Danfoss Hints and tips for the installer Service guide

MAKING MODERN LIVING POSSIBLE
Fitters Notes
Hints and tips for the installer
REFRIGERATION & AIR CONDITIONING DIVISION
Manual
This Fitters Notes, gives practical hints about Danfoss commercial refrigeration controls (mechanical) and Danfoss compressors.
www.danfoss.com
We hope that this book will help you in your daily work.
Danfoss A/S
Fitters notes
Chapter 1 . . . . . . . . . . . . . . . . . . Thermostatic expansion valves . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3
Chapter 2 . . . . . . . . . . . . . . . . . . Solenoid valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 13
Chapter 3 . . . . . . . . . . . . . . . . . . Pressure controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 19
Chapter 4 . . . . . . . . . . . . . . . . . . Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 27
expansion valves Solenoid valves Pressure controls Thermostats
Thermostatic
Chapter 5 . . . . . . . . . . . . . . . . . . Pressure regulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 35
Chapter 6 . . . . . . . . . . . . . . . . . . Water valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 45
Chapter 7 . . . . . . . . . . . . . . . . . . Filter driers & sight glasses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 51
Chapter 8 . . . . . . . . . . . . . . . . . . Danfoss compressors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 61
regulators Water valves
Pressure
Filter driers &
sight glasses
compressors Practical tips Trouble shooting
Danfoss
Chapter 9 . . . . . . . . . . . . . . . . . . Practical tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 125
Chapter 10 . . . . . . . . . . . . . . . . . Trouble shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 145
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 1
Fitters notes Thermostatic expansion valves
Contents Page
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Superheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Subcooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
External pressure equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Charges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Universal charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
MOP charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
MOP ballast charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Thermostatic expansion valve selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Orifice assembly replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Danfoss product range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
expansion valves
Thermostatic
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 3
Notes
4 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Fitters notes Thermostatic expansion valves
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 5
Thermostatic
expansion valves
A thermostatic expansion valve is built up around a thermostatic element (1) separated from the valve body by a diaphragm.
A capillary tube connects the element to a bulb (2) and a valve body with valve seat (3) and a spring (4).
A thermostatic expansion valve works like this:
The function of a thermostatic expansion valve is determined by three fundamental pressures: P1: Bulb pressure which acts on the upper surface of the diaphragm, in the valve opening direction. P2: Evaporating pressure which acts on the underside of the diaphragm, in the valve closing direction. P3: Spring pressure which also acts on the underside of the diaphragm, in the valve closing direction.
When the expansion valve regulates, balance is created between bulb pressure on one side of the diaphragm and evaporating pressure plus spring force on the other side.
The spring is used to set superheat.
Ad0-0001

Introduction

Superheat is measured at the point where the bulb is located on the suction line and is the diff erence between the temperature at the bulb and the evaporating pressure/evaporating temperature at the same point.
Superheat is measured in Kelvin (K) and is used as a signal to regulate liquid injection through the expansion valve.
Ad0-0012
Ad0-0015

Superheat

Subcooling Subcooling is defi ned as the diff erence between

condensing pressure/temperature and liquid temperature at the expansion valve inlet.
Subcooling is measured in Kelvin (K). Subcooling of the refrigerant is necessary to avoid vapour bubbles in the refrigerant ahead of the expansion valve.
Vapour bubbles in the refrigerant reduce capacity in the expansion valve and thereby reduce liquid supply to the evaporator.
Subcooling of 4-5K is adequate in most cases.
Fitters notes Thermostatic expansion valves

External pressure equalization

Expansion valves with external pressure equali­zation must always be used if liquid distributors are installed.
Typically, the use of distributors gives a pressure drop of 1 bar across distributor and distribution tubes.
Expansion valves with external pressure equali­zation should always be used in refrigeration systems with heavy evaporators or plate exchangers, where normally the pressure drop will be greater than pressure corresponding to 2K.

Charges Thermostatic expansion valves can contain one

of three different types of charge:
1. Universal charge
2. MOP charge
3. MOP charge with ballast, standard for Danfoss expansion valves with MOP.

