Data Sheet
Thermostat
Type KPU 19
KPU 19 thermostats are used for temperature
regulation in refrigeration, freezing, air
conditioning, ventilating and heating systems.
KPU 19 thermostats are tted with Single-Pole
Double-Throw (SPDT) or Single-Pole SingleThrow (SPST) contact system.
The standard KPU 19 enclosure is rated NEMA ~
1.
NEMA ~ 1 is obtained when the thermostat is
mounted on a at surface with all unused holes
covered.
Features
• Long operational life time
• Stable settings
• Reliable and robust SPST and SPDT contact
system
• Switching points can be set easily and
accurately using the range scale plate and
dierential adjusting knob.
• Terminals enable easy wiring
• KPU 19 easily replaces other manufacturers’
thermostats
AI209586429202en-000401

M
I
N
DIFF.
1.7
0.63 0.59
0.14
0.27
4.48
2.4
0.19
0.55
2.12
-31 – 140 °F for KPU with remote bulb
-31 – 140 °F for KPU with room sensor
SPST (close on temp. rise), SPDT
Locked rotor
96A / 120V AC
NEMA ~1 (when mounted on a at surface with all unused holes covered)
1. Terminals C – H close high and open low terminals C – L can be used as
low temperature alarm.
1. Low temperature cut-out
2. Terminals C – L open high and close low terminals C – H can be used as
high temperature alarm.
2. High temperature cut-out
Terminals C – H close high and open low
1. Low temperature cut-out
2. Condenser fan cycling control
Thermostat, KPU 19
Product specication
Technical data
Table 1: Technical data
Contact system
Table 2: Contact system
Dimensions [in]
Figure 1: Dimensions [in]
© Danfoss | Climate Solutions | 2021.02 AI209586429202en-000401 | 2