Danfoss MCHE D1300-C Data sheet

Data Sheet
Micro Channel Heat Exchanger Type MCHE D1300-C
Condenser – standard series
D1300-C is ideal for use in a number of various applications, such as Residential AC, Condensing units, Air driers, Cabinet cooling and Indoor display.
MCHEs have an ingeniously simple all­aluminum design that is not only lightweight but also prevents galvanic corrosion.
The refrigerant-carrying tubes are formed to optimize heat transfer, enabling the production of more compact, but equally eective, cooling solutions. The smart louvered n design maximizes surface contact, reducing the air­side pressure loss, improving eciency and reducing noise levels.
Features:
• Reduce refrigerant system charge
• Improve eciency – More compact/better COP/increased capacity
• Cost - Less sensitive to uctuations in raw material prices
• Better corrosion characteristics due to all­aluminum design
AI133486416424en-000701
Model
Coil length
Coil height
Core depth
Fin pitch
Inlet ID
diameter
Outlet ID diameter
Continuous
operating
temperature
Max. working
pressure
D1300-C
552 (mm)
21.7 (in)
517 (mm)
20.3 (in)
16 (mm)
0.6 (in)
1.1 (mm) 23 (FPI)
9.7 (mm) 0.38 (in)
8.2 (mm)
0.32 (in)
-40 °C / 121 °C
-40 °F / 250 °F
45 (bar)
650 (psi)
Air Velocity
Performance [KW/Btu/h×1000]
[m/s]
R410A
R134a
[ft/min]
Δ=10 K / 18 °F
Δ=15 K / 27 °F
Δ=20 K / 36 °F
Δ=25 K/ 45 °F
Δ=10 K / 18 °F
Δ=15 K / 27 °F
Δ=20 K / 36 °F
Δ=25 K/ 45 °F
1.0/197
2.08/7.1
3.73/12.73
5.08/17.33
6.42/21.91
2.3/7.85
3.61/12.32
4.91/16.75
6.2/21.15
1.5/295
3.27/11.16
5.15/17.57
7.02/23.95
9.23/31.49
3.15/10.75
4.98/16.99
6.78/23.13
8.57/29.24
2.0/394
4.05/13.82
6.39/21.8
9.04/30.84
11.61/39.61
3.89/13.27
6.16/21.02
8.41/28.69
10.65/36.34
2.5/492
4.75/16.21
7.49/25.56
10.74/36.64
13.79/47.05
4.54/15.49
7.22/24.63
9.85/33.61
12.49/42.62
3.0/591
5.37/18.32
8.49/28.97
12.49/42.62
15.79/53.88
5.13/17.5
8.16/27.84
11.18/38.15
14.41/49.17
Air Velocity
Performance [KW/Btu/h×1000]
[m/s]
R404A
R407C
[ft/min]
Δ=10 K / 18 °F
Δ=15 K / 27 °F
Δ=20 K / 36 °F
Δ=25 K/ 45 °F
Δ=10 K / 18 °F
Δ=15 K / 27 °F
Δ=20 K / 36 °F
Δ=25 K/ 45 °F
1.0/197
2.37/8.09
3.71/12.66
5.04/17.2
6.55/22.35
1.44/4.91
2.98/10.17
4.37/14.91
5.74/19.58
1.5/295
3.23/11.02
5.08/17.33
6.91/23.58
9.27/31.63
1.87/6.38
4.1/13.99
6.03/20.57
7.95/27.13
2.0/394
3.96/13.51
6.26/21.36
9.07/30.95
11.65/39.75
2.51/8.56
5.08/17.33
7.49/25.56
9.88/33.71
2.5/492
4.61/15.73
7.29/24.87
10.75/36.68
13.79/47.05
2.93/10
5.93/20.23
8.78/29.96
11.67/39.82
3.0/591
5.18/17.67
8.31/28.35
12.28/41.9
15.77/53.81
3.27/11.16
6.7/22.86
9.94/33.92
13.73/46.85
Micro Channel Heat Exchanger, type MCHE D1300-C
Product specication
Technical data
Table 1: Technical data
Weight / internal volume
Coil weight: 2.174 kg / 4.8 lb Internal volume: 0.4 l / 24.41 in
3
Material specication
MPE Tube: AA3102 Fins: AA3003Mod clad with AA4343 Manifold: AA3003 clad with AA4343 Side plate: AA3003 Inlet/Outlet tubes: Copper
Performance data
Table 2: Performance data of R410A and R134a
Table 3: Performance data of R404A and R407C
© Danfoss | Climate Solutions | 2021.02 AI133486416424en-000701 | 2
Loading...
+ 3 hidden pages