This manual is regularly reviewed and updated. All
suggestions for improvement are welcome. Table 1.1 shows
the manual version and the corresponding software
version.
EditionRemarksSoftware version
MG02K4XXMiscellaneous minor
Table 1.1 Manual and Software Version
Oces or online at: www.vlt-
VLT® Micro Drive FC 51 Quick Guide
VLT® Micro Drive FC 51 Programming Guide
VLT® Micro Drive FC 51 LCP Mounting Instruction
®
Micro Drive FC 51 De-coupling Plate Mounting
VLT
Instruction
VLT® Micro Drive FC 51 Remote Mounting Kit
Mounting Instruction
®
Micro Drive FC 51 DIN Rail Kit Mounting
VLT
Instruction
VLT® Micro Drive FC 51 IP21 Kit Mounting
Instruction
®
VLT
Micro Drive FC 51 Nema1 Kit Mounting
Instruction
VLT® Micro Drive FC 51 Line Filter MCC 107 Installation Instruction
The rated output current supplied by the frequency
converter.
U
VLT,MAX
The maximum output voltage.
1.4.2 Input
Control command
The connected motor can be started and stopped with LCP
and the digital inputs.
Functions are divided into 2 groups.
Functions in group 1 have higher priority than functions in
group 2.
Group 1Reset, coast stop, reset and coast stop, quick
stop, DC brake, stop, and the [O] key.
Group 2Start, pulse start, reversing, start reversing, jog,
and freeze output.
Table 1.3 Function Groups
Illustration 1.1 Break-away Torque
η
VLT
The eciency of the frequency converter is dened as the
ratio between the power output and the power input.
Start-disable command
A stop command belonging to the group 1 control
commands, see Table 1.3.
Stop command
See Table 1.3.
1.4.3 Motor
f
JOG
The motor frequency when the jog function is activated
(via digital terminals).
f
M
The motor frequency.
f
MAX
The maximum motor frequency.
f
MIN
The minimum motor frequency.
f
M,N
The rated motor frequency (nameplate data).
I
M
The motor current.
I
M,N
The rated motor current (nameplate data).
n
M,N
The nominal motor speed (nameplate data).
P
M,N
The rated motor power (nameplate data).
U
M
The instant motor voltage.
U
M,N
The rated motor voltage (nameplate data).
1.4.4 References
Analog reference
A signal transmitted to the analog inputs 53 or 54, can be
voltage or current.
Bus reference
A signal transmitted to the serial communication port (FC
port).
Preset reference
A dened preset reference to be set from -100% to +100%
of the reference range. Selection of 8 preset references via
the digital terminals.
Ref
MAX
Determines the relationship between the reference input at
100% full scale value (typically 10 V, 20 mA) and the
resulting reference. The maximum reference value set in
parameter 3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input at
0% value (typically 0 V, 0 mA, 4 mA) and the resulting
reference. The minimum reference value set in
parameter 3-02 Minimum Reference.
The analog inputs are used for controlling various
functions of the frequency converter.
There are 2 types of analog inputs:
Current input, 0–20 mA and 4–20 mA
•
Voltage input, 0–10 V DC.
•
Analog outputs
The analog outputs can supply a signal of 0–20 mA, 4–20
mA, or a digital signal.
Automatic Motor Tuning, AMT
AMT algorithm determines the electrical parameters for the
connected motor at standstill.
Brake resistor
The brake resistor is a module capable of absorbing the
brake power generated in regenerative braking. This
regenerative brake power increases the DC-link voltage,
and a brake chopper ensures that the power is transmitted
to the brake resistor.
CT characteristics
Constant torque characteristics used for all applications
such as conveyor belts, displacement pumps, and cranes.
Digital inputs
The digital inputs can be used for controlling various
functions of the frequency converter.
Relay outputs
The frequency converter features 2 programmable relay
outputs.
ETR
Electronic thermal relay is a thermal load calculation based
on present load and time. Its purpose is to estimate the
motor temperature.
Initializing
If initializing is carried out (parameter 14-22 Operation
Mode), the programmable parameters of the frequency
converter return to their default settings.
Initializing parameter 14-22 Operation Mode does not
initialize communication parameters.
Intermittent duty cycle
An intermittent duty rating refers to a sequence of duty
cycles. Each cycle consists of an on-load and an
period. The operation can be either periodic duty or noneperiodic duty.
LCP
The local control panel makes up a complete interface for
control and programming of the frequency converter. The
control panel is detachable and can be installed up to 3 m
from the frequency converter, that is, in a front panel with
the installation kit option.
lsb
Least signicant bit.
o-load
MCM
Short for Mille Circular Mil, an American measuring unit for
cable cross-section. 1 MCM ≡ 0.5067 mm2.
msb
Most signicant bit.
On-line/O-line parameters
Changes to on-line parameters are activated immediately
after the data value is changed. To activate changes to o-line parameters, press [OK].
PI controller
The PI controller maintains the speed, pressure,
temperature, and so on, by adjusting the output frequency
to match the varying load.
RCD
Residual current device.
Set-up
Save parameter settings in 2 set-ups. Change between the
2 parameter set-ups and edit 1 set-up, while another setup is active.
Slip compensation
The frequency converter compensates for the motor slip by
giving the frequency a supplement that follows the
measured motor load keeping the motor speed almost
constant.
Smart logic control (SLC)
The SLC is a sequence of user-dened actions executed
when the associated user-dened events are evaluated as
true by the SLC.
Thermistor
A temperature-dependent resistor.
STW
Status word.
FC standard bus
Includes RS485 bus with FC protocol.
Trip
A state entered in fault situations, for example, if the
frequency converter is subject to an overtemperature or
when the frequency converter is protecting the motor,
process, or mechanism. Restart is prevented until the cause
of the fault has disappeared and the trip state is canceled
by activating reset or, sometimes, by being programmed to
reset automatically. Do not use trip for personal safety.
Trip lock
A state entered in fault situations when the frequency
converter is protecting itself and requiring physical
intervention, for example, if the frequency converter is
subject to a short circuit on the output. A trip lock can
only be canceled by cutting o mains, removing the cause
of the fault, and reconnecting the frequency converter.
Restart is prevented until the trip state is canceled by
activating reset or, sometimes, by being programmed to
reset automatically. Trip lock may not be used for personal
safety.
Variable torque characteristics used for pumps and fans.
+
VVC
If compared with standard voltage/frequency ratio control,
voltage vector control (VVC+) improves the dynamics and
the stability, both when the speed reference is changed
and in relation to the load torque.
1.5 Power Factor
The power factor is the relation between I
3 × U × I
Power factor =
3 × U × I
1 ×COS ϕ
RMS
The power factor for 3-phase control:
Power factor =
I1 × cosϕ1
I
1
=
I
RMS
sincecosϕ1 = 1
I
RMS
The power factor indicates to which extent the frequency
converter imposes a load on the supply.
The lower the power factor, the higher the I
same kW performance.
2
2
2
I
= I
+ I
RMS
+ I
1
5
+ . . + I
7
2
n
In addition, a high-power factor indicates that the dierent
harmonic currents are low.
Indicates a potentially hazardous situation that could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
NOTICE
Indicates important information, including situations that
can result in damage to equipment or property.
2.1.1 Safety Precautions
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains,
DC supply, or load sharing, the motor may start at any
time. Unintended start during programming, service, or
repair work can result in death, serious injury, or
property damage. The motor can start with an external
switch, a eldbus command, an input reference signal
from the LCP or LOP, via remote operation using MCT 10
Set-up Software, or after a cleared fault condition.
To prevent unintended motor start:
Press [O/Reset] on the LCP before
•
programming parameters.
Disconnect the frequency converter from the
•
mains.
Completely wire and assemble the frequency
•
converter, motor, and any driven equipment
before connecting the frequency converter to
AC mains, DC supply, or load sharing.
22
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input, DC supply, or load sharing.
Failure to perform installation, start-up, and maintenance
by qualied personnel can result in death or serious
injury.
Only qualied personnel must perform instal-
•
lation, start-up, and maintenance.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. High voltage can be present
even when the warning LED indicator lights are o.
Failure to wait the specied time after power has been
removed before performing service or repair work can
result in death or serious injury.
Stop the motor.
•
Disconnect AC mains and remote DC-link power
•
supplies, including battery back-ups, UPS, and
DC-link connections to other frequency
converters.
Disconnect or lock PM motor.
•
Wait for the capacitors to discharge fully. The
•
minimum duration of waiting time is specied
in Table 2.1.
Before performing any service or repair work,
•
use an appropriate voltage measuring device to
make sure that the capacitors are fully
discharged.
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
Ensure the correct grounding of the equipment
•
by a certied electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment
can result in death or serious injury.
Ensure that only trained and qualied personnel
•
perform installation, start-up, and maintenance.
Ensure that electrical work conforms to national
•
and local electrical codes.
Follow the procedures in this guide.
•
WARNING
UNINTENDED MOTOR ROTATION
WINDMILLING
Unintended rotation of permanent magnet motors
creates voltage and can charge the unit, resulting in
death, serious injury, or equipment damage.
Ensure that permanent magnet motors are
•
blocked to prevent unintended rotation.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result
in serious injury when the frequency converter is not
properly closed.
Ensure that all safety covers are in place and
•
securely fastened before applying power.
2.2 Disposal Instruction
Equipment containing electrical
components cannot be disposed of
together with domestic waste.
It must be separately collected with
electrical and electronic waste according
to local and currently valid legislation.
The frequency converter complies with UL 508C thermal
memory retention requirements. For more information
refer to chapter 3.5.1 Motor Thermal Protection.
2.4 CE Labeling
2.4.1 CE Conformity and Labeling
What is CE conformity and labeling?
The purpose of CE labelling is to avoid technical trade
obstacles within EFTA and the EU. The EU has introduced
the CE label as a simple way of showing whether a
product complies with the relevant EU directives. The CE
label says nothing about the specications or quality of
the product. Frequency converters are regulated by 3 EU
directives:
The Machinery Directive (98/37/EEC)
All machines with critical moving parts are covered by the
machinery directive of January 1, 1995. Since a frequency
converter is largely electrical, it does not fall under the
machinery directive. However, if a frequency converter is
supplied for use in a machine, Danfoss provides
information on safety aspects relating to the frequency
converter. Danfoss does this with a manufacturer's
declaration.
The Low Voltage Directive (73/23/EEC)
Frequency converters must be CE labeled in accordance
with the Low Voltage Directive of January 1, 1997. The
directive applies to all electrical equipment and appliances
used in the 50–1000 V AC and the 75–1500 V DC voltage
ranges. Danfoss CE-labels in accordance with the directive
and issues a declaration of conformity on request.
The EMC Directive (2004/108/EC)
EMC is short for electromagnetic compatibility. The
presence of electromagnetic compatibility means that the
mutual interference between
appliances does not aect the way the appliances work.
The EMC directive came into eect January 1, 1996.
Danfoss CE-labels in accordance with the directive and
issues a declaration of conformity after request. To carry
out EMC-correct installation, see the instructions in this
design guide. In addition, Danfoss species which
standards our products comply with. Danfoss oers the
lters presented in the specications and provide other
types of assistance to ensure the optimum EMC result.
The frequency converter is most often used by professionals of the trade as a complex component forming part
of a larger appliance, system, or installation. Note that the
responsibility for the nal EMC properties of the appliance,
system or installation rests with the installer.
The EU Guidelines on the Application of Council Directive89/336/EEC outline 3 typical situations of using a frequency
converter. See chapter 2.4.3 Danfoss Frequency Converterand CE Labelling for EMC coverage and CE labelling.
The frequency converter is sold directly to the
•
end-consumer. The frequency converter is for
example sold to a DIY market. The end-consumer
is a layman. The end-consumer installs the
frequency converter himself for use with a hobby
machine, a kitchen appliance, and so on. For such
applications, the frequency converter must be CE
labeled in accordance with the EMC directive.
The frequency converter is sold for installation in
•
a plant. The plant is built up by professionals of
the trade. It could be a production plant or a
heating/ventilation plant designed and installed
by professionals of the trade. Neither the
frequency converter nor the
be CE labeled under the EMC directive. However,
the unit must comply with the basic EMC
requirements of the directive. This is ensured by
using components, appliances, and systems that
are CE labeled under the EMC directive.
The frequency converter is sold as part of a
•
complete system. The system is being marketed
as complete and could for example, be an airconditioning system. The complete system must
be CE labeled in accordance with the EMC
directive. The manufacturer can ensure CE
labelling under the EMC directive either by using
CE labeled components or by testing the EMC of
the system. It is not necessary to test the entire
system if only CE labeled components are
selected.
nished plant has to
2.4.3 Danfoss Frequency Converter and CE
Labelling
guarantees compliance with the Low Voltage Directive.
Danfoss issues a declaration of conformity that conrms
our CE labelling in accordance with the Low Voltage
Directive.
The CE label also applies to the EMC directive if the
instructions for EMC-correct installation and ltering are
followed. On this basis, a declaration of conformity in
accordance with the EMC directive is issued.
The design guide
to ensure EMC-correct installation. Furthermore, Danfoss
species which our dierent products comply with.
Danfoss provides other types of assistance that can help to
obtain the best EMC result.
oers detailed instructions for installation
2.4.4 Compliance with EMC Directive
2004/108/EC
As mentioned, the frequency converter is mostly used by
professionals of the trade as a complex component
forming part of a larger appliance, system, or installation.
Note that the responsibility for the nal EMC properties of
the appliance, system, or installation rests with the installer.
As an aid to the installer, Danfoss has prepared EMC installation guidelines for the power drive system. If the EMCcorrect instructions for installation are followed, the
standards and test levels stated for power drive systems
are complied with.
Air Humidity
2.5
The frequency converter has been designed to meet the
IEC/EN 60068-2-3 standard, EN 50178 9.4.2.2 at 50 °C
(122 °F).
Aggressive Environments
2.6
A frequency converter contains many mechanical and
electronic components. All are to some extent vulnerable
to environmental eects.
22
CE labelling is a positive feature when used for its original
purpose, that is, to facilitate trade within the EU and EFTA.
However, CE labelling may cover many dierentspeci-cations. Check what a given CE label specically covers.
