Danfoss Heating mats Operating guide

Installation Guide
Heating mats
Thin concrete < 3 cm
electricheating.danfoss.com
Table of Contents
1.1 Sikkerhedsinstruktioner . . . . . . . . . . . .2
1.2 Installationsvejledning . . . . . . . . . . . .4
2 Installation, trin for trin . . . . . . . . . . . . .5
2.1 Beregning af indbyrdes kabelafstand . . .5
2.2 Planlægning af installationen . . . . . . . .5
2.3 Klargøring af installationsstedet. . . . . . .6
3 Installation af elementer . . . . . . . . . . . . 6
3.1 Installation af varmeelementer . . . . . . .7
3.2 Følerinstallation . . . . . . . . . . . . . . . . .7
4 Indendørs anvendelser. . . . . . . . . . . . . . 8
4.1 Gulvvarme i tynde gulve (< 3 cm . . . . . .8
5 Valgfrie indstillinger . . . . . . . . . . . . . . . 9
1 Introduction
In this installation manual, the word “element” refers to both heating cables and heating mats.
If the words “heating cable” or “heating mat” are used, the instruction in question applies only to this type of element.
All dimensioning, product selection, installation and commissioning of any given application are the responsibility of an authorized installer.
Any application using heating elements or thermo­stats purchased by end user must be approved by an authorized electrician prior to commissioning.
• Including type, size, installation and connection of the heating element.
• Including type, size, connection and settings of the thermostat controlling the heating element.
• Children shall not play with the heating element.
• This heating element can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
• Cleaning and user maintenance shall not be made by children without supervision.
The intended use of the heating elements covered by this installation manual is oor heating, only.
• According to IEC 60335 the mats may not be installed in a metallic oor or storage heating application.
• Mats shall be fully embedded in at least 5 mm concrete, screed, tile adhesive or similar. incl. tiles.
1.1 Safety Instructions
Never cut or shorten the heating element
!
1
2
3
4
5
6
7
• Cutting the heating element will void the warranty.
• Cold leads can be shortened to suit require­ments.
Elements must always be installed according to local building regulations and wiring rules as well as the guidelines in this installation manual.
• Any other installation may hamper element functionality or constitute a safety risk, and will void the warranty.
Elements must always be connected by an au­thorised electrician using a xed connection.
• De-energize all power circuits before installa­tion and service.
• Each heating element screen must be earthed in accordance with local electricity regulations and connected to a residual current device (RCD).
• RCD trip rating is max. 30 mA.
• Heating elements must be connected via a switch providing all pole disconnection.
• The element must be equipped with a correctly sized fuse or circuit breaker according to local regulations.
1. Heating cable
2. Thermostat
3. Sensor
4. Screen
5. RCD
6. All-pole switch
7. Fuse
The presence of a heating mat must
• be made evident by axing caution signs or markings at the power connection ttings and/ or frequently along the circuit line where clearly visible
• be stated in any electrical documentation following the installation.
Connections
• Phase - Brown
• Neutral - Blue
• Earth - Screen
Never exceed the maximum heat density (W/m) for the actual application.
1.2 Installation guidelines
Prepare the installation site properly by removing
Regularly measure ohmic resistance and insula-
tion resistance before and during installation.
Do not lay heating elements under walls and xed
sharp objects, dirt, etc.
obstacles. Min. 6 cm air is required.
Keep elements clear of insulation material, other
heating sources and expansion joints
Elements may not touch or cross themselves or
other elements and must be evenly distributed
The elements and especially the connection must
be protected from stress and strain.
on areas.
The elements and sensors shall be installed min­imum 30 mm away from conductive parts of the
building, e.g. water pipes.
A oor sensor is mandatory and must be connect-
ed to a thermostat limiting the oor temperature
The element should be temperature controlled
and not operate at ambient temperature higher
to maximum 35°C.
than 10°C in outdoor applications.
2 Installation step by step
2.1 C-C distance for heating cables
The C-C distance is the distance in centimetres from the centre of one cable to the centre of the next.
C - C [cm] =
or
C - C[cm] =
• Max. C-C distance for thin beddings (<3 cm) is10 cm.
• Heating cable bending diameter must be at least 6 times cable diameter.
• The actual cable length may vary +/- 2 %.
C-C [cm] 5 7.5 10 12.5 15
W/m2 @ 6 W/m 120 80 60 48 40
W/m2 @ 10 W/m 200 130 100 80 67
W/m2 @ 18 W/m - - 180 144 120
W/m2 @ 20 W/m - - 200 160 133
2.2 Planning the installation
Draw a sketch of the installation showing
• element layout
• cold leads and connections
• junction box/cable well (if applicable)
• sensor
• connection box
• thermostat
Area [m]
Cable length [m]
Cable output [W/m] Heat density [W/m]
230V/400V
x 100 cm
x 100 cm
Save the sketch
• Knowing the exact location of these compo­nents makes subsequent troubleshooting and repair of faulty elements easier.
Please the following:
• Observe all guidelines - see section 1.2 .
• Observe correct C-C distance (heating cables only) - see section 2.1.
• Observe required installation depth and possible mechanical protection of cold leads according to local regulations.
• When installing more than one element, never wire elements in series but route all cold leads in parallel to the connection box.
• Two or more elements may be installed in the same room but a single element is not to be installed across two or more rooms.
