Danfoss MMILDS Data sheet

Data Sheet

Control panel

Type MMILDS

Electronic controller suitable for all HVAC/R software application needs.

MMILDS is MCX’s family remote interface. It’s •tted with a LED display for displaying data from a MCX or from 2 probes that can be locally connected. The connection with any MCX controller is through the CAN bus network. The power supply comes from controller which it is connected. All the information about the user interface is loaded inside the MCX controller; that’s why there is no need of programming the MMILDS interface.

Features:

• LED display 3-½ digit

• Easy connection to MCX CANbus network through wired connector kit

• Connections for 2 external probes

• Powered by the MCX which it is connected to

• Dimensions 84 x 36 mm

• Panel mounting

AI184586421012en-000501

Danfoss MMILDS Data sheet

Control panel, type MMILDS

Product speci€cation

General features

Table 1: General features

Features

Description

Power supply

From the MCX through the RJ12 telephone connector

 

Maximum power consumption: 1.5 W

Analog input

AI1: 0 / 20 mA, 4 / 20 mA, 0 / 5 V, 0 / 1 V

 

AI2: NTC, default 10 kΩ a 25 °C

Operating conditions

CE: -20T60, 90% RH non-condensing

Storage conditions

-30T80, 90% RH non-condensing

Integration

In Class I and / or II appliances

Index of protection

IP65

Period of electric stress across insulat-

Long

ing parts

 

Resistance to heat and •re

Category D

Immunity against voltage surges

Category I

Software class and structure

Class A

Construction

To be incorporated

 

 

Con€guration

Figure 1: Key reference

<![if ! IE]>

<![endif]>ANFOSS80G8100.01

<![if ! IE]>

<![endif]>D

Table 2: Con€guration

Function

Keys

Enter Program Mode

1+3 for 2s

Exit Program Mode

1+3

Scroll list of parameters

1 (scroll UP) and 3 (scroll DOWN)

Edit value

2

Esc and NOT Save

2

Esc and Save

2 pressed for 3 seconds

 

 

Table 3: Type of codes

Code

Description

Values

Default

NID

CAN node ID

1-127; 255=not con•gured

255

BAU

CAN baudrate (kBd)

0, 20, 50, 125, 250, 1000; 0=auto baud

50

CON

CAN address of the MCX connected

1-127; 255=auto detect

255

TYP

Type of AI1 analog input

2=0 / 5 V, 3=4 / 20 mA, 7=0 / 1 V, 9=0 / 20 mA

2

SEL

Analog input to be displayed

0=no, 1=AI1, 2=AI2

2

 

 

 

 

© Danfoss | Climate Solutions | 2021.03

AI184586421012en-000501 | 2

Loading...
+ 3 hidden pages