The covered specications can be dierent and a CE label
may therefore give the installer a false feeling of security
when using a frequency converter as a component in a
system or an appliance.
Danfoss CE labels the frequency converters in accordance
with the Low Voltage Directive. This means that if the
frequency converter is installed correctly, Danfoss
Do not install the frequency converter in environments
with airborne liquids, particles, or gases that may aect
or damage the electronic components. Failure to take
necessary protective measures increases the risk of
stoppages, potentially causing equipment damage and
personnel injury.
Liquids can be carried through the air and condense in the
frequency converter and may cause corrosion of
components and metal parts. Steam, oil, and salt water
may cause corrosion of components and metal parts. In
such environments, use equipment with enclosure rating
130BA780.11
SYSTEM CURVE
FAN CURVE
PRESSURE %
A
B
C
0
20
40
60
80
100
120
20406080 100 120 140 160 180
VOLUME %
Safety and Conformity
VLT® Micro Drive FC 51
IP54. As an extra protection, coated printed circuit boards
Advantages
2.8
can be ordered as an option (standard on some power
sizes).
22
2.8.1 Why use a Frequency Converter for
Controlling Fans and Pumps?
Airborne particles such as dust may cause mechanical,
electrical, or thermal failure in the frequency converter. A
typical indicator of excessive levels of airborne particles is
dust particles around the frequency converter fan. In dusty
environments, use equipment with enclosure rating IP54 or
A frequency converter takes advantage of the fact that
centrifugal fans and pumps follow the laws of proportionality for such fans and pumps. For further information,
see chapter 2.8.3 Example of Energy Savings.
a cabinet for IP20/TYPE 1 equipment.
2.8.2 The Clear Advantage - Energy Savings
In environments with high temperatures and humidity,
corrosive gases such as sulphur, nitrogen, and chlorine
compounds cause chemical processes on the frequency
converter components.
Such chemical reactions rapidly
aect and damage the
electronic components. In such environments, mount the
equipment in a cabinet with fresh air ventilation, keeping
aggressive gases away from the frequency converter.
An extra protection in such areas is a coating of the
printed circuit boards, which can be ordered as an option.
Before installing the frequency converter, check the
ambient air for liquids, particles, and gases. This is done by
observing existing installations in this environment. Typical
indicators of harmful airborne liquids are water or oil on
metal parts, or corrosion of metal parts.
The clear advantage of using a frequency converter for
controlling the speed of fans or pumps lies in the
electricity savings.
When comparing with alternative control systems and
technologies, a frequency converter is the optimum energy
control system for controlling fan and pump systems.
Excessive dust particle levels are often found on installation cabinets and existing electrical installations. One
indicator of aggressive airborne gases is blackening of
copper rails and cable ends on existing installations.
Vibration and Shock
2.7
Illustration 2.1 Fan Curves (A, B, and C) for Reduced Fan
Volumes
The frequency converter has been tested according to the
procedure based on the shown standards, Table 2.2.
The frequency converter complies with requirements that
exist for units mounted on the walls and oors of
production premises, and in panels bolted to walls or
Illustration 2.2 Energy Savings with Frequency Converter
Solution
When using a frequency converter to reduce fan capacity
to 60% - more than 50% energy savings may be obtained
in typical applications.
2.8.3 Example of Energy Savings
As shown in Illustration 2.3, the ow is controlled by
changing the RPM. By reducing the speed by only 20%
from the rated speed, the ow is also reduced by 20%.
This is because the ow is directly proportional to the
RPM. The consumption of electricity, however, is reduced
by 50%.
If the system in question only needs to be able to supply a
ow that corresponds to 100% a few days in a year, while
the average is below 80% of the rated ow for the
remainder of the year, the amount of energy saved is even
more than 50%.
Illustration 2.3 describes the dependence of
and power consumption on RPM.
ow, pressure,
Q=FlowP=Power
Q1=Rated owP1=Rated power
Q2=Reduced owP2=Reduced power
H=Pressuren=Speed control
H1=Rated pressuren1=Rated speed
H2=Reduced pressuren2=Reduced speed
Table 2.3 The Laws of Proportionality
2.8.4 Comparison of Energy Savings
The Danfoss frequency converter solution oers major
savings compared with traditional energy saving solutions
such as discharge damper solution and inlet guide vanes
(IGV) solution. This is because the frequency converter is
able to control fan speed according to thermal load on the
system, and the frequency converter has a built-in facility
that enables the frequency converter to function as a
building management system, BMS.
Illustration 2.3 shows typical energy savings obtainable
with 3 well-known solutions when fan volume is reduced
to 60%.
As the graph shows, more than 50% energy savings can be
achieved in typical applications.
This example is calculated based on pump characteristics
obtained from a pump datasheet.
The result obtained shows energy savings more than 50%
at the given ow distribution over a year. The payback
period depends on the price per kWh and the price of
frequency converter. In this example, it is less than a year
when compared with valves and constant speed.
Energy savings
P
shaft=Pshaft output
Illustration 2.4 The 3 Common Energy Saving Systems
Illustration 2.6 Flow Distribution over 1 Year
Illustration 2.5 Energy Savings
Discharge dampers reduce power consumption. Inlet guide
vanes oer a 40% reduction, but are expensive to install.
The Danfoss frequency converter solution reduces energy
consumption with more than 50% and is easy to install. It
and extends the life span of the entire application.
also reduces noise, mechanical stress and wear-and-tear,
175HA209.11
60
50
40
30
20
10
H
s
0100200300400
(mwg)
B
C
A
750rpm
1050rpm
1350rpm
1650rpm
0
10
20
30
(kW)
40
50
60
200100300
(
m3 /h
)
(
m3 /h
)
400
750rpm
1050rpm
1350rpm
1650rpm
P
shaft
C
1
B
1
A
1
Full load
% Full-load current
& speed
500
100
0
012,52537,550Hz
200
300
400
600
700
800
4
3
2
1
175HA227.10
Safety and ConformityDesign Guide
Simple control of process (ow, level, or pressure) utilizing
the built-in PI control.
2.8.7 Star/Delta Starter or Soft Starter not
Required
When larger motors are started, it is necessary in many
countries to use equipment that limits the start-up current.
In more traditional systems, a star/delta starter or soft
starter is widely used. Such motor starters are not required
if a frequency converter is used.
As illustrated in Illustration 2.8, a frequency converter does
not consume more than rated current.
22
Illustration 2.7 Energy
m3/
h
Distri-
bution
Valve regulationFrequency converter
% Hours PowerConsump-
A1 - B
350543842.518.61542.518.615
300 15 131438.550.58929.038.106
1
250 20 175235.061.32018.532.412
200 20 175231.555.18811.520.148
150 20 175228.049.0566.511.388
100 20 175223.040.2963.56.132
100 8760275.06426.801
Σ
Table 2.4 Result
2.8.6 Better Control
If a frequency converter is used for controlling the ow or
pressure of a system, improved control is obtained.
A frequency converter can vary the speed of the fan or
pump, obtaining variable control of ow and pressure.
Furthermore, a frequency converter can quickly adapt the
speed of the fan or pump to new ow or pressure
conditions in the system.
The example in chapter 2.8.9 Without a Frequency Converter
shows that a frequency converter replaces other
equipment. It is possible to calculate the cost of installing
the 2 dierent systems. In the example, the 2 systems can
be established at roughly the same price.
Use the VLT® Energy Box software that is introduced in
chapter 1.1 Available Literature to calculate the cost savings
that can be achieved by using a frequency converter.
Select the conguration mode in parameter 1-00 Conguration Mode.
3.1.1 Control Structure Open Loop
Illustration 3.1 Open-loop Structure
In the conguration shown in Illustration 3.1,
parameter 1-00 Conguration Mode is set to [0] Open loop.
The resulting reference from the reference handling system
or the local reference is received and fed through the ramp
limitation and speed limitation before being sent to the
motor control. The output from the motor control is then
limited by the maximum frequency limit.
frequency converter via the digital inputs and RS485. See
more about starting, stopping, changing ramps and
parameter set-ups, and so on, in parameter group 5-1*
Digital Inputs or parameter group 8-5* Serial Communication.
3.1.2 Local (Hand On) and Remote (Auto
On) Control
The frequency converter can be operated manually via the
local control panel (LCP) or remotely via analog/digital
inputs or eldbus. If allowed in parameter 0-40 [Hand on]
Key on LCP, parameter 0-44 [O/Reset] Key on LCP, and
parameter 0-42 [Auto on] Key on LCP, it is possible to start
and stop the frequency converter by pressing the [Hand
On] and [O/Reset] keys. Alarms can be reset via the [O/Reset] key. After pressing the [Hand On] key, the frequency
converter goes into hand mode and follows (by default)
the local reference set using the LCP potentiometer (LCP
12) or [▲]/[▼] (LCP 11). The potentiometer can be disabled
using parameter 6-80 LCP Potmeter Enable. If the potenti-
ometer is disabled, use the navigation keys for adjusting
reference.
After pressing the [Auto On] key, the frequency converter
goes into auto mode and follows (by default) the remote
reference. In this mode, it is possible to control the
Local reference forces the conguration mode to open
loop, independent on the setting of 1-00 CongurationMode.
Local reference is restored at power-down.
3.1.3 Control Structure Closed Loop
The internal controller allows the frequency converter to
become a part of the controlled system. The frequency
converter receives a feedback signal from a sensor in the
system. It then compares this feedback to a setpoint
reference value and determines the error, if any, between
these 2 signals. It then adjusts the speed of the motor to
correct this error.
7-30 PI
Normal/Inverse
Control
PI
Reference
Feedback
Scale to
speed
P 4-10
Motor speed
direction
To motor
control
130BB894.11
S
100%
0%
-100%
100%
*[-1]
_
+
Product OverviewDesign Guide
For example, consider a pump application where the speed
of a pump is to be controlled so that the static pressure in
a pipe is constant. The static pressure value is supplied to
the frequency converter as the setpoint reference. A static
pressure sensor measures the actual static pressure in the
pipe and supplies this data to the frequency converter as a
feedback signal. If the feedback signal is greater than the
Illustration 3.3 Control Structure Closed Loop
While the default values for the closed-loop controller of
the frequency converter often provide satisfactory
performance, the control of the system can often be
optimized by adjusting parameters.
setpoint reference, the frequency converter slows the
pump down to reduce the pressure. In a similar way, if the
pipe pressure is lower than the setpoint reference, the
frequency converter automatically speeds the pump up to
increase the pressure provided by the pump.
Up to 8 preset references can be programmed in the
frequency converter. The active preset reference can be
selected using digital inputs or the serial communications
bus. The reference can also be supplied externally, most
commonly from an analog input. This external source is
selected by 1 of the 3 reference source parameters
(parameter 3-15 Reference 1 Source,
parameter 3-16 Reference 2 Source, and
parameter 3-17 Reference 3 Source). All reference resources
and the bus reference are added to produce the total
external reference. The external reference, the preset
reference, or the sum of the 2 can be selected to be the
External references (analog inputs and serial
communication bus references).
The preset relative reference.
Feedback-controlled setpoint.
active reference. Finally, this reference can by be scaled
using parameter 3-14 Preset Relative Reference.
The scaled reference is calculated as follows:
Reference = X + X ×
Where X is the external reference, the preset reference or
100
Y
the sum of these and Y is parameter 3-14 Preset Relative
Reference in [%].
If Y, parameter 3-14 Preset Relative Reference, is set to 0%,
the reference is not
aected by the scaling.
1
2
z
z
z
L1
L2
L3
PE
U
V
W
C
S
I
2
I
1
I
3
I
4
C
S
C
S
C
S
C
S
I
4
C
S
z
PE
3
4
5
6
175ZA062.12
Product OverviewDesign Guide
3.2 General Aspects of EMC
3.2.1 General Aspects of EMC Emissions
Frequency converters (and other electrical devices)
generate electronic or magnetic elds that may interfere
with their environment. The electromagnetic compatibility
(EMC) of these eects depends on the power and the
harmonic characteristics of the devices.
Uncontrolled interaction between electrical devices in a
system can degrade compatibility and impair reliable
operation. Interference may take the form of mains
harmonics distortion, electrostatic discharges, rapid voltage
uctuations, or high frequency interference. Electrical
devices generate interference along with being aected by
interference from other generated sources.
Electrical interference usually occurs at frequencies in the
range 150 kHz to 30 MHz. Airborne interference from the
frequency converter system in the range 30 MHz to 1 GHz
is generated from the inverter, motor cable, and the motor.
Capacitive currents in the motor cable coupled with a high
dU/dt from the motor voltage generate leakage currents,
as shown in Illustration 3.5.
The use of a shielded motor cable increases the leakage
current (see Illustration 3.5) because shielded cables have
higher capacitance to ground than unshielded cables. If
the leakage current is not
interference on the mains in the radio frequency range
below approximately 5 MHz. Since the leakage current (I1)
is carried back to the unit through the shield (I3), there is,
in principle, only a small electro-magnetic eld (I4) from
the shielded motor cable according to Illustration 3.5.
ltered, it causes greater
The shield reduces the radiated interference, but increases
the low-frequency interference on the mains. Connect the
motor cable shield to the frequency converter enclosure
and to the motor enclosure. Use the integrated shield
clamps to avoid twisted-pair ends (pigtails). Pigtails
increase the shield impedance at higher frequencies, which
reduces the shield eect and increases the leakage current
(I4).
If a shielded cable is used for relay, control cable, signal
interface, and brake, mount the shield on the enclosure at
both ends. In some situations, it is necessary to break the
shield to avoid current loops.
When placing the shield on a mounting plate for the
frequency converter, ensure that the mounting plate is
made of metal, to convey the shield currents back to the
unit. Ensure good electrical contact from the mounting
plate through the mounting screws to the frequency
converter chassis.
When using unshielded cables, some emission
requirements are not complied with, although most
immunity requirements are observed.
To reduce the interference level from the entire system
(unit+installation), make motor and brake cables as short
as possible. Avoid placing cables with a sensitive signal
level alongside motor cables and brake cables. The control
electronics generate radio interference at frequencies
higher than 50 MHz (airborne).