Universal charge

Expansion valves with Universal charge are used in most refrigeration systems where there is no pressure limitation requirement and where the bulb can be located warmer than the element or at high evaporating temperature/evaporating pressure.
Ad0-0016

MOP charge

Universal charge means that there is liquid charge in the bulb. The amount of charge is so large that charge remains in the bulb irrespective of whether the element is colder or warmer than the bulb.
Expansion valves with MOP charge are typically used on factory-made units where suction pressure limitation on starting is required, e.g. in the transport sector and in air conditioning systems.
All expansion valves with MOP have a very small charge in the bulb.
This means that the valve or the element must be located warmer than the bulb. If it is not, charge can migrate from the bulb to the element and prevent the expansion valve from functioning.
MOP charge means limited liquid charge in the bulb.
“MOP” stands for Maximum Operating Pressure and is the highest suction pressure/ evaporating pressure permissible in the evaporator/suction line.
The charge will have evaporated when the temperature reaches the MOP point. Gradually, as the suction pressure rises, the expansion valve begins to close at approx. 0.3/0.4 bar below the MOP point. It becomes completely closed when the suction pressure is the same as the MOP point.
Ad0-0017
Ad0-0018
MOP is often called “Motor Overload Protection”.
6 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Fitters notes Thermostatic expansion valves

MOP ballast charge

Thermostatic expansion valve selection

Expansion valves with MOP ballast charges are used mainly in refrigeration systems with “high­dynamic” evaporators, e.g. in air conditioning systems and plate heat exchangers with high heat transfer.
With MOP ballast charge, up to 2 - 4 K less superheat can be obtained than with other types of charge.
The bulb in a thermostatic expansion valve contains a material of high porosity and large surface area in relation to weight.
MOP charge with ballast has a damping effect on expansion valve regulation.
The valve opens slowly as bulb temperature rises and closes quickly as bulb temperature fails.
The thermostatic expansion valve can be selec­ted when the following are known:
Refrigerant Evaporator capacity Evaporating pressure Condensing pressure
Ad0-0021
Subcooling Pressure drop across valve Internal or external pressure equalization
expansion valves
Thermostatic
Identification The thermostatic element is fitted with a laser
engraving on top of the diaphragm. The code refers to the refrigerant for which the
valve is designed: L = R410A N = R134a S = R404A/ R507 X = R22 Z = R407C
This engraving gives valve type (with code number), evaporating temperature range, MOP point, refrigerant, and max. working pressure, PS/MWP.
With TE 20 and TE 55 the rated capacity is stamped on a band label fastened to the valve.
The orifice assembly for T2 and TE2 is marked with the orifice size (e.g. 06) and week stamp + last number in the year (e.g. 279). The orifice assembly number is also given on the lid of its plastic container.
On TE 5 and TE 12 the upper stamp (TE 12) indicates for which valve type the orifice can be used. The lower stamp (01) is the orifice size.
On TE 20 and TE 55 the lower stamp (50/35 TR N/B) indicates the rated capacity in the two evaporating temperature ranges N and B, and the refrigerant. (50/35 TR = 175 kW in range N and 123 kW in range B).
The upper stamp (TEX 55) refers to the valve type for which the assembly can be used.
Ad0-0019
Ad0-0023
Ad0-0020
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 7
Fitters notes Thermostatic expansion valves
8 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
The bulb is best mounted on a horizontal suction line tube and in a position corresponding to between 1 o’clock and 4 o’clock.
Location depends on the outside diameter of the tube.
Note: The bulb must never be located at the bottom of the suction line due to the possibility of oil laying in the bottom of the pipe causing false signals.
Ad0-0002
Ad0-0003

Installation The expansion valve must be installed in the

liquid line, ahead of the evaporator, with its bulb fastened to the suction line as close to the evaporator as possible.
If there is external pressure equalization, the equalizing line must be connected to the suction line immediately after the bulb.
The bulb must not be installed after a heat exchanger because in this position it will give false signals to the expansion valve.
The bulb must not be installed close to com­ponents of large mass as this also will give rise to false signals to the expansion valve
Ad0-0004
Ad0-0005
Ad0-0006
The bulb must be able to sense the tem pe ra tu re of the superheated suction vapour and must therefore not be located in a position that will expose it to extraneous heat/cold.
If the bulb is exposed to a warm air current, insulation of the bulb is recommended.
The Danfoss bulb strap allows a tight and secure fi tting of the bulb to the tube, thereby securing that the bulb has ultimate thermal contact to the suction tube. The TORX design of the screw makes it easy for the fi tter to transfer the torque from the tool to the screw without having to press the tool into the screw slot. Furthermore, with the TORX slot design, there is no risk of damaging the screw slot.
Fitters notes Thermostatic expansion valves
Installation (cont.)
As previously mentioned, the bulb must be installed to the horizontal part of the suction line immediately after the evaporator. It must not be installed to a collection tube or a riser after an oil pocket.
The expansion valve bulb must always be installed ahead of any liquid lock.
Ad0-0007
expansion valves
Thermostatic
Ad0-0008

