This Fitters Notes, gives practical hints about Danfoss commercial
refrigeration controls (mechanical) and Danfoss compressors.
If you need further information about the Danfoss product range please
contact your dealer or local Danfoss agency. You can also find some very
useful information on our web site:
www.danfoss.com
We hope that this book will help you in your daily work.
A thermostatic expansion valve is built up around
a thermostatic element (1) separated from the
valve body by a diaphragm.
A capillary tube connects the element to a bulb
(2) and a valve body with valve seat (3) and a
spring (4).
A thermostatic expansion valve works like this:
The function of a thermostatic expansion valve is
determined by three fundamental pressures:
P1: Bulb pressure which acts on the upper
surface of the diaphragm, in the valve
opening direction.
P2: Evaporating pressure which acts on the
underside of the diaphragm, in the valve
closing direction.
P3: Spring pressure which also acts on the
underside of the diaphragm, in the valve
closing direction.
When the expansion valve regulates, balance is
created between bulb pressure on one side of the
diaphragm and evaporating pressure plus spring
force on the other side.
The spring is used to set superheat.
Ad0-0001
Introduction
Superheat is measured at the point where the
bulb is located on the suction line and is the
diff erence between the temperature at the
bulb and the evaporating pressure/evaporating
temperature at the same point.
Superheat is measured in Kelvin (K) and is used as
a signal to regulate liquid injection through the
expansion valve.
Ad0-0012
Ad0-0015
Superheat
SubcoolingSubcooling is defi ned as the diff erence between
condensing pressure/temperature and liquid
temperature at the expansion valve inlet.
Subcooling is measured in Kelvin (K).
Subcooling of the refrigerant is necessary to
avoid vapour bubbles in the refrigerant ahead of
the expansion valve.
Vapour bubbles in the refrigerant reduce capacity
in the expansion valve and thereby reduce liquid
supply to the evaporator.
Subcooling of 4-5K is adequate in most cases.
Fitters notes Thermostatic expansion valves
External pressure
equalization
Expansion valves with external pressure equalization must always be used if liquid distributors
are installed.
Typically, the use of distributors gives a pressure
drop of 1 bar across distributor and distribution
tubes.
Expansion valves with external pressure equalization should always be used in refrigeration
systems with heavy evaporators or plate
exchangers, where normally the pressure drop
will be greater than pressure corresponding to
2K.
ChargesThermostatic expansion valves can contain one
of three different types of charge:
1. Universal charge
2. MOP charge
3. MOP charge with ballast, standard for Danfoss
expansion valves with MOP.
Universal charge
Expansion valves with Universal charge are used
in most refrigeration systems where there is no
pressure limitation requirement and where the
bulb can be located warmer than the element
or at high evaporating temperature/evaporating
pressure.
Ad0-0016
MOP charge
Universal charge means that there is liquid
charge in the bulb. The amount of charge is so
large that charge remains in the bulb irrespective
of whether the element is colder or warmer than
the bulb.
Expansion valves with MOP charge are typically
used on factory-made units where suction
pressure limitation on starting is required, e.g.
in the transport sector and in air conditioning
systems.
All expansion valves with MOP have a very small
charge in the bulb.
This means that the valve or the element must be
located warmer than the bulb. If it is not, charge
can migrate from the bulb to the element and
prevent the expansion valve from functioning.
MOP charge means limited liquid charge in the
bulb.
“MOP” stands for Maximum Operating Pressure
and is the highest suction pressure/ evaporating
pressure permissible in the evaporator/suction
line.
The charge will have evaporated when the
temperature reaches the MOP point. Gradually,
as the suction pressure rises, the expansion valve
begins to close at approx. 0.3/0.4 bar below the
MOP point. It becomes completely closed when
the suction pressure is the same as the MOP
point.
Expansion valves with MOP ballast charges are
used mainly in refrigeration systems with “highdynamic” evaporators, e.g. in air conditioning
systems and plate heat exchangers with high
heat transfer.
