Danfoss HDU-SF Installation guide

Installation Guide
HDU-SF (Horizontal Distribution Units - Single Flat)
1 Introduction
HDU-SF single-port HDU-SF multi-port
1. Ball valve for in- and outlet connection to the riser.
2. Strainer to trap dirt, sand etc. from pipe water (replacement filter available as accessory).
flow limiter.
4. Manifold for radiator connection, flow.
5. Manifold for radiator connection, return.
6. Automatic air vent and drainage (both inlet and outlet has drainage and air vent possibilities).
7. Heat Meter for energy measuring, with 8-digit LCD.
8. Cabinet.
Note!
The HDU-SF must only be installed in a dry and frost-free environment.
Operation of the HDU-SF outside the specified operating and environmental conditions is not permitted.
Joints may be loose after transportation. Please check and re-tighten, if necessary.
HDU-SF are available with left or right side connections to riser. All illustrations are shown for the left side version.
Service guide is placed on the inside of the cabinet door.
2 Technical Data
Max. temperature 90 °C Max. working pressure in heating system piping before the unit 2 bar Nominal required differential pressure over unit (HDU-SF) 0.26 bar* Max. differential pressure in a control loop 0.22 bar Max. static pressure 10 bar (PN 10) Connection to riser (in and out) R 3/4" Connection to manifold (out) 3/4" Power supply (Heat Meter) A-cell battery, 3.6 VDC
* At differential pressure in control loop 10kPa at 100% AB-PM set­ting.
Danfoss Heating Solutions VIIGA102
1
260
380
51
49
2389
72
25
95
125
480
380
62
95
51
49
23
213
113 ­200
266
50
25
125
B
A
Installation Guide HDU-SF (Horizontal Distribution Units - Single Flat)
3 Mounting on Wall
HDU-SF single-port HDU-SF multi-port
HDU-SF 4-port
A = 480 mm
HDU-SF 7-port
A = 630 mm
The HDU-SF is mounted vertically, tilted angle is to be checked with a spirit level. Available for wall or recess mounting, depth can be regulated by moving the face frame. The cabinet has four holes in the back plate, intended for mounting with the supplied screws and rawlplugs.
4 Connections
4.1 Connection to riser
Connect the HDU-SF to the riser according to flow direction:
1. Riser inlet
2. Riser outlet
3. The connections are size DN20 with internal thread. Remember backstop to prevent the ball valves from loosening.
HDU-SF single-port
HDU-SF multi-port
2
VIIGA102 Danfoss Heating Solutions
Installation Guide HDU-SF (Horizontal Distribution Units - Single Flat)
4.2 Connection to radiator
Connection of system pipes to the HDU-SF manifold should be made with compression fittings, DN should be chosen according to the piping type and diameter.
1. Mount fittings by hand. 2. Tighten with spanner, max. ½ to 1 turns.
Danfoss recommends using the following compression fittings:
Compression fittings Size Code no. for PEX tubing
(in accordance with ISO 15875)
for AluPEX tubing
for steel and copper tubing
- PN6
- G ¾” internal thread
- PN10
- G ¾” internal thread
- PN10
- G ¾” internal thread
16 x 2 mm 013G4156 20 x 2 mm 013G4160
20 x 2.25 mm 013G4093
20 x 2.5 mm 013G4161
16 x 2 mm 013G4186 20 x 2 mm 013G4190
20 x 2.25 mm 013G4093
20 x 2.5 mm 013G4191
16 mm 013G4126 18 mm 013G4128
5 Check and Test
1. Ensure that the capillary tube in AB-PM valve is mounted cor­rectly.
2. Fill the system with water and make sure that all connections are tight and without leaks.
3. Check function of the Heat Meter. The meter will only meas­ure energy if the pipes are completely filled with water, other­wise a corresponding error message (E - 7) is shown in the display.
4. Check the flow rate display for plausibility. If the flow rate dis­play is not steady, bleed the system. Regulate the system us­ing the flow rate display.
5. Read the meter counts for energy, volume and operating hours.
Error messages for wrong installation
E - 3: Temperature sensors reversed during installation or connec­tion. E - 6: Heat meter has not been installed in the intended flow direc­tion.
Note! Please refer to the Service Guide (placed on the inside of the cabinet door) for other error codes.
HDU-SF single-port
Danfoss Heating Solutions VIIGA102
HDU-SF multi-port
3
10%
100%
h
h+ 2 mm, DN 15-20 h+ 4 mm, DN 25
1.5 mm
Installation Guide HDU-SF (Horizontal Distribution Units - Single Flat)
6 Settings
Setting of the AB-PM is done during the commissioning. The AB­PM automatic balancing valve is set to the wanted flow by
turning the top of the valve (or more information, please refer to
separate data sheet for AB-PM).
Push down on the top to lock the AB-PM settings. To unlock, simply lift up the top.
Danfoss A/S Heating Solutions Haarupvaenget 11 8600 Silkeborg Denmark Phone:+45 7488 8000 Fax: +45 7488 8100 Email: heating.solutions@danfoss.com www.heating.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss Heating Solutions and the Danfoss Heating Solutions logotype are trademarks of Danfoss A/S. All rights reserved.
013R2142 & VIIGA102 Produced by Danfoss Heating Solutions © 08/2012
Loading...