables at an
angle of 90o.
3
3
MG92B102 - VLT® is a registered Danfoss trademark11
Loading...
+ 27 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.