33
1Ground wire3AC mains supply5 Shielded motor cable
The EMC product standard for frequency converters
denes 4 categories (C1, C2, C3, and C4) with specied
requirements for emission and immunity. Table 3.1 states
the denition of the 4 categories and the equivalent classi-
33
cation from EN 55011.
CategoryDenition
C1Frequency converters installed in
the rst environment (home and
oce) with a supply voltage less
than 1000 V.
C2Frequency converters installed in
the rst environment (home and
oce) with a supply voltage less
than 1000 V, which are not plug-in
and not movable, and must be
installed and commissioned by a
professional.
C3Frequency converters installed in
the second environment (industrial)
with a supply voltage lower than
1000 V.
Equivalent
emission class
in EN 55011
Class B
Class A Group 1
Class A Group 2
C4Frequency converters installed in
the second environment with a
supply voltage equal to or above
1000 V, or rated current equal to or
above 400 A, or intended for use in
complex systems.
Table 3.1 Correlation between IEC 61800-3 and EN 55011
When the generic (conducted) emission standards are
used, the frequency converters are required to comply with
the limits in Table 3.2.
Environment
First
environment
(home and
oce)
Second
environment
(industrial
environment)
Generic emission
standard
EN/IEC 61000-6-3 Emission
standard for residential,
commercial, and light
industrial environments.
EN/IEC 61000-6-4 Emission
standard for industrial
environments.
Equivalent
emission class
in EN 55011
No limit line.
Make an EMC
plan.
Equivalent
emission class in
EN 55011
Class B
Class A Group 1
Table 3.2 Correlation between Generic Emission Standards and
EN 55011
3.2.3 EMC Test Results (Emission)
FC typeConducted emission. Maximum shielded cable length [m]Radiated emission
Industrial environment
EN 55011 Class A2EN 55011 Class A1EN 55011 Class BEN 55011 Class A2EN 55011 Class A1
Without a power option, the frequency converter may
not comply with harmonics emission requirements.
OptionsDenition
1IEC/EN 61000-3-2 Class A for 3-phase balanced
equipment (for professional equipment only up to 1
kW total power).
2IEC/EN 61000-3-12 Equipment 16 A-75 A and profes-
sional equipment as from 1 kW up to 16 A phase
current.
Table 3.4 Harmonics Emission Requirements
3.2.5 Immunity Requirements
The immunity requirements for frequency converters
depend on the environment where they are installed. The
requirements for the industrial environment are higher
than the requirements for the home and oce
environment. All Danfoss frequency converters comply
with the requirements for the industrial environment and
therefore comply also with the lower requirements for
home and oce environment with a large safety margin.
0.25–22 kW (0.34–30 hp)
33
1 Supply (SMPS)
2 Optocouplers, communication between AOC and BOC
3 Custom relays
a Control card terminals
Illustration 3.6 Galvanic Isolation
30–90 kW (40–120 hp)
Galvanic Isolation (PELV)
3.3
PELV oers protection through extra low voltage.
Protection against electric shock is ensured when the
electrical supply is of the PELV type and the installation is
made as described in local/national regulations on PELV
supplies.
All control terminals and relay terminals 01-03/04-06
comply with PELV (protective extra low voltage) (does not
apply to grounded delta leg above 440 V).
Galvanic (ensured) isolation is obtained by
fullling
requirements for higher isolation and by providing the
relevant creapage/clearance distances. These requirements
are described in the EN 61800-5-1 standard.
The components that make up the electrical isolation, as
described, also comply with the requirements for higher
isolation and the relevant test as described in EN
61800-5-1.
The PELV galvanic isolation can be shown in Illustration 3.7.
To maintain PELV, all connections made to the control
terminals must be PELV, for example, thermistor must be
reinforced/double insulated.
1 Supply (SMPS) including signal isolation of UDC, indicating
the intermediate current voltage
2 Gate drive that runs the IGBTs (trigger transformers/opto-
couplers)
3 Current transducers
4 Internal soft-charge, RFI, and temperature measurement
circuits
5 Custom relays
a Control card terminals
Illustration 3.7 Galvanic Isolation
The functional galvanic isolation (see Illustration 3.6) is for
the RS485 standard bus interface.
At altitudes above 2000 m (6500 ft), contact Danfoss
regarding PELV.
33
3.4 Ground Leakage Current
WARNING
DISCHARGE TIME
Touching the electrical parts could be fatal - even after
the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been
disconnected, such as load sharing (linkage of DC
intermediate circuit), and the motor connection for
kinetic back-up.
Before touching any electrical parts, wait at least the
amount of time indicated in Table 2.1.
Shorter time is allowed only if indicated on the
nameplate for the specic unit.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
Ensure the correct grounding of the equipment
•
by a certied electrical installer.
WARNING
RESIDUAL CURRENT DEVICE PROTECTION
This product can cause a DC current in the protective
conductor. Where a residual current device (RCD) is used
for protection in case of direct or indirect contact, only
an RCD of Type B is allowed on the supply side of this
product. Otherwise, apply another protective measure,
such as separation from the environment by double or
reinforced insulation, or isolation from the supply system
by a transformer. See also application note Protectionagainst Electrical Hazards.
Protective grounding of the frequency converter and the
use of RCDs must always follow national and local
regulations.
3.5 Extreme Running Conditions
Short circuit (motor phase-phase)
Current measurement in each of the 3 motor phases or in
the DC-link, protects the frequency converter against short
circuits. A short circuit between 2 output phases causes an
overcurrent in the inverter. The inverter is turned o
individually when the short circuit current exceeds the
allowed value (Alarm 16 Trip Lock).
For information about protecting the frequency converter
against a short circuit at the load sharing and brake
outputs, see chapter 6.6 Fuses.
Switching on the output
Switching on the output between the motor and the
frequency converter is fully permitted. The frequency
converter is not damaged in any way by switching on the
output. However, fault messages may appear.
Motor-generated overvoltage
The voltage in the DC link is increased when the motor
acts as a generator. This occurs in following cases:
The load drives the motor (at constant output
•
frequency from the frequency converter), that is
the load generates energy.
During deceleration (ramp-down) if the inertia
•
moment is high, the friction is low, and the rampdown time is too short for the energy to be
dissipated as a loss in the frequency converter,
the motor, and the installation.
Incorrect slip compensation setting
•
(parameter 1-62 Slip Compensation) may cause
higher DC-link voltage.
The control unit may attempt to correct the ramp if
parameter 2-17 Over-voltage Control is enabled.
The frequency converter turns o to protect the transistors
and the DC link capacitors when a certain voltage level is
reached.
Mains drop-out
During a mains drop-out, the frequency converter keeps
running until the DC-link voltage drops below the
minimum stop level, which is typically 15% below the
frequency converter's lowest rated supply voltage. The
mains voltage before the drop-out and the motor load
determines how long it takes for the frequency converter
to coast.
3.5.1 Motor Thermal Protection
Motor thermal protection can be provided in 2 ways.
Using a motor thermistor, via 1 of the following:
Thermistor input on a standard AI.
•
VLT® Sensor Input MCB 114.
•
VLT® PTC Thermistor Card MCB 112.
•
The frequency converter monitors motor temperature as
the speed and load vary to detect overheating conditions.
The other method calculates motor temperature by
measuring current, frequency, and operating time. The
frequency converter shows the thermal load on the motor
in percentage and can issue a warning at a programmable
overload setpoint. Programmable options at the overload
allow the frequency converter to stop the motor, reduce
output, or ignore the condition. Even at low speeds, the
frequency converter meets I2t Class 20 electronic motor
overload standards.
This method is called electronic thermal relay (ETR).
33
Illustration 3.8 ETR Characteristics
The X-axis shows the ratio between I
motor
and I
motor
nominal. The Y axis shows the time in s before the ETR cut
of and trips the frequency converter. The curves show the
characteristic nominal speed, at twice the nominal speed
and at 0.2 x the nominal speed.
At lower speed, the ETR cuts o at lower heat due to less
cooling of the motor. In that way, the motor is protected
from being overheated even at low speed. The ETR feature
is calculating the motor temperature based on actual
current and speed. The calculated temperature is visible as
a readout parameter in parameter 16-18 Motor Thermal in
the product-specicProgramming Guide.
A special version of the ETR is also available for EX-e
motors in ATEX areas. This function makes it possible to
enter a specic curve to protect the Ex-e motor. The
Programming Guide takes the user through the set-up.
For detailed information on programming, see VLT® Micro
44
Drive FC 51 Programming Guide.
NOTICE
The frequency converter can also be programmed from a
PC via RS485 port by installing the MCT 10 Set-up
Software.
This software can either be ordered using code number
130B1000 or downloaded from the Danfoss website:
A yellow indicator light above the operation keys indicates
the active key.
[Hand On]: Starts the motor and enables control of the
frequency converter via the LCP.
[O/Reset]: Stops the motor (o). If in alarm mode, the
alarm is reset.
[Auto On]: The frequency converter is controlled either via
control terminals or serial communication.
[Potentiometer] (LCP 12): The potentiometer works in 2
ways:
In auto mode the potentiometer acts as an extra
programmable analog input.
In hand-on mode, the potentiometer controls local
reference.
4.1.2 Remote Mounting Kit for LCP
The LCP can be moved to the front of a cabinet by using
the remote built-in kit. The enclosure is IP55.
EnclosureIP55 front
Maximum cable length between LCP and
unit3 m
Communication standard:RS485
Ordering number132B0102
Illustration 4.1 Description of LCP Keys and Display
Press [Menu] to select one of the following menus:
Status
For readouts only.
Quick Menu
For access to Quick Menus 1 and 2.
Main Menu
For access to all parameters.
Navigation keys
[Back]: For moving to the previous step or layer in the
navigation structure.
[▲] [▼]: For maneuvering between parameter groups,
parameters and within parameters.
[OK]: For selecting a parameter and for accepting changes
to parameter settings.
Table 4.1 Technical Data
4.1.3 FC 51 Remote Mounting Kit Mounting
Instruction
Step 1
Fit the gasket on the LCP in the frequency converter.
Fit frequency converter on DIN rail (DIN rail kit is only for
M1 and M2).
4.1.14 Line Filter MCC 107 Installation
Instructions
Line lters of the type MCC 107 combine a harmonic lter
and an EMC lter. The line lters improve performance of
the line current to the frequency converter. The 3 dierent
line lter enclosure sizes correspond to the VLT® Micro
Drive enclosure types M1, M2 and M3.
44
1 Mounting holes for frequency converter
2 Input terminal
3 Output line
4 Protective earth (PE)
Illustration 4.27 Line Filter MCC 107 with VLT® Micro Drive FC
51
CAUTION
HOT SURFACES
The surface of the line lter can get hot during
operation.
Do not touch the line lter during operation or
•
wear protective gloves.
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input, DC supply, or load sharing.
Failure to perform installation, start-up, and maintenance
by qualied personnel can result in death or serious
Illustration 4.26 Fit Frequency Converter on DIN Rail
injury.
Only qualied personnel must perform instal-
•
lation, start-up, and maintenance.
NOTICE
Always replace defective lters, never repair them.
Consider the purpose of derating when using the
frequency converter at low air pressure (heights), at low
speeds, with long motor cables, cables with a large crosssection, or at high ambient temperature. The required
action is described in this section.
44
4.2.2 Derating for Ambient Temperature
Derating for ambient temperature and IGBT switching.
Illustration 4.34 M2 200 V
The ambient temperature measured over 24 hours should
be at least 5 °C lower than the maximum ambient
temperature. If the frequency converter is operated at high
ambient temperature, decrease the constant output
current. The frequency converter has been designed for
operation at maximum 50 °C ambient temperature with 1
motor size smaller than nominal. Continuous operation at
full load at 50 °C ambient temperature reduces the lifetime
of the frequency converter.
The cooling capability of air is decreased at low air
pressure.
CAUTION
INSTALLATION AT HIGH ALTITUDE
For altitudes above 2000 m (6560 ft), contact Danfoss
regarding PELV.
Below 1000 m (3280 ft) altitude, no derating is necessary,
but above 1000 m (3280 ft), decrease the ambient
temperature or the maximum output current.
Decrease the output by 1% per 100 m (328 ft) altitude
above 1000 m (3280 ft), or reduce the maximum ambient
temperature by 1 °C per 200 m (656 ft).
4.2.4 Automatic Adaptations to Ensure
Performance
44
The frequency converter constantly checks for critical levels
of:
Internal temperature.
•
Load current.
•
High voltage on the DC link.
•
Low motor speeds.
Illustration 4.38 M4 200 V
•
As a response to a critical level, the frequency converter
can adjust the switching frequency and/or change the
switching pattern to ensure the performance of the
frequency converter. The capability for automatic output
current reduction extends the acceptable operating
conditions even further.
4.2.5 Derating for Running at Low Speed
When a motor is connected to a frequency converter, it is
necessary to check that the cooling of the motor is
adequate. The level of heating depends on the load on the
motor, as well as the operating speed and time.
A problem may occur at low RPM values in constant
torque applications. In a constant torque application, a
motor may overheat at low speeds due to less cooling air
from the motor integral fan.
Therefore, if the motor runs continuously at an RPM value
lower than half of the rated value, supply the motor with
extra air-cooling (or use a motor designed for this type of
operation).
An alternative is to reduce the load level of the motor by
using a larger motor. However, the design of the frequency
converter puts a limit to the motor size.
How to Order
5 How to Order
VLT® Micro Drive FC 51
5.1 Drive Congurator
It is possible to design a frequency converter according to
the application requirements by using the ordering
number system.
To order standard frequency converters and frequency
converters with integral options, send a type code string
55
describing the product to the Danfoss sales
example type code:
FC051PXXXXXXXXHXXXXXXXSXXX
Use the web-based Drive
right frequency converter for the right application and
generate the type code string. The Drive Congurator
automatically generates an 8-digit sales number (either for
1 product or a project list with several products) to be
delivered to your local sales oce.
Fine the Drive Congurator at: www.vlt-drives.danfoss.com/support/drive-congurator/.
Congurator to congure the
oce. An
FC Identication
5.2
The nameplate sticker is located on the top of each
frequency converter and shows the ratings, serial number,
warnings catalog number, and other relevant data for each
unit. See Table 5.2 for details, how to read the type code
string.