With MOP ballast charge, up to 2 - 4 K less
superheat can be obtained than with other types
of charge.
The bulb in a thermostatic expansion valve
contains a material of high porosity and large
surface area in relation to weight.
MOP charge with ballast has a damping effect on
expansion valve regulation.
The valve opens slowly as bulb temperature rises
and closes quickly as bulb temperature fails.
The thermostatic expansion valve can be selected when the following are known:
Subcooling
Pressure drop across valve
Internal or external pressure equalization
expansion valves
Thermostatic
IdentificationThe thermostatic element is fitted with a laser
engraving on top of the diaphragm.
The code refers to the refrigerant for which the
valve is designed:
L = R410A
N = R134a
S = R404A/ R507
X = R22
Z = R407C
This engraving gives valve type (with code
number), evaporating temperature range, MOP
point, refrigerant, and max. working pressure,
PS/MWP.
With TE 20 and TE 55 the rated capacity is
stamped on a band label fastened to the valve.
The orifice assembly for T2 and TE2 is marked
with the orifice size (e.g. 06) and week stamp +
last number in the year (e.g. 279).
The orifice assembly number is also given on the
lid of its plastic container.
On TE 5 and TE 12 the upper stamp (TE 12)
indicates for which valve type the orifice can be
used. The lower stamp (01) is the orifice size.
On TE 20 and TE 55 the lower stamp (50/35 TR
N/B) indicates the rated capacity in the two
evaporating temperature ranges N and B, and the
refrigerant. (50/35 TR = 175 kW in range N and
123 kW in range B).
The upper stamp (TEX 55) refers to the valve type
for which the assembly can be used.
The bulb is best mounted on a horizontal suction
line tube and in a position corresponding to
between 1 o’clock and 4 o’clock.
Location depends on the outside diameter of the
tube.
Note:
The bulb must never be located at the bottom
of the suction line due to the possibility of oil
laying in the bottom of the pipe causing false
signals.
Ad0-0002
Ad0-0003
InstallationThe expansion valve must be installed in the
liquid line, ahead of the evaporator, with its
bulb fastened to the suction line as close to the
evaporator as possible.
If there is external pressure equalization, the
equalizing line must be connected to the suction
line immediately after the bulb.
The bulb must not be installed after a heat
exchanger because in this position it will give
false signals to the expansion valve.
The bulb must not be installed close to components of large mass as this also will give rise to
false signals to the expansion valve
Ad0-0004
Ad0-0005
Ad0-0006
The bulb must be able to sense the tem pe ra tu re
of the superheated suction vapour and must
therefore not be located in a position that will
expose it to extraneous heat/cold.
If the bulb is exposed to a warm air current,
insulation of the bulb is recommended.
The Danfoss bulb strap allows a tight and secure
fi tting of the bulb to the tube, thereby securing
that the bulb has ultimate thermal contact to
the suction tube. The TORX design of the screw
makes it easy for the fi tter to transfer the torque
from the tool to the screw without having to
press the tool into the screw slot. Furthermore,
with the TORX slot design, there is no risk of
damaging the screw slot.
Fitters notes Thermostatic expansion valves
Installation (cont.)
As previously mentioned, the bulb must be
installed to the horizontal part of the suction line
immediately after the evaporator. It must not be
installed to a collection tube or a riser after an oil
pocket.
The expansion valve bulb must always be
installed ahead of any liquid lock.
Ad0-0007
expansion valves
Thermostatic
Ad0-0008
SettingThe expansion valve is supplied with a factory
setting suitable for most applications.
If necessary, readjustment can be made using the
setting spindle on the valve.
Turning the spindle clockwise increases the
expansion valve superheat and turning it
counterclock-wise reduces it.
For T /TE 2, one turn of the spindle produces a
change of approx. 4K in the superheat at 0°C
evaporating temperature.
For TE 5 and following sizes, one turn of the
spindle produces a change of approx. 0.5K in
the superheat at 0°C evaporating temperature.
