Micro Channel Heat Exchanger
Type MCHE D1900-C
Condenser – standard series
D1900-C is ideal for use in many different applications, such as chillers and commercial split/roof tops.
MCHEs have an ingeniously simple allaluminum design that is not only lightweight but also prevents galvanic corrosion.
The refrigerant-carrying tubes are formed to optimize heat transfer, enabling the production of more compact, but equally effective, cooling solutions. The smart louvered fin design maximizes surface contact, reducing the airside pressure loss, improving efficiency and reducing noise levels.
Features:
• Reduce refrigerant system charge
• Improve efficiency – More compact/better COP/increased capacity
• Cost - Less sensitive to …uctuations in raw material prices
• Better corrosion characteristics due to allaluminum design
AI133486416540en-000701
Micro Channel Heat Exchanger, type MCHE D1900-C
Product speci€cation
Technical data
Table 1: Technical data
|
|
|
|
|
Inlet ID |
Outlet ID |
Continuous |
Max. working |
||
Model |
Coil length |
Coil height |
Core depth |
Fin pitch |
operating |
|||||
diameter |
diameter |
pressure |
||||||||
|
|
|
|
|
temperature |
|||||
|
|
|
|
|
|
|
|
|||
D1900-C |
1274 (mm) |
1362.9 (mm) |
25.4 (mm) |
1.1 (mm) |
22.4 (mm) |
22.4 (mm) |
-40 °C / 121 |
°C |
45 (bar) |
|
50.2 (in) |
53.7 (in) |
1.0 (in) |
23 (FPI) |
0.88 (in) |
0.88 (in) |
-40 °F / 250 |
°F |
650 (psi) |
||
|
||||||||||
|
|
|
|
|
|
|
|
|
|
Weight / internal volume
Coil weight: 19.8 kg / 43.8 lb
Internal volume: 3.49 l / 212.97 in3
Material speci€cation
MPE Tube: AA3102
Fins: AA3003Mod clad with AA4343
Manifold: AA3003 clad with AA4343
Side plate: AA3003
Inlet/Outlet tubes: Copper
Performance data
Table 2: Performance data of R410A and R134a
Air Velocity |
|
|
|
Performance [KW/Btu/h×1000] |
|
|
|
|
[m/s] |
|
R410A |
|
|
R134a |
|
||
[ft/min] |
Δ=10 K / 18 °F |
Δ=15 K / 27 °F |
Δ=20 K / 36 °F |
Δ=25 K/ 45 °F |
Δ=10 K / 18 °F |
Δ=15 K / 27 °F |
Δ=20 K / 36 °F |
Δ=25 K/ 45 °F |
1.0/197 |
18.1/61.76 |
27.5/93.83 |
37.27/127.17 |
46.91/160.06 |
17.33/59.13 |
26.34/89.87 |
35.31/120.48 |
44.27/151.05 |
1.5/295 |
25.81/88.06 |
39.93/136.24 |
53.68/183.16 |
67.65/230.82 |
24.42/83.32 |
37.28/127.2 |
50.11/170.98 |
63.59/216.97 |
2.0/394 |
32.78/111.85 |
51.12/174.42 |
68.76/234.61 |
86.71/295.85 |
30.68/104.68 |
47/160.36 |
64.08/218.64 |
80.63/275.11 |
2.5/492 |
40.18/137.09 |
61.34/209.29 |
82.7/282.17 |
104.36/356.08 |
36.25/123.69 |
55.72/190.12 |
76.24/260.13 |
95.23/324.92 |
3.0/591 |
46.35/158.15 |
70.93/242.01 |
95.65/326.36 |
120.72/411.9 |
41.28/140.85 |
64.53/220.18 |
87.27/297.77 |
108.75/371.06 |
|
|
|
|
|
|
|
|
|
Table 3: Performance data of R404A and R407C
Air Velocity |
|
|
|
Performance [KW/Btu/h×1000] |
|
|
|
|
[m/s] |
|
R404A |
|
|
R407C |
|
||
[ft/min] |
Δ=10 K / 18 °F |
Δ=15 K / 27 °F |
Δ=20 K / 36 °F |
Δ=25 K/ 45 °F |
Δ=10 K / 18 °F |
Δ=15 K / 27 °F |
Δ=20 K / 36 °F |
Δ=25 K/ 45 °F |
1.0/197 |
18.03/61.52 |
27.42/93.56 |
37.41/127.64 |
46.99/160.33 |
12.12/41.35 |
22.36/76.29 |
31.94/108.98 |
41.54/141.73 |
1.5/295 |
25.47/86.9 |
39.86/136 |
53.59/182.85 |
67.45/230.14 |
17.05/58.17 |
31.77/108.4 |
45.55/155.42 |
60.06/204.92 |
2.0/394 |
32.06/109.39 |
50.67/172.89 |
68.24/232.83 |
85.97/293.33 |
21.35/72.85 |
40.24/137.3 |
58.83/200.73 |
76.46/260.88 |
2.5/492 |
39.61/135.15 |
60.59/206.73 |
81.61/278.45 |
102.88/351.03 |
25.11/85.68 |
47.92/163.5 |
70.51/240.58 |
91.53/312.3 |
3.0/591 |
45.6/155.59 |
69.65/237.65 |
93.84/320.18 |
118.42/404.05 |
28.57/97.48 |
56.28/192.03 |
80.89/276 |
105.35/359.45 |
|
|
|
|
|
|
|
|
|
© Danfoss | Climate Solutions | 2021.02 |