When unpacking the frequency converter, make sure that
the unit is undamaged and complete. Check that the
packaging contains the following:
VLT® Micro Drive FC 51
•
Quick Guide
•
Optional: LCP and/or decoupling plate.
Side-by-Side Installation
6.2
The frequency converter can be mounted side-by-side for
IP20 rating units and requires 100 mm (3.94 in) clearance
above and below for cooling. Regarding surroundings in
general, see chapter 9 Specications.
Illustration 6.2 Side-by-side Installation
Illustration 6.1 Content of Box
Mechanical Dimensions
6.4
A template for drilling is on the ap of the packaging.
6.3 Before Commencing Repair Work
1.Disconnect the FC 51 from mains (and external
DC supply, if present).
2.Wait for 4 minutes (M1, M2, and M3) and 15
minutes (M4 and M5) for discharge of the DC-link.
See Table 2.1.
3.Disconnect the DC bus terminals and the brake
terminals (if present).
1) For LCP with potentiometer, add 7.6 mm (0.3 in).
Illustration 6.3 Mechanical Dimensions
Electrical Installation in General
6.5
A (including
decoupling plate)
aBbC[kg]
Depth1) [mm]
Maximum
weight
NOTICE
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper
conductors required, (60–75 °C) recommended.
Power [kW ]Torque [Nm]
Enclosure 1x200–240 V 3x200–240 V 3x380–480 V LineMotorDC connection/brake Control terminals GroundRelay
M10.18–0.750.25–0.750.37–0.750.80.7
M21.51.51.5–2.20.80.7
M32.22.2–3.73.0–7.50.80.7
M4––11.0–15.01.31.31.30.1530.5
M5––18.5–22.01.31.31.30.1530.5
1) Spade connectors (6.3 mm (0.25 in) Faston plugs)
To avoid overheating of the cables in the installation,
Branch circuit protection
To protect the installation against electrical and re
hazards, protect all branch circuits in an installation, switch
gear, machines, and so on, against short circuits and
overcurrent according to national/international regulations.
Short-circuit protection
Use the fuses mentioned in Table 6.2 to protect service
personnel or other equipment if there is an internal failure
in the unit or short circuit on DC-link. If there is a short
circuit on the motor or brake output, the frequency
converter provides full short-circuit protection.
provide overload protection. Always carry out overcurrent
protection according to national regulations. Fuses must be
designed for protection in a circuit capable of supplying a
maximum of 100000 A
(symmetrical), 480 V maximum.
rms
Non-UL compliance
If UL/cUL is not to be complied with, use the fuses
mentioned in Table 6.2, which ensure compliance with
EN50178/IEC61800-5-1:
If there is a malfunction, not following the fuse recommendation may result in damage to the frequency converter
and the installation.
Step 2: Mount wires in terminals L1/L, L2, and L3/N and
tighten.
Illustration 6.4 Mounting of Ground Cable and Mains Wires
For 3-phase connection, connect wires to all 3 terminals.
For single-phase connection, connect wires to terminals
L1/L and L3/N.
All types of 3-phased asynchronous standard motors can
be connected to the frequency converter. Normally, small
motors are star-connected (230/400 V, Δ/Y). Large motors
are delta-connected (400/690 V, Δ/Y). Refer to the motor
nameplate for correct connection and voltage.
Illustration 6.6 Star and Delta Connections
Step 1: Mount the ground cable.
Step 2: Connect wires to terminals either in star or delta
connection. See the motor nameplate for further
information.
6
6
Illustration 6.5 3-phase and Single-phase Wire Connections
6.8 Motor Connection
6.8.1 How to Connect the Motor
See chapter 9 Specications for correct dimensioning of
motor cable cross-section and length.
Use a shielded/armored motor cable to comply
•
with EMC emission
this cable to both the decoupling plate and the
motor metal.
Keep the motor cable as short as possible to
•
reduce the noise level and leakage currents.
For further details on mounting of the decoupling plate,
see VLT® Micro Drive FC 51 Decoupling Plate Mounting
Instruction for M1 and M2.
specications, and connect
Illustration 6.7 Mounting of Ground Cable and Motor Wires
For EMC-correct installation, use optional decoupling plate,
see chapter 5.5 Options.
Illustration 6.8 Frequency Converter with Decoupling Plate
See chapter 9 Specications for maximum dimensioning of
motor cable cross-section and length.
Use a shielded/armored motor cable to comply
•
with EMC emission specications.
Keep the motor cable as short as possible to
•
reduce the noise level and leakage currents.
Connect the motor cable shield to both the
•
decoupling plate of the frequency converter and
to the metal cabinet of the motor.
Make the shield connections with the largest
•
possible surface area (cable clamp). This is done
by using the supplied installation devices in the
frequency converter.
Avoid mounting with twisted shield ends
•
(pigtails), which spoils high frequency shielding
eects.
If it is necessary to split the shield to install a
•
motor isolator or motor relay, the shield must be
continued with the lowest possible HF
impedance.
6.8.3 Electrical Installation of Motor Cables
Shielding of cables
Avoid installation with twisted shield ends (pigtails). They
spoil the shielding eect at higher frequencies.
If it is necessary to break the shield to install a motor
isolator or motor contactor, the shield must be continued
at the lowest possible HF impedance.
Cable length and cross-section
The frequency converter has been tested with a given
length of cable and a given cross-section of that cable. If
the cross-section is increased, the cable capacitance, and
thus the leakage current, may increase, and the cable
length must be reduced correspondingly.
Switching frequency
When frequency converters are used together with sinewave lters to reduce the acoustic noise from a motor, the
switching frequency must be set according to the sinewave lter instruction in parameter 14-01 SwitchingFrequency.
Aluminum conductors
Aluminum conductors are not recommended. When using
aluminum conductors, ensure that the conductor surface is
clean and the oxidation is removed and sealed by a
neutral acid-free grease before connecting the conductor.
Retighten the terminal screw after 2 days due to the
softness of aluminum. It is crucial to keep the connection a
gas-tight joint, otherwise the aluminum surface oxidizes
again.
6.8.4 EMC-correct Electrical Installation
General points to be observed to ensure EMC-correct
electrical installation.
Use only shielded/armored motor cables and
•
shielded/armored control cables.
Connect the shield to ground at both ends.
•
Avoid installation with twisted shield ends
•
(pigtails), since this ruins the shielding
high frequencies. Use the cable clamps provided
instead.
It is important to ensure good electrical contact
•
from the installation plate through the installation
screws to the metal cabinet of the frequency
converter.
The lower the Z the better the cable screening performance
Transfer impedance, Z
t
mOhm/m
How to Install
6.9 Use of EMC-Correct Cables
Danfoss recommends braided shielded/armored cables to
optimize EMC immunity of the control cables and the EMC
emission from the motor cables.
The ability of a cable to reduce the ingoing and outgoing
radiation of electric noise depends on the transfer
impedance (ZT). The shield of a cable is normally designed
to reduce the transfer of electric noise; however, a shield
with a lower transfer impedance (ZT) value is more
eective than a shield with a higher transfer impedance
(ZT).
Transfer impedance (ZT) is rarely stated by cable manufac-
6
turers, but it is often possible to estimate transfer
impedance (ZT) by assessing the physical design of the
cable.
Transfer impedance (ZT) can be assessed based on the
following factors:
VLT® Micro Drive FC 51
The conductibility of the shield material.
•
The contact resistance between the individual
•
shield conductors.
The shield coverage, that is, the physical area of
•
the cable covered by the shield - often stated as
a percentage value.
Shield type, that is, braided or twisted pattern.
•
-Aluminum-clad with copper wire.
-Twisted copper wire or armored steel
wire cable.
-Single-layer braided copper wire with
varying percentage shield coverage.
This is the typical Danfoss reference
cable.
-Double-layer braided copper wire.
-Twin layer of braided copper wire with a
magnetic, shielded/armored
intermediate layer.
-Cable that runs in copper tube or steel
tube.
-Lead cable with 1.1 mm (0.04 in) wall
thickness.
Illustration 6.10 Transfer Impedance of Dierent Wires
Braid and shield/armor the control cables. Connect the
shield to the metal cabinet of the unit with a cable clamp
at both ends. Illustration 6.11 shows correct grounding
examples.
a.Correct grounding
Control cables and cables for serial communication are tted with cable clamps at both ends
to ensure the best possible electrical contact.
b.Incorrect grounding
Do not use twisted cable ends (pigtails). They
increase the shield impedance at high
frequencies.
c.Protection from potential between PLC and
frequency converter
If the ground potential between the frequency
converter and the PLC is dierent, electric noise
that disturbs the entire system is possible. Fit an
equalizing cable, next to the control cable.
Minimum cable cross-section: 16 mm2 (4 AWG).
d.For 50/60 Hz ground loops
Long control cables sometimes causes 50/60 Hz
ground loops. Connect 1 end of the shield to
ground via a 100 nF capacitor (keeping leads
short).
e.Cables for serial communication
Eliminate low-frequency noise currents between 2
frequency converters by connecting 1 end of the
shield to terminal 61. This terminal is connected
to ground via an internal RC link. Use twisted-pair
cables to reduce the dierential mode
interference between the conductors.
6
6
a Correct grounding
b Incorrect grounding
c Protection from potential between PLC and frequency
converter
d 50/60 Hz ground loops
e Cables for serial communication
Residual Current Device
6.11
If local safety regulations are complied with, use RCD
relays, multiple protective grounding, or grounding as
extra protection.
If an ground fault appears, a DC content may develop in
the faulty current.
If RCD relays are used, observe local regulations. Relays
must be suitable for protection of 3-phase equipment with
a bridge rectier and for a brief discharge on power-up,
see chapter 3.4 Ground Leakage Current for further
information.
Illustration 6.12 Diagram Showing all Electrical Terminals
* Brakes (BR+ and BR-) are not applicable for enclosure size M1.
For information about brake resistors, see VLT® Brake Resistor MCE 101 Design Guide.
Improved power factor and EMC performance can be achieved by installing optional Danfoss line lters.
Danfoss power lters can also be used for load sharing. For more information about load sharing, see VLT® FC 51 Micro Drive
Load Sharing application note.
53Analog input (voltage or current)3-15/6-1*Reference
55Common analog ground–Common
60Current input3-16/6-2*Reference
Table 6.3 Terminal Connections
6
6
Long control cables and analog signals may, in rare cases
and depending on installation, result in 50/60 Hz ground
loops due to noise from mains supply cables.
If this occurs, break the shield or insert a 100 nF capacitor
between shield and chassis.
NOTICE
To separate common terminals 20, 39, and 55, connect
the common of digital/analog inputs and outputs. This
avoids ground current interference among groups. For
example, it avoids switching on digital inputs disturbing
analog inputs.
NOTICE
Control cables must be shielded/armored.
6.14 Control Terminals
6.14.1 Access to Control Terminals
All control cable terminals are located underneath the
terminal cover in front of the frequency converter. Remove
the terminal cover using a screwdriver.
Illustration 6.13 Removing Terminal Cover
NOTICE
See back of terminal cover for outlines of control
terminals and switches.
Illustration 6.14 shows all control terminals of the frequency
converter. Applying start (terminal 18) and an analog
reference (terminals 53 or 60) make the frequency
converter run.
Illustration 6.14 Overview of Control Terminals in PNP-congu-
ration and Factory Setting
6.15 Switches
NOTICE
Do not operate switches with power on the frequency
converter.
S200 Switches 1-4
Switch 1
Switch 2
Switch 3No function
Switch 4
*=default setting
Illustration 6.16 S200 Switches 1–4
*O=PNP terminals 29
On=NPN terminals 29
*O=PNP terminal 18, 19, 27, and 33
On=NPN terminal 18, 19, 27, and 33
*O=Terminal 53 0–10 V
On=Terminal 53 0/4–20 mA
NOTICE
Set parameter 6-19 Terminal 53 Mode according to switch
4 position.
Bus termination
Switch BUS TER position ON terminates the RS485 port,
terminals 68, 69. See Illustration 6.15.
Default setting = O
Illustration 6.15 S640 Bus Termination
6.16 Final Set-Up and Test
To test the set-up and ensure that the frequency converter
is running, follow these steps.
Step 1. Locate the motor nameplate
The motor is either star- (Y) or delta-connected (Δ). This
information is on the motor nameplate data.
Step 2. Enter the motor nameplate data in this
parameter list
To access this list, press the [Quick Menu] key and select
Q2 Quick Setup.
1.The frequency converter enters into alarm mode.
A description of the alarm can be found in the
Troubleshooting section in VLT® Micro Drive FC 51
Programming Guide.
2.Report value in the [Alarm Log] shows the last
measuring sequence carried out by the AMT,
before the frequency converter entered alarm
mode. This number along with the description of
the alarm helps with troubleshooting. Contact
Danfoss Service and make sure to mention
number and alarm description.
Unsuccessful AMT is often caused by incorrectly registered
motor nameplate data or too big dierence between the
motor power size and the frequency converter power size.
Step 4. Set speed limit and ramp time
Set up the limits for speed and ramp time.
6
6
Illustration 6.17 Motor Nameplate Example
Step 3. Activate the automatic motor tuning (AMT)
Performing an AMT ensures optimum performance. The
AMT measures the values from the motor model
equivalent diagram.
1.Connect terminal 27 to terminal 12 or set
parameter 5-12 Terminal 27 Digital Input to [0] No
function.
2.Activate the AMT 1-29 Automatic Motor Tuning
(AMT).
3.Select between complete or reduced AMT. If an
LC lter is mounted, run only the reduced AMT,
or remove the LC lter during the AMT
procedure.
4.Press [OK]. The display shows Press [Hand On] to
Stop the AMT during operation
start.
5.Press [Hand On]. A progress bar indicates if the
AMT is in progress.
1.Press [O] - the frequency converter enters into
alarm mode and the display shows that the user
terminated the AMT.
The frequency converter can control several motors
connected in parallel. When using a parallel motor
connection, consider the following points:
When motors are connected in parallel, parameter
•
1-29 Automatic Motor Tuning (AMT) cannot be
used.
Run applications with motors connected in
•
parallel in U/F mode (volts per hertz).
The usage of VVC+ mode is limited to certain
•
applications when the motors connected in
parallel are of the same type and size.
Total current consumption of motors must not
•
exceed the rated output current I
frequency converter.
