Danfoss MCI 15 DOL Installation guide [da]

INSTRUCTIONS
Montering - Mounting - Montage mm (inch)
047C0422
DK Hvis enhed er monteret vandret reducer strøm med 50% UK If unit is mounted horizontally derate current by 50% D Falls Einheit horizontal montiert wird, reduziert sich der Strom
um 50%.
Mål - Dimensions - Abmessungen mm (inch)
MCI 15 DOL
DK Køleplade skal holdes ren. Luftstrøm må ikke blokeres UK Keep heat sink clean. Airflow should not be blocked D Kühlflächen freihalten. Luftstrom muß ungehindert fließen
047C0422
Forbindelse - Wiring - Verdrahtung
75°C
K
abel/wire* mm2 (AWG) mm2 (AWG)
0.75 - 4 0 (18 - 12) (20 - 16)
2 x 1 2 (2 x 18) (2 x 20 - 18)
0.75 - 6 0 (18 - 10) (20 - 16)
2 x 0.75 - 2.5 2 x 0.5 - 1.5 (
2 x 18 - 14) (2 x 20 - 16)
0.75 - 6 0 (18 - 10) (20 - 16)
2 x 0.75 - 1.5 2 x 0.5 - 1.5 (
2 x 18 - 16) (2 x 20 - 16)
Pozidrive 1 0
.5 Nm max. N.A.
4.4 lb-in max.
4 mm 3
0.5 Nm max. 0.5 Nm max.
4.4 lb-in max. 4.4 lb-in max.
- Vigtigt: (
- Important: (Observe the maximum screw torque limits)
- Wichtig: (Max. Drehmoment beachten)
* Use copper only
Overhold max. skruedrejningsmomenter)
.5 - 1.5
x 0.5 - 0.75
.5 - 1.5
.5 - 1.5
mm
24-480 V2
4-60 V
UL: Use thermal overload protection as required by the National Electric Code UL: When protected by a non-time delay K5 or H Class fuse, rated 266% of motor FLA, this device is rated
for use on a circuit capable of delivering not more than 5,000 rms. symmetrical amperes, 600 V maximum. Maximum surrounding temperature 40°C
© Danfoss | DCS (rja) | 2015-09 IC.PI.C50.D2.51
520B6904