For TUA and TUB, one turn of the spindle
produces a change of approx. 3K in the superheat at 0°C evaporating temperature.
Hunting in the evaporator can be eliminated by
the following procedure:
Increase the superheat by turning the expansion
valve setting spindle well to the right (clockwise)
so that hunting stops. Then turn the setting
spindle in counter-clockwise steps so that
hunting again occurs.
From this position, turn the spindle about once
clockwise (but only 1/4 turn for T /TE 2 valves).
On this setting the refrigeration system will not
hunt and the evaporator is fully utilized.
A variation of 1 K in superheat is not regarded as
hunting.
Ad0-0010
Ad0-0011
Orifice assembly
replacement
If the superheat in the evaporator is too high, the
reason might be an inadequate supply of liquid
refrigerant.
The superheat can be reduced by turning the
expansion valve setting spindle counterclockwise
in steps until hunting is observed.
From this setting, the spindle must be turned
about once clockwise (but only 1/4 turn for T/TE
2). This setting fully utilizes the evaporator.
A variation of 1 K in superheat is not regarded as
hunting.
Ad0-0013
If the evaporator continues to hunt, regardless of
the superheat setting, the valve capacity might
be too high and the orifice assembly, or the valve,
needs replacing with a smaller one.
If the evaporator superheat is too high the valve
capacity is too low and the orifice assembly must
be replaced with a larger one.
TE, T2, TUA, TCAE valves are supplied with an
interchangeable orifice.
All EVR/EVRA, and EVH types solenoid valves
operate only when installed correctly in the
direction of flow, i.e. in the direction indicated by
the arrow.
Normally, solenoid valves installed ahead of a
thermostatic expansion valve must be close to
that valve.
This avoids liquid hammer when the solenoid
valve opens.
Ensure that pipes around the valve are properly
installed so that no fracture can occur.
Solenoid valves
Af0_0001
Af0_0003
EVRA 32 & 40 precautions
Brazing/welding EVR/EVRA and EVH solenoid
valves does not normally necessitate dismantling,
provided steps are taken to avoid heating the
valve.
Note! Always protect the armature tube against
weld spatter.
After tacking the valve to the pipe, remove the
valve body to protect O-rings and gaskets against
heat. In installations with welded steel pipe, a
FA type strainer or similar mounted ahead of the
solenoid valve is recommended. (On new plant,
flushing out before starting up is recommended).
All solenoid valves in the system must be open,
either by applying voltage to the coils or by
opening the valves manually (provided a manual
operation spindle is fi tted).
Remember to screw the spindle back before
starting up, otherwise the valve will be unable to
close.
When pressure testing
Always use counter force when fi nally
tightening the solenoid valve on pipes, i.e.
two spanners on the same side of the valve.
Af0_0006
Fitters notes Solenoid valves
The coil
When fitting the coil, it has merely to be pressed
down over the armature tube until a click is
heard. This means that the coil has been correctly
fitted.
Note: Remember to fit an O-ring between valve
body and coil.
Be sure that the O-ring is smooth, not damaged
and that the surface is free from paint or any
other material.
Note: The O-ring must be changed at service.
The coil can be removed by inserting a
screwdriver between valve body and coil. The
screwdriver can then be used as a lever to loosen
the coil.
Solenoid valves
Af0_0018
Af0_0019
Be careful with cable entries. It must not be
possible for water to enter the terminal box. The
cable must be led out via a drip loop.
The entire cable circumference must be retained by the cable entry.
Therefore, always use round cable (which is the
only type of cable that can be sealed effectively).
Be aware of the colour of leads in the cable.
Yellow/green is always earth.
Leads of one colour are either phase or neutral.
When removing a coil it might be necessary to
use hand tools, e.g. two screwdrivers.
Make sure that coil data (voltage and frequency)
and supply voltage correspond. If they do not,
the coil might burn out. Always ensure that valve
and coil match each other.
When replacing a coil in an EVR 20 NC
(NC = normally closed) note:
- A valve body using an a.c. coil has a square
armature.