Signicantdierence in motor sizes may cause
•
problems at start and at low RPM. The relatively
high ohmic resistance in the stator of a small
motor demands higher voltage at start and at
low RPM.
Do not use the electronic thermal relay (ETR) of
•
the frequency converter as motor protection. To
provide extra motor protection, include
thermistors in each motor winding or individual
thermal relays.
During the installation of a parallel motor application,
consider the following points:
Connection A/B is only possible when the total
•
motor cable is shorter than 50 m (164 ft).
In connection C/D the total motor cable length
•
specied in general specications is valid as long
as the parallel cables are less than 10 m (32.8 ft).
For motor cable lengths ≤ the maximum cable length
listed in chapter 9.1
insulation ratings are recommended, because the peak
voltage can be up to twice the DC-link voltage, 2.8 times
the mains voltage, due to transmission line eects in the
motor cable. If a motor has lower insulation rating, use a
dU/dt or sine-wave lter.
Nominal Mains VoltageMotor Insulation
UN ≤420 V
420 V<UN≤500 VReinforced ULL=1600 V
500 V<UN≤600 VReinforced ULL=1800 V
600 V<UN≤690 VReinforced ULL=2000 V
Table 6.8 Motor Insulation Ratings
Specications, the following motor
Standard ULL=1300 V
6.19 Installation of Misc. Connections
6.19.1 RS485 Bus Connection
1 or more frequency converters can be connected to a
control (or master) using the RS485 interface. Terminal 68
is connected to the P signal (TX+, RX+), while terminal 69
is connected to the N signal (TX-, RX-).
If more than 1 frequency converter is connected to a
master, use parallel connections.
6.19.2 How to Connect a PC to the
Frequency Converter
To control or program the frequency converter from a PC,
install the PC-based conguration tool MCT 10 Set-up
Software.
MCT 10 Set-up Software
MCT 10 Set-up Software has been designed as an easy-touse interactive tool for setting parameters in our frequency
converters.
The PC-based conguration tool MCT 10 Set-up Software is
useful for:
Planning a communication network o-line. MCT
•
10 Set-up Software contains a complete
frequency converter database.
Commissioning frequency converters online.
•
Saving settings for all frequency converters.
•
Replacing a frequency converter in a network.
•
Expanding an existing network.
•
Save frequency converter settings
1.Connect a PC to the unit via USB port.
2.Open the MCT 10 Set-up Software.
3.Select Read from drive.
4.Select Save as.
All parameters are now stored in the PC.
Save frequency converter settings
1.Connect a PC to the unit via USB port.
2.Open the MCT 10 Set-up Software.
3.Select Open, the software shows the stored les.
4.Open the appropriate le.
5.Select Write to drive.
All parameter settings are now transferred to the frequency
converter.
6
6
Illustration 6.19 RS485 Bus Connection
To avoid potential equalizing currents in the shield, ground
the cable shield via terminal 61, which is connected to the
enclosure via an RC-link.
Bus termination
Terminate the RS485 bus with resistors at both ends. For
this purpose, set switch S801 on the control card for ON.
Set the communication protocol to parameter 8-30 Protocol.
A separate manual for the MCT 10 Set-up Software is
available.
How to Install
VLT® Micro Drive FC 51
6
The MCT 10 Set-up Software modules
The following modules are included in the software
package:
MCT 10 Set-up Software
Setting parameters.
Copy to and from frequency converters.
Documentation and print out of parameter
settings including diagrams.
External user interface
Preventive maintenance schedule.
Clock settings.
Timed action programming.
Smart logic controller set-up.
Table 6.9 MCT 10 Set-up Software
Ordering number
Order the CD containing the MCT 10 Set-up Software
using code number 130B1000.
MCT 10 Set-up Software can also be downloaded from the
Danfoss Internet: www.danfoss.com/BusinessAreas/DrivesSo-lutions/Softwaredownload/DDPC+Software+Program.htm.
Safety
6.20
6.20.2 Safety Ground Connection
The frequency converter has a high leakage current and
must be grounded appropriately for safety reasons
according to EN 50178.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
Ensure the correct grounding of the equipment
•
by a certied electrical installer.
6.20.1 High-voltage Test
Carry out a high-voltage test by short-circuiting terminals
U, V, W, L1, L2, and L3. Energize maximum 2.15 kV DC for
380–500 V frequency converters and 2.525 kV DC for 525–
690 V frequency converters for 1 s between this short
circuit and the chassis.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
Refer to VLT® Motion Control Tools MCT 10 Set-up Software
Operating Instructions.
7.1.2 Programming with the LCP 11 or LCP
12
The LCP is divided into 4 functional groups:
1.Numeric display.
2.Menu key.
3.Navigation keys.
4.Operation keys and indicator lights.
The display
The display shows dierent information.
Set-up number shows the active set-up and the edit setup. If the same set-up acts as both active and edit set-up,
only that set-up number is shown (factory setting).
When active and edit set-up dier, the display shows both
numbers (set-up 12). The ashing number indicates the
edit set-up.
77
Illustration 7.3 Indicating Set-up
The small digits to the left are the selected parameter
number.
Illustration 7.1 LCP 12 with Potentiometer
Illustration 7.2 LCP 11 without Potentiometer
Illustration 7.4 Indicating Selected Parameter Number
The large digits in the middle of the display show the
value of the selected parameter.
Illustration 7.5 Indicating Value of Selected Parameter
The right side of the display shows the unit of the selected
parameter. This can be either Hz, A, V, kW, hp, %, s, or
RPM.
Illustration 7.6 Indicating Unit of Selected Parameter
Motor direction is shown to the bottom left of the display,
indicated by a small arrow pointing either clockwise or
counterclockwise.
77
Illustration 7.7 Indicating Motor Direction
Press [Menu] to select 1 of the following menus
Status Menu
The status menu is either in readout mode or hand-on
mode. In readout mode, the value of the currently selected
readout parameter is shown in the display.
In hand-on mode, the local LCP reference is displayed.
Quick Menu
Displays Quick Menu parameters and their settings.
Parameters in the Quick Menu can be accessed and edited
from here. Most applications can be run by setting the
parameters in Quick Menu.
Main Menu
Displays Main Menu parameters and their settings. All
parameters can be accessed and edited here.
Indicator lights
Green indicator light: The frequency converter is
•
on.
Yellow indicator light: Indicates a warning. See
•
chapter Troubleshooting in the VLT
51 Programming Guide.
Flashing red LED: Indicates an alarm. See chapter
•
Troubleshooting in VLT
Programming Guide.
Navigation keys
[Back]: For moving to the previous step or layer in the
navigation structure.
[▲] [▼]: For maneuvering between parameter groups,
parameters, and within parameters.
[OK]: For selecting a parameter and for accepting changes
to parameter settings.
®
Micro Drive FC 51
VLT® Micro Drive FC 51
®
Micro Drive FC
Pressing [OK] for more than 1 s enters the adjust mode. In
the adjust mode, it is possible to make fast adjustment by
pressing [▲] [▼] combined with [OK].
Press [▲] [▼] to change value. Press [OK] to shift between
digits quickly.
To exit the adjust mode, press [OK] more than 1 s again
with changes saving or press [Back] without changes
saving.
Operation keys
A yellow indicator light above the operation keys indicates
the active key.
[Hand On]: Starts the motor and enables control of the
frequency converter via the LCP.
[O/Reset]: The motor stops except in alarm mode. In
alarm mode, the motor is reset.
[Auto On]: The frequency converter is controlled either via
control terminals or serial communication.
[Potentiometer] (LCP 12): The potentiometer works in 2
ways depending on the mode in which the frequency
converter is running.
In auto mode, the potentiometer acts as an extra
programmable analog input.
In hand-on mode, the potentiometer controls local
reference.
Status Menu
7.2
After power-up, the Status Menu is active. Press [Menu] to
toggle between Status, Quick Menu, and Main Menu.
[▲] and [▼] toggle between the options in each menu.
The display indicates the status mode with a small arrow
above Status.
The Quick Menu gives easy access to the most frequently
used parameters.
1.To enter Quick Menu, press [Menu] key until
indicator in display is placed above Quick Menu.
2.
Press [▲] [▼] to select either QM1 or QM2, then
press [OK].
3.
Press [▲] [▼] to browse through the parameters in
the Quick Menu.
4.Press [OK] to select a parameter.
5.
Press [▲] [▼] to change the value of a parameter
setting.
6.Press [OK] to accept the change.
7.To exit, press either [Back] twice to enter Status,
or press [Menu] once to enter Main Menu.
Illustration 7.9 Indicating Quick Menu Mode
1-20 Motor Power [kW]/[hp] (P
m.n
)
Option:Function:
[14] 5.50 kW/7.50 hp
[15] 7.50 kW/10.0 hp
[16] 11.00 kW/15.00 hp
[17] 15.00 kW/20.00 hp
[18] 18.50 kW/25.00 hp
[19] 22.00 kW/29.50 hp
[20] 30.00 kW/40.00 hp
NOTICE
Changing this parameter aects parameters 1-22 Motor
Voltage to 1-25 Motor Nominal Speed, 1-30 Stator
Resistance (Rs), 1-33 Stator Leakage Reactance (X1), and
1-35 Main Reactance (Xh).
1-22 Motor Voltage (U_
Range:Function:
230/400 V [50–999 V] Enter motor voltage from nameplate
1-23 Motor Frequency (f_
Range:Function:
50 Hz* [20–400 Hz] Enter motor frequency from nameplate
data.
m.n
data.
m.n
)
)
77
7.4 Quick Menu Parameters
7.4.1 Quick Menu Parameters - Basic
Settings QM1
This section describes the parameters in Quick Menu.
*=Factory setting.
1-20 Motor Power [kW]/[hp] (P
Option:Function:
Enter motor power from nameplate
data.
Two sizes down, 1 size up from nominal
VLT rating.
[1]0.09 kW/0.12 hp
[2]0.12 kW/0.16 hp
[3]0.18kW/0.25 hp
[4]0.25 kW/0.33 hp
[5]0.37kW/0.50 hp
[6]0.55 kW/0.75 hp
[7]0.75 kW/1.00 hp
[8]1.10 kW/1.50 hp
[9]1.50 kW/2.00 hp
[10] 2.20 kW/3.00 hp
[11] 3.00 kW/4.00 hp
[12] 3.70 kW/5.00 hp
[13] 4.00 kW/5.40 hp
m.n
)
1-24 Motor Current (I_
m.n
)
Range:Function:
M-type dependent* [0.01–100.00 A] Enter motor current from
nameplate data.
1-25 Motor Nominal Speed (n_
m.n
)
Range:Function:
M-type Dependent* [100–9999
RPM]
Enter motor nominal
speed from nameplate
data.
1-29 Automatic Motor Tuning (AMT)
Option:Function:
Use AMT to optimize motor performance.
When parameter 1-01 Motor Control Principle is
set to [0] U/f, AMT does not work.
NOTICE
This parameter cannot be changed
while the motor is running.
[Main Menu] is used for programming all parameters. The
Main Menu parameters can be accessed immediately
unless a password has been created via
parameter 0-60 Main Menu Password. For most VLT® Micro
Drive applications it is not necessary to access the Main
Menu parameters, but instead the Quick Menu provides
the simplest and quickest access to the typical required
parameters.
The Main Menu accesses all parameters.
1.Press [Menu] key until indicator light in the
display is located above Main Menu.
2.
Use [▲] [▼] to browse through the parameter
groups.
3.Press [OK] to select a parameter group.
4.
Use [▲] [▼] to browse through the parameters in
the specic group.
5.Press [OK] to select the parameter.
6.
Use [▲] [▼] to set/change the parameter value.
Press [Back] to go back 1 level.
Data transfer from the LCP to the frequency converter
1.Go to parameter 0-50 LCP Copy.
2.Press [OK].
3.Select [2] All from LCP.
4.Press [OK].
7.7 Readout and Programming of Indexed
Parameters
Use chapter 7.4.2 Quick Menu Parameters - PI Basic SettingsQM2 as an example.
Press [OK] to select a parameter and use [▲]/[▼]
•
for selecting the indexed values.
To change a parameter value, select the value
•
and press [OK].
Change the value using [▲]/[▼].
•
Press [OK] to accept the new setting.
•
Pressing [OK] for more than 1 s activates the
•
adjust mode. In the adjust mode, it is possible to
make fast adjustment by pressing [▲]/[▼]
together with [OK].
Press [▲]/[▼] to change the value. Press [OK] to
•
shift between digits. To exit the adjust mode,
press [OK] for more than 1 s again to exit and
save changes, or press [Back] to exit without
saving changes.
RS485 is a 2-wire bus interface compatible with multi-drop
network topology, that is, nodes can be connected as a
bus, or via drop cables from a common trunk line. A total
of 32 nodes can be connected to 1 network segment.
Repeaters divide network segments.
NOTICE
Each repeater functions as a node within the segment in
which it is installed. Each node connected within a given
network must have a unique node address across all
segments.
Terminate each segment at both ends, using either the
termination switch (S801) of the frequency converters or a
biased termination resistor network. Always use shielded
twisted pair (STP) cable for bus cabling, and always follow
good common installation practice.
Low-impedance ground connection of the shield at every
node is important, including at high frequencies. Thus,
connect a large surface of the shield to ground, for
example with a cable clamp or a conductive cable gland. It
may be necessary to apply potential equalizing cables to
maintain the same ground potential throughout the
network, particularly in installations with long cables.
To prevent impedance mismatch, always use the same
type of cable throughout the entire network. When
connecting a motor to the frequency converter, always use
shielded motor cable.
NOTICE
To reduce noise between conductors, use shielded,
twisted-pair cables.
Illustration 8.1 Network Connection
8.1.3 Frequency Converter Hardware Set-up
To terminate the RS485 bus, use the terminator DIP switch
on the main control board of the frequency converter.
8.1.5 Frequency Converter Parameter
Settings for Modbus Communication
The following EMC precautions are recommended to
achieve interference-free operation of the RS485 network.
Observe relevant national and local regulations, for
example regarding protective ground connection. To avoid
coupling of high frequency noise from 1 cable to another,
keep the RS485 communication cable away from motor
and brake resistor cables. Keep the greatest possible
distance between the cables, especially where cables run
in parallel over long distances. The minimum distance is
200 mm (8 inches). When crossing is unavoidable, the
RS485 cable must cross motor cable and brake resistor
cables at an angle of 90°.