Setting The expansion valve is supplied with a factory

setting suitable for most applications. If necessary, readjustment can be made using the
setting spindle on the valve. Turning the spindle clockwise increases the
expansion valve superheat and turning it counterclock-wise reduces it.
For T /TE 2, one turn of the spindle produces a change of approx. 4K in the superheat at 0°C evaporating temperature.
Ad0-0009
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 9
Fitters notes Thermostatic expansion valves
Setting (cont.)
For TE 5 and following sizes, one turn of the spindle produces a change of approx. 0.5K in the superheat at 0°C evaporating temperature.
For TUA and TUB, one turn of the spindle produces a change of approx. 3K in the super­heat at 0°C evaporating temperature.
Hunting in the evaporator can be eliminated by the following procedure: Increase the superheat by turning the expansion valve setting spindle well to the right (clockwise) so that hunting stops. Then turn the setting spindle in counter-clockwise steps so that hunting again occurs.
From this position, turn the spindle about once clockwise (but only 1/4 turn for T /TE 2 valves).
On this setting the refrigeration system will not hunt and the evaporator is fully utilized. A variation of 1 K in superheat is not regarded as hunting.
Ad0-0010
Ad0-0011
Orifice assembly replacement
If the superheat in the evaporator is too high, the reason might be an inadequate supply of liquid refrigerant.
The superheat can be reduced by turning the expansion valve setting spindle counterclockwise in steps until hunting is observed.
From this setting, the spindle must be turned about once clockwise (but only 1/4 turn for T/TE
2). This setting fully utilizes the evaporator. A variation of 1 K in superheat is not regarded as hunting.
Ad0-0013
If the evaporator continues to hunt, regardless of the superheat setting, the valve capacity might be too high and the orifice assembly, or the valve, needs replacing with a smaller one.
If the evaporator superheat is too high the valve capacity is too low and the orifice assembly must be replaced with a larger one.
TE, T2, TUA, TCAE valves are supplied with an interchangeable orifice.
Ad0-0014
10 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Fitters notes Thermostatic expansion valves
Danfoss product range Thermostatic expansion valves
Danfoss offers a comprehensive range of thermostatic expansion valves with capacities from 0.4 to 1083 kW (R134a).
T/TE 2 valves have a brass housing and flare/ flare or solder/flare connections.
Rated capacity: 0.4 - 10.5 kW (R134a).
TUA, TUB, TUC valves have a stainless steel housing and stainless steel/copper bimetal solder connections.
Rated capacity: 0.5 - 12 kW (R134a).
The valves can be supplied with or without external pressure equalization.
TUA has an interchangeable orifice assembly and adjustable superheat.
TUB has a fixed orifice and adjustable superheat.
TUC has a fixed orifice and factory set superheat.
TUB and TUC are primarily for OEM customers. All TUB and TUC valves can be replaced by TUA valves.
TCAE, TCBE, TCCE valves have a stainless steel housing and stainless steel/copper bimetal solder connections.
Rated capacity: 12 - 18 kW (R134a).
The valves are designed as the TU valves but with a higher capacity.
TDE valves have a brass housing and copper solder connections.
Rated capacity: 10.5 - 140 kW (R407C)
The valves are supplied with a fixed orifice and adjustable superheat.
TE 5 - TE 55 valves have a brass housing. The valves are supplied as a part programme consisting of valve housing, orifice and thermo­static element.
The valve housing is available in a straightway or angleway version with solder, flare and flange connections.
Rated capacity: 12.9 - 220 kW (R134a).
The valves are supplied with external pressure equalization.
PHT 85 - 300 valves are supplied as a part programme consisting of valve housing, flanges, orifice and thermostatic element.
Rated capacity: 55 - 1083 kW (R134a).
For further information consult the internet or the catalogue material.
expansion valves
Thermostatic
The valves are supplied with external pressure equalization.
TRE valves have a brass housing and stainless steel/copper bimetal connections.
Rated capacity: 18 - 196 kW (R134a).
The valves are supplied with a fixed orifice and adjustable superheat.
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 11
Fitters notes Solenoid valves
Contents Page
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
EVRA 32 & 40 precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
When pressure testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
The coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
The correct product. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Solenoid valves
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 13
Notes
14 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Fitters notes Solenoid valves
Installation