- A valve body using a d.c. coil has a round
armature.
Fitting the wrong coil results in a lower MOPD.
See data on the top nut. As far as possible, always
choose single-frequency coils. These give off
less heat than double-frequency coils.
Use NC (normally closed) solenoid valves for
systems in which the valve must remain closed
(de-energised) for most of the operating time.
Use NO (normally open) solenoid valves for
systems in which the valve must remain open
(de-energised) for most of the operating time.
Never replace an NO (normally open) solenoid
valve with an NC (normally closed) valve - or vice
versa.
Af0_0012
Af0_0013
Af0_0014
(The new “clip-on” coil type)
Two labels are supplied with each clip-on coil
(see illustration).
The adhesive label is for attaching to the side of
the coil, while the other, perforated label should
be placed over the armature tube before the coil
is clicked into position.
Mount the KP pressure control on a bracket or on
a completely flat surface.
The pressure control can also be mounted on the
compressor itself.
In unfavourable conditions, an angle bracket
could amplify vibration in the mounting plane.
Therefore, always use a wall bracket where strong
vibration occurs.
If the risk of water droplets or water spray is
present, the accompanying top plate should be
used. The plate increases the grade of enclosure
to IP 44 and is suitable for all KP pressure controls.
To obtain IP 44, the holes in the backplate of the
control must be covered by mounting on either
an angle bracket (060-105666) or a wall plate
(060-105566).
The top plate is supplied with all units incorporating automatic reset. It can also be used on
units with manual reset, but in that case must
be purchased separately (code no.: for single unit,
060-109766; for dual unit, 060-109866).
If the unit is to be used in dirty conditions or
where it might be exposed to heavy spray -
from above or from the side - it should be fitted
with a protective cap. The cap can be used
together with either an angle bracket or a wall
bracket.
Al0_0001
Al0_0007
Pressure controls
Al0_0008
If the unit risk being exposed to heavy water
influence a better grade of enclosure can be
achieved when mounting the product in a special
IP 55 enclosure.
The IP 55 enclosure is available for both single
unit (060-033066) and dual unit (060-035066).
The pressure connection of the control must
always be fitted to the pipe in such a way that
liquid cannot collect in the bellows. This risk is
present especially when:
the unit is located in a low ambient condition,
e.g. in an air current,
the connection is made on the underside of
the pipe.
Such liquid could damage the high-pressure
control.
Consequently, compressor pulsation would
not be damped and might give rise to contact
chatter.
Surplus capillary tube can fracture if vibration
occurs and might lead to complete loss of system
charge. It is therefore very important that the
following rules are observed:
When mounting direct on compressor:
Secure the capillary tube so that the compressor/control installation vibrates as a
whole. Surplus capillary tube must be coiled
and bound.
Note:
According to EN rules it is not allowed to use
capillary tube for connecting safety pressure
controles. In such case a 1/4 inch tube is
prescribed.
Al0_0009
Al0_0010
Setting
Low-pressure control
High-pressure control
Other types of mounting:
Coil surplus capillary tube into a loose loop.
Secure the length of capillary tube between
compressor and loop to the compressor.
Secure the length of capillary tube between
loop and pressure control to the base on
which the pressure control is mounted.
In case of very strong vibrations, Danfoss
steel capillary tubes with flare connection are
recommended:
Code no. 0.5 m = 060-016666
Code no. 1.0 m = 060-016766
Code no. 1.5 m = 060-016866
KP pressure controls can be preset using a compressed air cylinder. Ensure that the change-over
contacts are correctly connected for the required
function.
Set the start pressure (CUT IN) on the range scale
(A). Then set the differential on the differential
scale (B).
Stop pressure = CUT IN minus DIFF.
Set the stop pressure (CUTOUT) on the range
scale (A). The set the differential on the
differential scale (B).
Start pressure = CUT OUT minus DIFF.
Indicative evaporating
pressures (pe) for different
types of systems
Medium: ice cream at –25°C,
t0 ≈ –37°C,
CompressorCUT OUTCUT IN
p0 ≈ –0.5 bar,
∆p suction line corresponding to 0.1 bar.