The following parameters apply to the RS485 interface (FCport):
ParameterFunction
Parameter 8-30 Prot
ocol
Parameter 8-31 Add
ress
Parameter 8-32 Bau
d Rate
Select the application protocol to run on the
RS485 interface.
Set the node address.
NOTICE
The address range depends on the
protocol selected in
parameter 8-30 Protocol.
Set the baud rate.
NOTICE
The baud rate depends on the
protocol selected in
parameter 8-30 Protocol.
88
Parameter 8-33 Pari
ty / Stop Bits
Set the parity and number of stop bits.
NOTICE
The selection depends on the protocol
selected in parameter 8-30 Protocol.
Illustration 8.3 EMC Precautions for RS485
Parameter 8-35 Min
imum Response
Delay
Parameter 8-36 Ma
ximum Response
Delay
Table 8.2 Parameters Related to RS485 Interface
FC Protocol Overview
8.2
Specify a minimum delay time between
receiving a request and transmitting a
response. This function is for overcoming
modem turnaround delays.
Specify a maximum delay time between
transmitting a request and receiving a
response.
8.2.1 Overview
The FC protocol, also referred to as FC eldbus, is the
Danfoss standard eldbus. It denes an access technique
according to the master/slave principle for communications
via a eldbus.
1 master and a maximum of 126 slaves can be connected
to the bus. The master selects the individual slaves via an
address character in the telegram. A slave itself can never
transmit without rst being requested to do so, and direct
message transfer between the individual slaves is not
possible. Communications occur in the half-duplex mode.
The master function cannot be transferred to another node
(single-master system).
The physical layer is RS485, thus utilizing the RS485 port
built into the frequency converter.
The FC protocol supports dierent telegram formats:
A short format of 8 bytes for process data.
•
A long format of 16 bytes that also includes a
•
parameter channel.
A format used for texts.
•
8.2.2 FC with Modbus RTU
The FC protocol provides access to the control word and
bus reference of the frequency converter.
The control word allows the Modbus master to control
several important functions of the frequency converter:
Start.
•
Stop of the frequency converter in various ways:
•
-Coast stop.
-Quick stop.
-DC brake stop.
-Normal (ramp) stop.
Reset after a fault trip.
•
Run at various preset speeds.
•
Run in reverse.
•
Change of the active set-up.
•
Control of the 2 relays built into the frequency
•
converter.
The bus reference is commonly used for speed control. It is
also possible to access the parameters, read their values,
and where possible, write values to them. Accessing the
parameters
controlling the setpoint of the frequency converter when
its internal PI controller is used.
oers a range of control options, including
Network Conguration
8.3
To enable the FC protocol for the frequency converter, set
the following parameters.
ParameterSetting
Parameter 8-30 ProtocolFC
Parameter 8-31 Address1–126
Parameter 8-32 Baud
Rate
Parameter 8-33 Parity /
Stop Bits
Table 8.3 Parameters to Enable the Protocol
2400–115200
Even parity, 1 stop bit (default)
8.4 FC Protocol Message Framing Structure
8.4.1 Content of a Character (byte)
Each character transferred begins with a start bit. Then 8
data bits are transferred, corresponding to a byte. Each
character is secured via a parity bit. This bit is set at 1
when it reaches parity. Parity is when there is an equal
number of 1 s in the 8 data bits and the parity bit in total.
A stop bit completes a character, thus consisting of 11 bits
in all.
Illustration 8.4 Content of a Character
8.4.2 Telegram Structure
Each telegram has the following structure:
Start character (STX)=02 hex.
•
A byte denoting the telegram length (LGE).
•
A byte denoting the frequency converter address
•
(ADR).
Several data bytes (variable, depending on the type of
telegram) follow.
The telegram length is the number of data bytes plus the
address byte ADR and the data control byte BCC.
The slave returns the address byte unchanged to the
master in the response telegram.
Bit 0–6 = 0 broadcast.
•
8.4.5 Data Control Byte (BCC)
4 data bytesLGE=4+1+1=6 bytes
12 data bytesLGE=12+1+1=14 bytes
Telegrams containing texts
Table 8.4 Length of Telegrams
1) The 10 is the
on the length of the text).
xed characters, while the n is variable (depending
101)+n bytes
The checksum is calculated as an XOR-function. Before the
rst byte in the telegram is received, the calculated
checksum is 0.
8.4.4 Frequency Converter Address (ADR)
Address format 1–126
Bit 7 = 1 (address format 1–126 active).
•
Bit 0–6 = frequency converter address 1–126.
•
8.4.6 The Data Field
88
The structure of data blocks depends on the type of telegram. There are 3 telegram types, and the type applies for both
control telegrams (master⇒slave) and response telegrams (slave⇒master).
The 3 types of telegram are:
Process block (PCD).
•
Parameter block.
•
Text block.
•
Process block (PCD)
The PCD is made up of a data block of 4 bytes (2 words) and contains:
Control word and reference value (from master to slave).
•
Status word and present output frequency (from slave to master).
•
Illustration 8.6 Process Block
Parameter block
The parameter block is used to transfer parameters between master and slave. The data block is made up of 12 bytes (6
words) and also contains the process block.
Bits 0–11 transfer parameter numbers. The function of the
relevant parameter is dened in the parameter description
in the VLT® Micro Drive FC 51 Programming Guide.
8.4.9 Index (IND)
The index is used with the parameter number to read/
write access parameters with an index, for example,
parameter 15-30 Alarm Log: Error Code. The index consists
of 2 bytes; a low byte, and a high byte.
Only the low byte is used as an index.
8.4.10 Parameter Value (PWE)
The parameter value block consists of 2 words (4 bytes),
and the value depends on the dened command (AK). The
master prompts for a parameter value when the PWE block
88
contains no value. To change a parameter value (write),
write the new value in the PWE block and send from the
master to the slave.
When a slave responds to a parameter request (read
command), the present parameter value in the PWE block
is transferred and returned to the master. If a parameter
contains several data options, for example
parameter 0-01 Language, select the data value by entering
the value in the PWE block. Serial communication is only
capable of reading parameters containing data type 9 (text
string).
Parameter 15-40 FC Type to parameter 15-53 Power Card
Serial Number contain data type 9.
For example, read the unit size and mains voltage range in
parameter 15-40 FC Type. When a text string is transferred
(read), the length of the telegram is variable, and the texts
are of dierent lengths. The telegram length is dened in
the 2nd byte of the telegram (LGE). When using text
transfer, the index character indicates whether it is a read
or a write command.
Unsigned means that there is no operational sign in the
telegram.
Data typesDescription
3Integer 16
4Integer 32
5Unsigned 8
6Unsigned 16
7Unsigned 32
9Text string
Table 8.8 Data Types
8.4.12 Conversion
The programming guide contains the descriptions of
attributes of each parameter. Parameter values are
transferred as whole numbers only. Conversion factors are
used to transfer decimals.
Parameter 4-12 Motor Speed Low Limit [Hz] has a conversion
factor of 0.1. To preset the minimum frequency to 10 Hz,
transfer the value 100. A conversion factor of 0.1 means
that the value transferred is multiplied by 0.1. The value
100 is thus perceived as 10.0.
Conversion indexConversion factor
743600
2100
110
01
-10.1
-20.01
-30.001
-40.0001
-50.00001
Table 8.9 Conversion
8.4.13 Process Words (PCD)
To read a text via the PWE block, set the parameter
command (AK) to F hex. The index character high-byte
must be 4.
The block of process words is divided into 2 blocks of 16
bits, which always occur in the dened sequence.
Change parameter 4-14 Motor Speed High Limit [Hz] to 100
Hz.
Write the data in EEPROM.
PKE = E19E hex - Write single word in
parameter 4-14 Motor Speed High Limit [Hz]:
IND = 0000 hex.
•
PWEHIGH = 0000 hex.
•
PWELOW = 03E8 hex.
•
Data value 1000, corresponding to 100 Hz, see
chapter 8.4.12 Conversion.
The telegram looks like Illustration 8.10.
Illustration 8.10 Telegram
NOTICE
Parameter 4-14 Motor Speed High Limit [Hz] is a single
word, and the parameter command for write in EEPROM
is E. Parameter 4-14 Motor Speed High Limit [Hz] is 19E in
hexadecimal.
Illustration 8.12 Telegram
If the value in parameter 3-41 Ramp 1 Ramp Up Time is 10
s, the response from the slave to the master is shown in
Illustration 8.13.
Illustration 8.13 Response
3E8 hex corresponds to 1000 decimal. The conversion
index for parameter 3-41 Ramp 1 Ramp Up Time is -2, that
is, 0.01.
Parameter 3-41 Ramp 1 Ramp Up Time is of the type
Unsigned 32.
Modbus RTU Overview
8.6
8.6.1 Prerequisite Knowledge
Danfoss assumes that the installed controller supports the
interfaces in this manual, and strictly observes all
requirements and limitations stipulated in the controller
and frequency converter.
88
The response from the slave to the master is shown in
Illustration 8.11.
Illustration 8.11 Response from Master
8.5.2 Reading a Parameter Value
Read the value in parameter 3-41 Ramp 1 Ramp Up Time.
PKE = 1155 hex - Read parameter value in
parameter 3-41 Ramp 1 Ramp Up Time:
IND = 0000 hex.
•
PWE
•
PWE
•
= 0000 hex.
HIGH
= 0000 hex.
LOW
The built-in Modbus RTU (remote terminal unit) is
designed to communicate with any controller that
supports the interfaces dened in this manual. It is
assumed that the user has full knowledge of the
capabilities and limitations of the controller.
8.6.2 What the User Should Already Know
The built-in Modbus RTU is designed to communicate with
any controller that supports the interfaces dened in this
manual. It is assumed that the user has full knowledge of
the capabilities and limitations of the controller.
8.6.3 Overview
Regardless of the type of physical communication
networks, this section describes the process a controller
uses to request access to another device. This process
includes how the Modbus RTU responds to requests from
another device, and how errors are detected and reported.
It also establishes a common format for the layout and
contents of telegram elds.
During communications over a Modbus RTU network, the
protocol:
Determines how each controller learns its device
•
address.
Recognizes a telegram addressed to it.
•
Determines which actions to take.
•
Extracts any data or other information contained
•
in the telegram.
If a reply is required, the controller constructs the reply
telegram and sends it.
Controllers communicate using a master/slave technique in
which only the master can initiate transactions (called
queries). Slaves respond by supplying the requested data
to the master, or by acting as requested in the query.
The master can address individual slaves, or initiate a
broadcast telegram to all slaves. Slaves return a response
to queries that are addressed to them individually. No
responses are returned to broadcast queries from the
master.
88
The Modbus RTU protocol establishes the format for the
master query by providing the following information:
The device (or broadcast) address.
•
A function code dening the requested action.
•
Any data to be sent.
•
An error-checking eld.
•
The response telegram of the slave device is also
constructed using Modbus protocol. It contains eldsconrming the action taken, any data to be returned, and
an error-checking eld. If an error occurs in receipt of the
telegram, or if the slave is unable to perform the requested
action, the slave constructs and sends an error message.
Alternatively, a timeout occurs.
8.6.4 Frequency Converter with Modbus
RTU
The bus reference is commonly used for speed control. It is
also possible to access the parameters, read their values,
and, where possible, write values to them. Accessing the
parameters oers a range of control options, including
controlling the setpoint of the frequency converter when
its internal PI controller is used.
8.7 Network Conguration
To enable Modbus RTU on the frequency converter, set the
following parameters:
ParameterSetting
Parameter 8-30 ProtocolModbus RTU
Parameter 8-31 Address1–247
Parameter 8-32 Baud Rate2400–115200
Parameter 8-33 Parity / Stop BitsEven parity, 1 stop bit
Table 8.11 Network Conguration
8.8
8.8.1 Introduction
The controllers are set up to communicate on the Modbus
network using RTU (remote terminal unit) mode, with each
byte in a telegram containing 2 4-bit hexadecimal
characters. The format for each byte is shown in Table 8.12.
Start
bit
Run at various preset speeds.
•
Run in reverse.
•
Change the active set-up.
•
Control built-in relay of the frequency converter.
•
(default)
Modbus RTU Message Framing
Structure
Data byteStop/
Stop
parity
The frequency converter communicates in Modbus RTU
format over the built-in RS485 interface. Modbus RTU
provides access to the control word and bus reference of
the frequency converter.
The control word allows the Modbus master to control
several important functions of the frequency converter:
The transmitting device places a Modbus RTU telegram
into a frame with a known beginning and ending point.
This allows receiving devices to begin at the start of the
telegram, read the address portion, determine which
device is addressed (or all devices, if the telegram is
broadcast), and to recognize when the telegram is
completed. Partial telegrams are detected and errors set as
a result. Characters for transmission must be in
hexadecimal 00–FF format in each eld. The frequency
converter continuously monitors the network bus, also
during silent intervals. When the rsteld (the address
eld) is received, each frequency converter or device
decodes it to determine which device is being addressed.
Modbus RTU telegrams addressed to 0 are broadcast
telegrams. No response is permitted for broadcast
telegrams. A typical telegram frame is shown in Table 8.14.
StartAddress FunctionDataCRC
check
T1-T2-T3-T48 bits8 bitsN x 8 bits16 bitsT1-T2-T3-
Table 8.14 Typical Modbus RTU Telegram Structure
End
T4
When the slave sends its response, it places its own
address in this address eld to let the master know which
slave is responding.
8.8.5 Function Field
The function eld of a message frame contains 8 bits. Valid
codes are in the range of 1-FF. Function elds are used to
send messages between master and follower. When a
message is sent from a master to a follower device, the
function code eld tells the follower what kind of action to
perform. When the follower responds to the master, it uses
the function code eld to indicate either a normal (errorfree) response, or that some kind of error occurred (called
an exception response). For a normal response, the
follower simply echoes the original function code. For an
exception response, the follower returns a code that is
equivalent to the original function code with its most
signicant bit set to logic 1. In addition, the follower places
a unique code into the data eld of the response message.