All EVR/EVRA, and EVH types solenoid valves operate only when installed correctly in the direction of flow, i.e. in the direction indicated by the arrow.
Normally, solenoid valves installed ahead of a thermostatic expansion valve must be close to that valve.
This avoids liquid hammer when the solenoid valve opens.
Ensure that pipes around the valve are properly installed so that no fracture can occur.
Solenoid valves
Af0_0001
Af0_0003
EVRA 32 & 40 precautions
Brazing/welding EVR/EVRA and EVH solenoid valves does not normally necessitate dismantling, provided steps are taken to avoid heating the valve.
Note! Always protect the armature tube against weld spatter.
After tacking the valve to the pipe, remove the valve body to protect O-rings and gaskets against heat. In installations with welded steel pipe, a FA type strainer or similar mounted ahead of the solenoid valve is recommended. (On new plant, flushing out before starting up is recommended).
Af0_0004
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 15
Fitters notes Solenoid valves
16 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Af0_0005
All solenoid valves in the system must be open, either by applying voltage to the coils or by opening the valves manually (provided a manual operation spindle is fi tted).
Remember to screw the spindle back before starting up, otherwise the valve will be unable to close.
When pressure testing
Always use counter force when fi nally tightening the solenoid valve on pipes, i.e. two spanners on the same side of the valve.
Af0_0006
Fitters notes Solenoid valves
The coil
When fitting the coil, it has merely to be pressed down over the armature tube until a click is heard. This means that the coil has been correctly fitted.
Note: Remember to fit an O-ring between valve body and coil.
Be sure that the O-ring is smooth, not damaged and that the surface is free from paint or any other material.
Note: The O-ring must be changed at service.
The coil can be removed by inserting a screwdriver between valve body and coil. The screwdriver can then be used as a lever to loosen the coil.
Solenoid valves
Af0_0018
Af0_0019
Be careful with cable entries. It must not be possible for water to enter the terminal box. The cable must be led out via a drip loop.
The entire cable circumference must be retai­ned by the cable entry.
Therefore, always use round cable (which is the only type of cable that can be sealed effectively).
Be aware of the colour of leads in the cable. Yellow/green is always earth. Leads of one colour are either phase or neutral.
Af0_0009
Af0_0010
Af0_0011
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 17
Fitters notes Solenoid valves
The coil (cont.)
The correct product
(The “old” coil type)
When removing a coil it might be necessary to use hand tools, e.g. two screwdrivers.
Make sure that coil data (voltage and frequency) and supply voltage correspond. If they do not, the coil might burn out. Always ensure that valve and coil match each other.
When replacing a coil in an EVR 20 NC (NC = normally closed) note:
- A valve body using an a.c. coil has a square armature.
- A valve body using a d.c. coil has a round armature.
Fitting the wrong coil results in a lower MOPD. See data on the top nut. As far as possible, always choose single-frequency coils. These give off less heat than double-frequency coils. Use NC (normally closed) solenoid valves for systems in which the valve must remain closed (de-energised) for most of the operating time. Use NO (normally open) solenoid valves for systems in which the valve must remain open (de-energised) for most of the operating time. Never replace an NO (normally open) solenoid valve with an NC (normally closed) valve - or vice versa.
Af0_0012
Af0_0013
Af0_0014
(The new “clip-on” coil type)
Two labels are supplied with each clip-on coil (see illustration).
The adhesive label is for attaching to the side of the coil, while the other, perforated label should be placed over the armature tube before the coil is clicked into position.
Af0_0015
Af0_0020
18 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Fitter notes Pressure controls
Contents Page
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Placing of surplus capillary tube. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Low-pressure control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
High-pressure control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Example with four compressors in parallel (R404A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Setting LP for outdoor location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Indicative evaporating pressures (pe) for different types of systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Test of contact function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
The correct pressure control for your system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Pressure controls
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 19
Notes
20 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Fitter notes Pressure controls