• All heating elements in the same room must have the same heat density (W/m) unless they are connected to separate oor sensors and thermostats.
• For single conductor cables, both cold leads must be connected to the connection box.
2.3 Preparing the installation area
• Remove all traces of old installations, if appli­cable.
• Ensure that the installation surface is even, stable, smooth, dry and clean.
• If necessary, ll out gaps around pipes, drains and walls.
• There must be no sharp edges, dirt or foreign objects.
3 Installing elements
It is not recommended to install elements at temper­atures below -5 °C.
At low temperatures, heating cables can become rigid. After rolling out the element, briey connect it to the mains supply to soften the cable before fastening.
Measuring Resistance
Measure, verify and record element resistance dur­ing installation.
• After unpacking
• After fastening the elements
• After the installation in nalized
If ohmic resistance and insulation resistance are not as labelled, the element must be replaced.
• The ohmic resistance must be within -5 to +10 % of the value labelled.
• The insulation resistance should read >20 M after one minute at min. 500V DC..
3.1 Installing heating elements
Observe all instructions and guidelines in section 1.1 and 1.2.
Heating elements
• Position the heating element so that it is at least half the C-C distance from obstacles.
• Elements must always be in good contact with the heat distributor (e.g. concrete), see section 4 for details.
Heating mats
• Always roll out heating mats with the heating cables facing up.
• When the heating mat reaches the area bound­ary, cut the liner/net and turn the mat before rolling it back.
Extending cold leads
• Avoid extending cold leads if possible. Wire cold leads to e.g. junction boxes or cable wells.
• Be aware of power loss in the cable according to local regulations.
3.2 Sensor Installation
• Mandatory under wooden oors and on wood­en sub oors.
• The oor sensor should be mounted in an insu­lating conduit, sealed at the oor end, for easy replacement of the sensor if required.
• The oor sensor must be considered a LIVE ca­ble; therefore any extension made to the sensor wiring should be treated in the same way as normal mains voltage cabling.
• The sensor can be extended up to a total of 50 m using 1.5 mm installation cable.
• The minimum bending radius for the pipe is 50 mm (1).
• The sensor cable must be placed between two loops of the heating cable (2).
• To avoid cracks in the concrete oor do not switch on the heat until the oor has complete­ly hardened.
12
• The conduit should be ush with the sub oor.
1
2
1
234
567
• Route the conduit to the connection box.
4 Indoor applications
Suboor
Wood -
Concrete Max. 200 W/m
Floor types
Wood, parquet, laminate Maks. 150 W/m
Carpet, vinyl, linoleum, etc. Maks. 150 W/m
Tiled oors in bathrooms
conservatories cellars, etc.
Tiled oors in kitchens
living rooms halls, etc.
May be up to 225 W/m in rim zones e.g. under large windows.
• On concrete sub oors and under tiles, only.
• If connected to a separate oor sensor and thermostat.
Wooden oor coverings
Wood shrinks and swells naturally depending on the relative humidity (RH) in the room.
100 - 200 W/m
100 - 150 W/m
• Avoid beech and maple in multilayered oor coverings unless press dried.
• Install a vapour barrier for sub oors <95% RH and a damp proof membrane >95%.
• Ensure 100% contact between the element and the embedding material above (no air pockets).
• Install the heating system in the whole oor area at 15°C surface temperature.
• Always install a oor sensor to limit the max. oor temperature.
4.1 Floor heating in thin beddings
New tiles on existing tiles, concrete oors or wooden oors
1. New tiles.
2. Tile adhesive.
3. Vapour barrier.
4. Self-levelling compound.
5. Heating element.
6. Primer (on concrete) or screed (on wood).
7. Existing tiles, concrete or wooden oor.
New oor covering on existing tiles, concrete
5
4
1
2
3
6
7
oors or wooden oors
1. Wooden oor, laminate or carpet.
2. Noise absorption mat.
3. Vapour barrier.
4. Self-levelling compound.
5. Heating mat or heating cable.
6. Primer (on concrete) or screed (on wood).
7. Existing tiles, concrete or wooden oor.
Wooden sub oors must be properly anchored
• Apply screed before laying the heating ele­ment.
Vapour barrier
• Apply only if not already installed in existing oor.
• In wet rooms apply only above the heating elements.
Tile adhesive or self-levelling compound
• Prime the sub oor as specied by the supplier.
• The heating element should be securely fas­tened before applying.
• The heating element must be fully embedded and at least 5 mm.
Installation summary
Cut out a wall groove and x cable ducts and connection box. Chisel o a groove for the sensor conduit and cold cable. Fix the sensor conduit e.g. with a glue gun.
Roll out the element. Attach it to the sub oor. Cut and turn the mat mesh when meeting walls or obstacles. Do NOT cut the heating elements.
Apply exible self-levelling compound, vapour barrier, and tile adhesive, depending on the oor nish.
5 Optional settings
If the element is connected to a thermostat such as a ECtemp, congure basic settings according to the table below and as described in the thermostat installation manual.
If applicable, adjust the temperature limit in accord­ance with the manufacturer’s recommendations in order to prevent damage to e.g. the oor or the pipe.
Thermostat Max. load
ECtemp 13x 16A
ECtemp 330 16A
ECtemp 53x 15A
ECtemp 610 10A
ECtemp Touch 16A
Danfoss link CC 15A (FT)
Floor heating
in general
Room temp.
20-22° C.
VIKZB102
Loading...