This tells the master what kind of error occurred, or the
reason for the exception. Also refer to
chapter 8.8.10 Function Codes Supported by Modbus RTU and
chapter 8.8.11 Modbus Exception Codes.
88
8.8.3 Start/Stop Field
Telegrams start with a silent period of at least 3.5 character
intervals. The silent period is implemented as a multiple of
character intervals at the selected network baud rate
(shown as Start T1-T2-T3-T4). The rsteld to be
transmitted is the device address. Following the last
transmitted character, a similar period of at least 3.5
character intervals marks the end of the telegram. A new
telegram can begin after this period.
Transmit the entire telegram frame as a continuous stream.
If a silent period of more than 1.5 character intervals
occurs before completion of the frame, the receiving
device ushes the incomplete telegram and assumes that
the next byte is the address eld of a new telegram.
Similarly, if a new telegram begins before 3.5 character
intervals after a previous telegram, the receiving device
considers it a continuation of the previous telegram. This
behavior causes a timeout (no response from the slave),
since the value in the nal CRC eld is not valid for the
combined telegrams.
8.8.4 Address Field
The address eld of a telegram frame contains 8 bits. Valid
slave device addresses are in the range of 0–247 decimal.
The individual slave devices are assigned addresses in the
range of 1–247. (0 is reserved for broadcast mode, which
all slaves recognize.) A master addresses a slave by placing
the slave address in the address eld of the telegram.
8.8.6 Data Field
The data eld is constructed using sets of 2 hexadecimal
digits, in the range of 00–FF hexadecimal. These digits are
made up of 1 RTU character. The data eld of telegrams
sent from a master to a slave device contains additional
information which the slave must use to perform
accordingly.
The information can include items such as:
Coil or register addresses.
•
The quantity of items to be handled.
•
The count of actual data bytes in the eld.
•
8.8.7 CRC Check Field
Telegrams include an error-checking eld, operating based
on a cyclic redundancy check (CRC) method. The CRC eld
checks the contents of the entire telegram. It is applied
regardless of any parity check method used for the
individual characters of the telegram. The transmitting
device calculates the CRC value and appends the CRC as
the last eld in the telegram. The receiving device
recalculates a CRC during receipt of the telegram and
compares the calculated value to the actual value received
in the CRC eld. 2 unequal values result in bus timeout.
The error-checking eld contains a 16-bit binary value
implemented as 2 8-bit bytes. After the implementation,
the low-order byte of the eld is appended rst, followed
by the high-order byte. The CRC high-order byte is the last
byte sent in the telegram.
In Modbus, all data is organized in coils and holding
registers. Coils hold a single bit, whereas holding registers
hold a 2 byte word (that is 16 bits). All data addresses in
Modbus telegrams are referenced to 0. The rst occurrence
of a data item is addressed as item number 0. For example:
The coil known as coil 1 in a programmable controller is
addressed as coil 0000 in the data address eld of a
Modbus telegram. Coil 127 decimal is addressed as coil
007Ehex (126 decimal).
Holding register 40001 is addressed as register 0000 in the
data address eld of the telegram. The function code eld
already species a holding register operation. Therefore,
the 4XXXX reference is implicit. Holding register 40108 is
addressed as register 006Bhex (107 decimal).
Coil
number
1–16Frequency converter control word
88
17–32Frequency converter speed or
33–48Frequency converter status word
49–64Open-loop mode: Frequency
65
66–65536 Reserved.–
Table 8.15 Coil Register
DescriptionSignal
direction
Master to slave
(see Table 8.16).
Master to slave
setpoint reference range 0x0–
0xFFFF (-200% ... ~200%).
Slave to master
(see Table 8.17).
converter output frequency.
Closed-loop mode: Frequency
converter feedback signal.
Parameter write control (master to
slave).
0 = Parameter changes are written
to the RAM of the frequency
converter.
1 = Parameter changes are written
to the RAM and EEPROM of the
frequency converter.
Slave to master
Master to slave
Coil01
01Preset reference lsb
02Preset reference msb
03DC brakeNo DC brake
04Coast stopNo coast stop
05Quick stopNo quick stop
06Freeze frequencyNo freeze frequency
07Ramp stopStart
08No resetReset
09No jogJog
10Ramp 1Ramp 2
11Data not validData valid
12Relay 1 oRelay 1 on
13Relay 2 oRelay 2 on
14Set up lsb
15–
16No reversingReversing
Table 8.16 Frequency Converter Control Word (FC Prole)
Coil01
33Control not readyControl ready
34Frequency converter not
ready
35Coast stopSafety closed
36No alarmAlarm
37Not usedNot used
38Not usedNot used
39Not usedNot used
40No warningWarning
41Not at referenceAt reference
42Hand modeAuto mode
43Out of frequency rangeIn frequency range
44StoppedRunning
45Not usedNot used
46No voltage warningVoltage warning
47Not in current limitCurrent limit
48No thermal warningThermal warning
Table 8.17 Frequency Converter Status Word (FC Prole)
The PNU (parameter number) is translated from the
register address contained in the Modbus read or write
message. The parameter number is translated to Modbus
as (10 x parameter number) decimal. Example: Reading
parameter 3-12 Catch up/slow Down Value (16 bit): The
holding register 3120 holds the parameters value. A value
8.8.11 Modbus Exception Codes
For a full explanation of the structure of an exception code
response, refer to chapter 8.8.5 Function Field.
88
Code NameMeaning
1Illegal
function
2Illegal data
address
3Illegal data
value
The function code received in the query is
not an allowable action for the server (or
slave). This may be because the function
code is only applicable to newer devices
and was not implemented in the unit
selected. It could also indicate that the
server (or slave) is in the wrong state to
process a request of this type, for example
because it is not congured and is being
asked to return register values.
The data address received in the query is
not an allowable address for the server (or
slave). More specically, the combination
of reference number and transfer length is
invalid. For a controller with 100 registers,
a request with oset 96 and length 4
succeeds, while a request with oset 96
and length 5 generates exception 02.
A value contained in the query data eld
is not an allowable value for server (or
slave). This indicates a fault in the
structure of the remainder of a complex
request, such as that the implied length is
incorrect. It does NOT mean that a data
item submitted for storage in a register
has a value outside the expectation of the
application program, since the Modbus
protocol is unaware of the signicance of
any value of any register.
of 1352 (decimal), means that the parameter is set to
12.52%
Reading parameter 3-14 Preset Relative Reference (32 bit):
The holding registers 3410 and 3411 hold the parameters
values. A value of 11300 (decimal), means that the
parameter is set to 1113.00.
For information on the parameters, size, and conversion
index, see chapter 7 Programming.
8.9.2 Storage of Data
The coil 65 decimal determines whether data written to
the frequency converter is stored in EEPROM and RAM (coil
65=1), or only in RAM (coil 65=0).
8.9.3 IND (Index)
Some parameters in the frequency converter are array
parameters, for example parameter 3-10 Preset Reference.
Since the Modbus does not support arrays in the holding
registers, the frequency converter has reserved the holding
register 9 as pointer to the array. Before reading or writing
an array parameter, set the holding register 9. Setting
holding register to the value of 2 causes all following read/
write to array parameters to be to the index 2.
8.9.4 Text Blocks
Parameters stored as text strings are accessed in the same
way as the other parameters. The maximum text block size
is 20 characters. If a read request for a parameter is for
more characters than the parameter stores, the response is
truncated. If the read request for a parameter is for fewer
characters than the parameter stores, the response is space
The dierent attributes for each parameter can be seen in
the section on factory settings. Since a parameter value
can only be transferred as a whole number, a conversion
factor must be used to transfer decimals. Refer to the
chapter 7.4 Quick Menu Parameters.
8.9.6 Parameter Values
Standard data types
Standard data types are int 16, int 32, uint 8, uint 16, and
uint 32. They are stored as 4x registers (40001–4FFFF). The
parameters are read using function 03 hex read holding
registers. Parameters are written using the function 6 hex
preset single register for 1 register (16 bits), and the
function 10 hex preset multiple registers for 2 registers (32
bits). Readable sizes range from 1 register (16 bits) up to
10 registers (20 characters).
Non-standard data types
Non-standard data types are text strings and are stored as
4x registers (40001–4FFFF). The parameters are read using
function 03 hex read holding registers and written using
function 10 hex preset multiple registers. Readable sizes
range from 1 register (2 characters) up to 10 registers (20
characters).
Examples
8.10
The following examples show various Modbus RTU
commands. If an error occurs, refer to
chapter 8.8.11 Modbus Exception Codes.
Field nameExample (hex)
Slave address01 (frequency converter address)
Function01 (read coils)
Starting address HI00
Starting address LO20 (32 decimals) coil 33
Number of points HI00
Number of points LO10 (16 decimals)
Error check (CRC)–
Table 8.22 Query
Response
The coil status in the response telegram is packed as 1 coil
per bit of the data
0=OFF. The lsb of the rst data byte contains the coil
addressed in the query. The other coils follow toward the
high-order end of this byte, and from low order to high
order in subsequent bytes.
If the returned coil quantity is not a multiple of 8, the
remaining bits in the nal data byte are padded with
values 0 (toward the high-order end of the byte). The byte
count eldspecies the number of complete bytes of data.
Field nameExample (hex)
Slave address01 (frequency converter address)
Function01 (read coils)
Byte count02 (2 bytes of data)
Data (coils 40–33)07
Data (coils 48–41)06 (STW=0607hex)
Error check (CRC)–
Table 8.23 Response
eld. Status is indicated as: 1=ON;
88
8.10.1 Read Coil Status (01 hex)
Description
This function reads the ON/OFF status of discrete outputs
(coils) in the frequency converter. Broadcast is never
supported for reads.
Query
The query telegram species the starting coil and quantity
of coils to be read. Coil addresses start at 0, that is, coil 33
is addressed as 32.
Example of a request to read coils 33–48 (status word)
from slave device 01.
NOTICE
Coils and registers are addressed explicitly with an oset of -1 in Modbus.
For example, coil 33 is addressed as coil 32.
8.10.2 Force/Write Single Coil (05 hex)
Description
This function forces the coil to either ON or OFF. When
broadcast, the function forces the same coil references in
all attached slaves.
Query
The query telegram species the coil 65 (parameter write
control) to be forced. Coil addresses start at 0, that is, coil
65 is addressed as 64. Force data = 00 00 hex (OFF) or FF
00 hex (ON).
The normal response returns the slave address, function
code, starting address, and quantity of coils forced.
Field nameExample (hex)
Slave address01 (frequency converter address)
Function0F (write multiple coils)
Coil address HI00
Coil address LO10 (coil address 17)
Quantity of coils HI00
Quantity of coils LO10 (16 coils)
Error check (CRC)–
The normal response is an echo of the query, returned
after the coil state has been forced.
Field nameExample (hex)
Slave address01
Function05
Force data HIFF
Force data LO00
Quantity of coils HI00
88
Quantity of coils LO01
Error check (CRC)–
Table 8.25 Response
Table 8.27 Response
8.10.4 Read Holding Registers (03 hex)
Description
This function reads the contents of holding registers in the
slave.
Query
The query telegram species the starting register and
quantity of registers to be read. Register addresses start at
0, that is, registers 1–4 are addressed as 0–3.
Example: Read parameter 3-03 Maximum Reference, register
8.10.3 Force/Write Multiple Coils (0F hex)
03030.
Description
This function forces each coil in a sequence of coils to
either on or o. When broadcasting, the function forces
the same coil references in all attached slaves.
Query
The query telegram species the coils 17–32 (speed
setpoint) to be forced.
NOTICE
Coil addresses start at 0, that is, coil 17 is addressed as
16.
Field nameExample (hex)
Slave address01 (frequency converter address)
Function0F (write multiple coils)
Coil address HI00
Coil address LO10 (coil address 17)
Quantity of coils HI00
Quantity of coils LO10 (16 coils)
Byte count02
Force data HI
(Coils 8–1)
Force data LO
(Coils 16–9)
Error check (CRC)–
20
00 (reference=2000 hex)
Field nameExample (hex)
Slave address01
Function03 (Read holding registers)
Starting address HI0B (Register address 3029)
Starting address LOD5 (Register address 3029)
Number of points HI00
Number of points LO02 – (parameter 3-03 Maximum
Reference is 32 bits long, that is, 2
registers)
Error check (CRC)–
Table 8.28 Query
Response
The register data in the response telegram is packed as 2
bytes per register, with the binary contents right justied
within each byte. For each register, the 1st byte contains
the high-order bits, and the 2nd contains the low-order
bits.
This function presets a value into a single holding register.
Query
The query telegram species the register reference to be
preset. Register addresses start at 0, that is, register 1 is
addressed as 0.
Example: Write to parameter 1-00 Conguration Mode,
register 1000.
Field nameExample (hex)
Slave address01
Function06
Register address HI03 (register address 999)
Register address LOE7 (register address 999)
Preset data HI00
Preset data LO01
Error check (CRC)–
Table 8.30 Query
Response
The normal response is an echo of the query, returned
after the register contents have been passed.
Field nameExample (hex)
Slave address01
Function06
Register address HI03
Register address LOE7
Preset data HI00
Preset data LO01
Error check (CRC)–
8.10.6 Preset Multiple Registers (10 hex)
Description
This function presets values into a sequence of holding
registers.
Query
The query telegram species the register references to be
preset. Register addresses start at 0, that is, register 1 is
addressed as 0. Example of a request to preset 2 registers
(set parameter 1-24 Motor Current to 738 (7.38 A)):
Field nameExample (hex)
Slave address01
Function10
Starting address HI04
Starting address LO07
Number of registers HI00
Number of registers LO02
Byte count04
Write data HI (Register 4: 1049)00
Write data LO (Register 4: 1049)00
Write data HI (Register 4: 1050)02
Write data LO (Register 4: 1050)E2
Error check (CRC)–
Table 8.32 Query
Response
The normal response returns the slave address, function
code, starting address, and quantity of registers preset.
Set parameter 8-30 Protocol to [0] FC.