Installation

Mount the KP pressure control on a bracket or on a completely flat surface.
The pressure control can also be mounted on the compressor itself.
In unfavourable conditions, an angle bracket could amplify vibration in the mounting plane. Therefore, always use a wall bracket where strong vibration occurs.
If the risk of water droplets or water spray is present, the accompanying top plate should be used. The plate increases the grade of enclosure to IP 44 and is suitable for all KP pressure controls. To obtain IP 44, the holes in the backplate of the control must be covered by mounting on either an angle bracket (060-105666) or a wall plate (060-105566).
The top plate is supplied with all units incor­porating automatic reset. It can also be used on units with manual reset, but in that case must be purchased separately (code no.: for single unit, 060-109766; for dual unit, 060-109866).
If the unit is to be used in dirty conditions or where it might be exposed to heavy spray - from above or from the side - it should be fitted with a protective cap. The cap can be used together with either an angle bracket or a wall bracket.
Al0_0001
Al0_0007
Pressure controls
Al0_0008
If the unit risk being exposed to heavy water influence a better grade of enclosure can be achieved when mounting the product in a special IP 55 enclosure.
The IP 55 enclosure is available for both single unit (060-033066) and dual unit (060-035066).
Ak0_0020
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 21
Fitter notes Pressure controls
Installation (cont.)
Placing of surplus capillary tube
The pressure connection of the control must always be fitted to the pipe in such a way that liquid cannot collect in the bellows. This risk is present especially when:
the unit is located in a low ambient condition, e.g. in an air current,
the connection is made on the underside of the pipe.
Such liquid could damage the high-pressure control.
Consequently, compressor pulsation would not be damped and might give rise to contact chatter.
Surplus capillary tube can fracture if vibration occurs and might lead to complete loss of system charge. It is therefore very important that the following rules are observed:
When mounting direct on compressor: Secure the capillary tube so that the com­pressor/control installation vibrates as a whole. Surplus capillary tube must be coiled and bound.
Note:
According to EN rules it is not allowed to use capillary tube for connecting safety pressure controles. In such case a 1/4 inch tube is prescribed.
Al0_0009
Al0_0010

Setting

Low-pressure control

High-pressure control

Other types of mounting: Coil surplus capillary tube into a loose loop. Secure the length of capillary tube between compressor and loop to the compressor.
Secure the length of capillary tube between loop and pressure control to the base on which the pressure control is mounted.
In case of very strong vibrations, Danfoss steel capillary tubes with flare connection are recommended: Code no. 0.5 m = 060-016666 Code no. 1.0 m = 060-016766 Code no. 1.5 m = 060-016866
KP pressure controls can be preset using a com­pressed air cylinder. Ensure that the change-over contacts are correctly connected for the required function.
Set the start pressure (CUT IN) on the range scale (A). Then set the differential on the differential scale (B). Stop pressure = CUT IN minus DIFF.
Set the stop pressure (CUTOUT) on the range scale (A). The set the differential on the differential scale (B). Start pressure = CUT OUT minus DIFF.
Remember: The scales are indicative only.
Al0_0011
Al0_0012
22 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Fitter notes Pressure controls
Example with four compressors in parallel (R404A)