Each pressure control (e.g. KP 2) must be set
individually in accordance with the following
table.
The pressure control must be mounted in such
a way that liquid cannot collect in the bellows.
If the compressor, condenser and receiver are
situated outdoors, KP low pressure must be set to
a “CUT IN” setting lower than the lowest occurring
pressure (temperature around compressor)
during winter operation. In this case, after longer
standstill periods the pressure in the receiver
determines the suction pressure.
Example:
Lowest occurring temperature around the
compressor –20°C means, for R404A, a pressure
of 1 bar. CUT IN must be set at –24°C (corresponding to 1.6 bar).
Al0_0013
Room temp. (tr)System typeDifference
+0.5°/+2°CFan-cooled
meat cold room
+0.5°/+2°CMeat cold room with
natural air circulation
–1°/0°CRefrigeration meat
counter (open)
+2°/+6°CMilk cold room14K1.0 bar
0°/+2°CFruit cold room
Vegetable chiller
–24°CFreezer10K1.6 bar
–30°CVentilated deep
freeze room
–26°CIce cream freezer10K1.4 bar
between te
and t
media
10K1.0 - 1.1 bar
12K0.8 - 0.9 bar
14K0.6 bar
6K1.3 - 1.5 bar
10K1 bar
Evaporating
pressure (pe)
(air)
(R134a)
(R134a)
(R134a)
(R134a)
(R134a)
(R404A)
(R404A)
(R404A)
1–0.05 bar0.35 bar
20.1 bar0.5 bar
30.2 bar0.6 bar
40.35 bar0.75 bar
RH
Setting of KP2/KP1
[%]
(cut in - cut out)
D = Operating press. cont.
S = Safety press. cont.
When the electrical leads are connected and the
system is under normal operating pressure, the
contact function can be tested manually.
Depending on the bellows pressure and setting,
the test device must be pressed up or down.
Any reset mechanism becomes inoperative
during the test.
On single units:
Use the test device at top left.
On dual units:
Use the test device on the left for low-pressure
testing and the one at bottom right for highpressure testing.
Al0_0018
Warning!The contact function on a KP
Pressure Control must never be tested by activating the device at top
right. If this warning is ignored, the control may
go out of adjustment. In the worst case function
can be impaired.
Al0_0019
On the KP 15 dual pressure control with optional
automatic or manual reset on low-pressure
and high-pressure side, automatic reset must
be set when servicing is being carried out. The
pressure control can then automatically restart.
Remember, the original reset function must be
set after servicing.
The pressure control can be protected against
being set on automatic reset: Simply remove the
washer controlling the reset function!
If the unit is to be protected against tampering,
the washer can be sealed with red lacquer.
KP with solder connections can be used instead
of flare connections on hermetic systems.
In ammonia plant where KP pressure controls are
used, they must be type KP-A.
A connector with M10 × 0.75 – 1/
no. 060- 014166).
- 18 NPT (code
4
Al0_0006
Pressure controls
For refrigerating systems containing a large
quantity of charge medium and where extra
safety is desired/demanded (Fail-safe): Use KP
7/17 with double bellows. The system will stop
if one of the bellows ruptures - without loss of
charge.
For systems operating with low pressure on the
evaporator side, and where the pressure control
must regulate (not just monitor): Use KP 2 with a
small differential.
An example where pressure control and thermostat are in series:
KP 61 regulates the temperature via compressor
stop/start.
KP 2 stops the compressor when suction pressure
becomes too low.
KP 61:
CUT IN = 5°C (2.6 bar)
CUT OUT = 1°C (2.2 bar)
KP 2 low pressure:
CUT IN = 2.3 bar
CUT OUT = 1.8 bar
The correct pressure control
for your system (cont.)
For systems where KP is activated occasionally
(alarm) and for systems where KP is the signal
source for PLC, etc.: Use KP with gold contacts;
these give good contact at low voltages.