Danfoss KPP-SPD Operating guide

User Manual
PLUS+1® Compliant
KPP_SPD Speed Sensor Function Block
www.danfoss.com
PLUS+1® Compliant KPP_SPD Speed Sensor Function Block
Revision history Table of revisions
Date Changed Rev
January 2019 Rebranding 0103
November 2011 BA
2 | © Danfoss | January 2019 11022915 | AQ00000070en-000103
PLUS+1® Compliant KPP_SPD Speed Sensor Function Block

Contents

KPP_SPD Function Block
Inputs....................................................................................................................................................................................................4
Function Block Parameter Values...............................................................................................................................................4
Outputs................................................................................................................................................................................................ 5
Function Block Connections.........................................................................................................................................................5
Using Namespaces...........................................................................................................................................................................5
Change Namespace Value.......................................................................................................................................................6
Include Advanced Checkpoint with Namespace in Compiled Application...........................................................6
Status and Fault Logic.....................................................................................................................................................................7
Status Logic........................................................................................................................................................................................ 7
Fault Logic...........................................................................................................................................................................................7
Fault Reporting Examples........................................................................................................................................................8
Speed Sensor 1 Fault Detection....................................................................................................................................... 8
Speed Sensor 2 Fault Detection....................................................................................................................................... 8
Legacy MC Controller—Input Configuration.........................................................................................................................9
Configure the MFIn..................................................................................................................................................................10
SC and Non-Legacy MC Controller—Input Configuration..............................................................................................10
Configure the MFIn..................................................................................................................................................................10
Customizable Service Screens...................................................................................................................................................11
Pre-Made Service Screen for Speed Sensor Function Block......................................................................................11
Pre-Made Service Screen Panel Components for Speed Sensor Function Block.............................................. 13
©
Danfoss | January 2019 11022915 | AQ00000070en-000103 | 3
PLUS+1® Compliant KPP_SPD Speed Sensor Function Block

KPP_SPD Function Block

The KPP_SPD function block outputs an RPM signal that is based on inputs from a KPP speed sensor.
This function block receives its Spd input through MFIn.

Inputs

Inputs to the function block are described.
Input Type Range Description Para —— —— Input for a user-defined Pulse/Rev value that defines the number of pulses equal to one
revolution. Optionally, inputs a:
FaultDetTm value that replaces the function block’s internal default fault-direction time.
DirLockHz value that replaces the function block's internal default fault direction-lock frequency. SnsrPwr —— —— Reports sensor power supply voltage. Spd —— —— Speed signal from the speed sensor.

Function Block Parameter Values

The para bus input signals, which set the KPP_SPD function block's operating characteristics, are described.
The input signals of the Para bus set the function block’s operating characteristics. The Puls/Rev value is specified outside of the function block for the specific sensor used. Typically, you do not have to change any of the other values for the correct operation of the function block.
Input Type Range Description Puls/Rev U16 1–600 Sets the conversion factor that is used to convert the measured frequency from Hz to RPM. FaultDetTm U16 0-65535 Sets the delay time before the function block:
Reports a detected fault.Clears a reported fault that is no longer detected.
4 | © Danfoss | January 2019 11022915 | AQ00000070en-000103
PLUS+1® Compliant KPP_SPD Speed Sensor Function Block
KPP_SPD Function Block

Outputs

Outputs of the function block are described.
Output Type Range Description Diag —— —— Outputs a Diag bus that has a:
Para sub-bus.
FltTmrFreq signal. Also has a Checkpoints page which you can set to enable advanced checkpoint with
namespace components. This makes all of the function block's input, output, and internal signals available to the Service Tool.
Status U16 —— Reports the function block’s status conditions. Fault U16 —— Reports the function block’s fault conditions. RPM U32 0–9000000 rpm The calculated rpm.
1—1.0 rpm.
dRPM U32 0–9000000 x .1 Legacy signal, previously labeled RPM in version 1.03 and earlier.
10—1.0 rpm.

Function Block Connections

Connections you can make with the KPP_SPD function block are described.
Item Description
1 Pulses per revolution value. 2 Sensor power supply voltage. 3 Sensor speed. 4 Diagnostic signals. 5 Function block status. 6 Function block faults. 7 RPM output. 8 dRPM output.

Using Namespaces

Namespaces can help you successfully compile an application that uses the same function block more than once.
Change each function block's namespace by setting its Namespace value to something unique. If you do not change the Namespace value, you cannot compile the application.
©
Danfoss | January 2019 11022915 | AQ00000070en-000103 | 5
Loading...
+ 9 hidden pages