Setting LP for outdoor location

Indicative evaporating pressures (pe) for different types of systems
Medium: ice cream at –25°C, t0 –37°C,
Compressor CUT OUT CUT IN
p0 –0.5 bar, p suction line corresponding to 0.1 bar.
Each pressure control (e.g. KP 2) must be set individually in accordance with the following table.
The pressure control must be mounted in such a way that liquid cannot collect in the bellows.
If the compressor, condenser and receiver are situated outdoors, KP low pressure must be set to a “CUT IN” setting lower than the lowest occurring pressure (temperature around compressor) during winter operation. In this case, after longer standstill periods the pressure in the receiver determines the suction pressure.
Example:
Lowest occurring temperature around the compressor –20°C means, for R404A, a pressure of 1 bar. CUT IN must be set at –24°C (corre­sponding to 1.6 bar).
Al0_0013
Room temp. (tr) System type Difference
+0.5°/+2°C Fan-cooled
meat cold room
+0.5°/+2°C Meat cold room with
natural air circulation
–1°/0°C Refrigeration meat
counter (open)
+2°/+6°C Milk cold room 14K 1.0 bar
0°/+2°C Fruit cold room
Vegetable chiller
–24°C Freezer 10K 1.6 bar
–30°C Ventilated deep
freeze room
–26°C Ice cream freezer 10K 1.4 bar
between te and t
media
10K 1.0 - 1.1 bar
12K 0.8 - 0.9 bar
14K 0.6 bar
6K 1.3 - 1.5 bar
10K 1 bar
Evaporating pressure (pe)
(air)
(R134a)
(R134a)
(R134a)
(R134a)
(R134a)
(R404A)
(R404A)
(R404A)
1 –0.05 bar 0.35 bar 2 0.1 bar 0.5 bar 3 0.2 bar 0.6 bar 4 0.35 bar 0.75 bar
RH
Setting of KP2/KP1
[%]
(cut in - cut out) D = Operating press. cont. S = Safety press. cont.
85 0.9 - 2.1 bar (D)
85 0.7 - 2.1 bar (D)
85 0.5 - 1.8 bar (D)
85 0.7 - 2.1 bar (D)
90 1.2 - 2.1 bar (D)
90 0.7 - 2.2 bar (S)
90 0.3 - 2.7 bar (S)
90 0.5 - 2.0 bar (S)
Pressure controls
Al0_0015
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 23
Fitter notes Pressure controls

Test of contact function

When the electrical leads are connected and the system is under normal operating pressure, the contact function can be tested manually.
Depending on the bellows pressure and setting, the test device must be pressed up or down.
Any reset mechanism becomes inoperative during the test.
On single units:
Use the test device at top left.
On dual units:
Use the test device on the left for low-pressure testing and the one at bottom right for high­pressure testing.
Al0_0018
Warning! The contact function on a KP Pressure Control must never be tested by activating the device at top right. If this warning is ignored, the control may go out of adjustment. In the worst case function can be impaired.
Al0_0019
On the KP 15 dual pressure control with optional automatic or manual reset on low-pressure and high-pressure side, automatic reset must be set when servicing is being carried out. The pressure control can then automatically restart. Remember, the original reset function must be set after servicing.
The pressure control can be protected against being set on automatic reset: Simply remove the washer controlling the reset function! If the unit is to be protected against tampering, the washer can be sealed with red lacquer.
Al0_0020
Low pressure Manual reset *) Automatic reset Automatic reset Manual reset
High pressure Manual reset *) Manual reset Automatic reset Automatic reset
*) Factory setting
Al0_0021
24 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Fitter notes Pressure controls

The correct pressure control for your system

KP with solder connections can be used instead of flare connections on hermetic systems.
In ammonia plant where KP pressure controls are used, they must be type KP-A. A connector with M10 × 0.75 – 1/ no. 060- 014166).
- 18 NPT (code
4
Al0_0006
Pressure controls
For refrigerating systems containing a large quantity of charge medium and where extra safety is desired/demanded (Fail-safe): Use KP 7/17 with double bellows. The system will stop if one of the bellows ruptures - without loss of charge.
For systems operating with low pressure on the evaporator side, and where the pressure control must regulate (not just monitor): Use KP 2 with a small differential. An example where pressure control and thermo­stat are in series:
KP 61 regulates the temperature via compressor stop/start. KP 2 stops the compressor when suction pressure becomes too low.
KP 61: CUT IN = 5°C (2.6 bar) CUT OUT = 1°C (2.2 bar)
KP 2 low pressure: CUT IN = 2.3 bar CUT OUT = 1.8 bar
Al0_0002
Al0_0003
Al0_0004
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 25
Fitter notes Pressure controls
The correct pressure control for your system (cont.)
For systems where KP is activated occasionally (alarm) and for systems where KP is the signal source for PLC, etc.: Use KP with gold contacts; these give good contact at low voltages.
Al0_0005
26 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Fitters notes Thermostats
Contents Page
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
KP thermostat with air sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Thermostats with automatic reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Thermostats with maximum reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Thermostats with minimum reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Setting example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Test of contact function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
KP 98 dual thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
The correct thermostat for your refrigeration system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Vapour charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Absorption charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Low voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Placing of surplus capillary tube. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Thermostats with vapour charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Thermostats
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 27
Notes
28 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Loading...
+ 182 hidden pages