Modbus Holding Register numbers for Input data – CTW
and REF – and Output data – STW and MAV – are
in Table 8.34:
50000 input data Frequency converter control word register
(CTW)
50010 input data Bus reference register (REF)
50200 output data Frequency converter status word register
(STW)
50210 output data Frequency converter main value register
(MAV)
Table 8.34 Modbus Holding Register Numbers for Input and
Output Data
88
In VLT® Micro Drive FC 51 after software version 2.32, the
input/output data is also available in a lower holding
register area:
dened
BitBit value=0Bit value=1
00Reference valueExternal selection lsb
01Reference valueExternal selection msb
02DC brakeRamp
03CoastingNo coasting
04Quick stopRamp
05Hold output
frequency
06Ramp stopStart
07No functionReset
08No functionJog
09Ramp 1Ramp 2
10Data invalidData valid
11Relay 01 openRelay 01 active
12Relay 02 openRelay 02 active
13Parameter set-upSelection lsb
15No functionReverse
Table 8.36 Denition of Control Bits
Use ramp
Explanation of the control bits
Bits 00/01
Bits 00 and 01 are used to select between the 4 reference
values, which are pre-programmed in parameter 3-10 PresetReference according to the Table 8.37.
02810 input data Frequency converter control word register
(CTW)
02811 input data Bus reference register (REF)
02910 output data Frequency converter status word register
(STW)
02911 output data Frequency converter main value register
(MAV)
Table 8.35 Lower Register Numbers for Input and Output Data
Make a selection in parameter 8-56 Preset Reference Select
to dene how bit 00/01 gates with the corresponding
function on the digital inputs.
Bit 02, DC brake
Bit 02=0 leads to DC brake and stop. Set braking current
and duration in parameter 2-01 DC Brake Current andparameter 2-02 DC Braking Time.
Bit 02=1 leads to ramping.
Bit 03, Coasting
Bit 03=0: The frequency converter immediately releases the
motor, (the output transistors are shut o) and the motor
coasts to a standstill.
Bit 03=1: The frequency converter starts the motor if the
other starting conditions are met.
Make a selection in parameter 8-50 Coasting Select to
dene how bit 03 gates with the corresponding function
on a digital input.
Output freq.STW
Bit
no.:
Follower-master
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BA273.11
RS485 Installation and Set-...Design Guide
Bit 04, Quick stop
Bit 04=0: Makes the motor speed ramp down to stop (set
in parameter 3-81 Quick Stop Ramp Time).
Bit 05, Hold output frequency
Bit 05=0: The present output frequency (in Hz) freezes.
Change the frozen output frequency only with the digital
inputs (parameter 5-10 Terminal 18 Digital Input to
parameter 5-13 Terminal 29 Digital Input) programmed to
[21] Speed up and [22] Slow down.
NOTICE
If freeze output is active, the frequency converter can
only be stopped by the following:
Bit 03 coast stop
•
Bit 02 DC brake
•
Digital input (parameter 5-10 Terminal 18 Digital
•
Input to parameter 5-13 Terminal 29 Digital
Input) programmed to [5] DC-brake inverse, [2]
Coast inverse, or [3] Coast and reset inverse.
Bit 06, Ramp stop/start
Bit 06=0: Causes a stop and makes the motor speed ramp
down to stop via the selected ramp down parameter.
Bit 06=1: Allows the frequency converter to start the motor
if the other starting conditions are met.
Make a selection in parameter 8-53 Start Select to dene
how bit 06 Ramp stop/start communicates with the
corresponding function on a digital input.
Bit 07, Reset
Bit 07=0: No reset.
Bit 07=1: Resets a trip. Reset is activated on the signal’s
leading edge, that is, when changing from logic 0 to logic
1.
Bit 08, Jog
Bit 08=1: The output frequency is determined by
parameter 3-11 Jog Speed [Hz].
Bit 09, Selection of ramp 1/2
Bit 09=0: Ramp 1 is active (parameter 3-41 Ramp 1 Ramp
Up Time to parameter 3-42 Ramp 1 Ramp Down Time).
Bit 09=1: Ramp 2 (parameter 3-51 Ramp 2 Ramp Up Time to
parameter 3-52 Ramp 2 Ramp Down Time) is active.
Bit 10, Data not valid/Data valid
Tell the frequency converter whether to use or ignore the
control word.
Bit 10=0: The control word is ignored.
Bit 10=1: The control word is used.
This function is relevant because the telegram always
contains the control word, regardless of the telegram type.
Turn o the control word if not wanting to use it when
updating or reading parameters.
Bit 11, Relay 01
Bit 11=0: Relay not activated.
Bit 11=1: Relay 01 activated if [36] Control word bit 11 is
selected in parameter 5-40 Function Relay.
Bit 12, Relay 02
Bit 12=0: Relay 02 is not activated.
Bit 12=1: Relay 02 is activated if [37] Control word bit 12 is
selected in parameter 5-40 Function Relay.
Bit 13, Selection of set-up
Use bit 13 to select from the 2 menu set-ups according to
Table 8.38.
Set-upBit 13
10
21
Table 8.38 Set-up Selection
The function is only possible when [9] Multi Set-up is
selected in parameter 0-10 Active Set-up.
Make a selection in parameter 8-55 Set-up Select to dene
how bit 13 communicates with the corresponding function
on the digital inputs.
Bit 15 Reverse
Bit 15=0: No reversing.
Bit 15=1: Reversing. In the default setting, reversing is set
to digital in parameter 8-54 Reversing Select. Bit 15 causes
reversing only when 1 of the following options is selected:
[1] Bus, [2] Logic AND, [3] Logic OR.
Bit 00=0: The frequency converter trips.
Bit 00=1: The frequency converter controls are ready but
the power component does not necessarily receive any
supply (if there is 24 V external supply to controls).
Bit 08, Speed reference/speed=reference
Bit 08=0: The motor runs, but the present speed is
dierent from the preset speed reference. It might happen
when the speed ramps up/down during start/stop.
Bit 08=1: The motor speed matches the preset speed
reference.
Bit 09, Local operation/bus control
Bit 09=0: [O/Reset] is activated on the control unit or [2]
Local in parameter 3-13 Reference Site is selected. It is not
possible to control the frequency converter via serial
communication.
Bit 09=1: It is possible to control the frequency converter
via the eldbus/serial communication.
Bit 10, Out of frequency limit
Bit 10=0: The output frequency has reached the value in
parameter 4-12 Motor Speed Low Limit [Hz] or
parameter 4-14 Motor Speed High Limit [Hz].
Bit 10=1: The output frequency is within the dened limits.
Bit 11, No operation/in operation
Bit 11=0: The motor is not running.
Bit 11=1: The frequency converter has a start signal
without coast.
Bit 12, Frequency converter OK/stopped, auto start
Bit 12=0: There is no temporary overtemperature on the
frequency converter.
Bit 12=1: The frequency converter stops because of
overtemperature but the unit does not trip and resumes
operation once the overtemperature normalizes.
Bit 01, Frequency converter ready
Bit 01=0: The frequency converter is not ready.
Bit 13, Voltage OK/limit exceeded
Bit 13=0: There are no voltage warnings.
Bit 01=1: The frequency converter is ready for operation,
but the coasting command is active via the digital inputs
Bit 13=1: The DC voltage in the frequency converter’s DC
link is too low or too high.
or via serial communication.
Bit 14, Torque OK/limit exceeded
Bit 02, Coast stop
Bit 02=0: The frequency converter releases the motor.
Bit 02=1: The frequency converter starts the motor with a
start command.
Bit 03, No error/trip
Bit 03=0: The frequency converter is not in fault mode.
Bit 03=1: The frequency converter trips. To re-establish
operation, press [Reset].
Bit 14=0: The motor current is lower than the current limit
selected in parameter 4-18 Current Limit.
Bit 14=1: The current limit in parameter 4-18 Current Limit is
exceeded.
Bit 15, Timer OK/limit exceeded
Bit 15=0: The timers for motor thermal protection and
thermal protection are not exceeded 100%.
Bit 15=1: 1 of the timers exceeds 100%.
Bit 04, No error/error (no trip)
Bit 04=0: The frequency converter is not in fault mode.
Bit 04=1: The frequency converter shows an error but does
not trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06=0: The frequency converter is not in fault mode.
Bit 06=1: The frequency converter is tripped and locked.
Bit 07, No warning/warning
Bit 07=0: There are no warnings.
Bit 07=1: A warning has occurred.
Speed reference value is transmitted to the frequency
converter in a relative value in %. The value is transmitted
in the form of a 16-bit word. The integer value 16384
(4000 hex) corresponds to 100%. Negative gures are
formatted using 2’s complement. The actual output
frequency (MAV) is scaled in the same way as the bus
reference.
Electronic motor thermal protection against overload.
•
Temperature monitoring of the heat sink ensures that the frequency converter trips if there is overtemperature.
•
The frequency converter is protected against short circuits between motor terminals U, V, W.
•
When a motor phase is missing, the frequency converter trips and issues an alarm.
•
When a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
•
Monitoring of the DC-link voltage ensures that the frequency converter trips when the DC-link voltage is too low
•
or too high.
The frequency converter is protected against ground faults on motor terminals U, V, W.
•
Mains supply (L1/L, L2, L3/N)
Supply voltage200–240 V ±10%
Supply voltage380–480 V ±10%
Supply frequency50/60 Hz
Maximum imbalance temporary between mains phases3.0% of rated supply voltage
True power factor≥0.4 nominal at rated load
Displacement power factor (cosφ) near unity(>0.98)
Switching on input supply L1/L, L2, L3/N (power-ups)Maximum 2 times/minute
Environment according to EN60664-1Overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes, 240/480 V
maximum.
99
Motor output (U, V, W)
Output voltage0–100% of supply voltage
Output frequency0–200 Hz (VVC+), 0–400 Hz (u/f )
Switching on outputUnlimited
Ramp times0.05–3600 s
VLT® Micro Drive FC 51
Cable length and cross-section
Maximum motor cable length, shielded/armored (EMC-correct installation)15 m (49 ft)
Maximum motor cable length, unshielded/unarmored50 m (164 ft)
Maximum cross-section to motor, mains
Connection to load sharing/brake (M1, M2, M3)6.3 mm insulated Faston plugs
Maximum cross-section to load sharing/brake (M4, M5)16 mm2/6 AWG
Maximum cross-section to control terminals, rigid wire1.5 mm2/16 AWG (2x0.75 mm2)
Maximum cross-section to control terminals, exible cable1 mm2/18 AWG
Maximum cross-section to control terminals, cable with enclosed core0.5 mm2/20 AWG
Minimum cross-section to control terminals0.25 mm2 (24 AWG)
1) See chapter 9 Specications for more information.
Digital inputs (pulse/encoder inputs)
Programmable digital inputs (pulse/encoder)5 (1)
Terminal number18, 19, 27, 29, 33
LogicPNP or NPN
Voltage level0–24 V DC
Voltage level, logic 0 PNP<5 V DC
Voltage level, logic 1 PNP>10 V DC
Voltage level, logic 0 NPN>19 V DC
Voltage level, logic 1 NPN<14 V DC
Maximum voltage on input28 V DC
Input resistance, R
Maximum pulse frequency at terminal 335000 Hz
Minimum pulse frequency at terminal 3320 Hz
Analog inputs
Number of analog inputs2
Terminal number53, 60
Voltage mode (terminal 53)Switch S200=OFF(U)
Current mode (terminal 53 and 60)Switch S200=ON(I)
Voltage level0–10 V
Input resistance, R
Maximum voltage20 V
Current level0/4 to 20 mA (scaleable)
Input resistance, R
Maximum current30 mA
Analog output
Number of programmable analog outputs1
Terminal number42
Current range at analog output0/4–20 mA
Maximum load to common at analog output500 Ω
Maximum voltage at analog output17 V
Accuracy on analog outputMaximum error: 0.8% of full scale
Scan interval4 ms
Resolution on analog output8 bit
Scan interval4 ms
i
i
Approximately 10000 Ω
Approximately 200 Ω
Control card, RS485 serial communication
Terminal number68 (P, TX+, RX+), 69 (N, TX-, RX-)
Terminal number 61Common for terminals 68 and 69
Control card, 24 V DC output
Terminal number12
Maximum load (M1 and M2)100 mA
Maximum load (M3)50 mA
Maximum load (M4 and M5)80 mA
Maximum terminal load (AC-1)1) on 01-02 (NO) (Resistive load)250 V AC, 2 A
Maximum terminal load (AC-15)1) on 01-02 (NO) (Inductive load @ cosφ 0.4)250 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 01-02 (NO) (Resistive load)30 V DC, 2 A
Maximum terminal load (DC-13)1) on 01-02 (NO) (Inductive load)24 V DC, 0.1 A
Maximum terminal load (AC-1)1) on 01-03 (NC) (Resistive load)250 V AC, 2 A
Maximum terminal load (AC-15)1) on 01-03 (NC) (Inductive load @ cosφ 0.4)250 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 01-03 (NC) (Resistive load)30 V DC, 2 A
Minimum terminal load on 01-03 (NC), 01-02 (NO)24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1Overvoltage category III/pollution degree 2
1) IEC 60947 part 4 and 5
99
Control card, 10 V DC output
Terminal number50
Output voltage10.5 V ±0.5 V
Maximum load25 mA
NOTICE
All inputs, outputs, circuits, DC supplies, and relay contacts are galvanically isolated from the supply voltage (PELV) and
other high voltage terminals.
Surroundings
Enclosure protection ratingIP20
Enclosure kit availableIP21, TYPE 1
Vibration test1.0 g
Maximum relative humidity5%–95 % (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60721-3-3), coatedclass 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
Minimum ambient temperature during full-scale operation0 °C (32 °F)
Minimum ambient temperature at reduced performance-10 °C (14 °F)
Temperature during storage/transport-25 to +65/70 °C
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Safety standardsEN/IEC 61800-5-1, UL 508C
EMC standards, EmissionEN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
Energy eciency classIE2
1) Refer to chapter 4.2 Special Conditions for:
Derating for high ambient temperature.
•
Derating for high altitude.
•
2) Determined according to EN 50598-2 at:
99
Rated load.
•
90% rated frequency.
•
Switching frequency factory setting.
•
Switching pattern factory setting.
•
1)
VLT® Micro Drive FC 51
1)
1)
Maximum 40 °C (104 °F)
1000 m (3280 ft)
3000 m (9842 ft)
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3,
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to
products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property
of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.