This manual is regularly reviewed and updated. All
suggestions for improvement are welcome. Table 1.1 shows
the manual version and the corresponding software
version.
EditionRemarksSoftware version
MG02K4XXMiscellaneous minor
Table 1.1 Manual and Software Version
Oces or online at: www.vlt-
VLT® Micro Drive FC 51 Quick Guide
VLT® Micro Drive FC 51 Programming Guide
VLT® Micro Drive FC 51 LCP Mounting Instruction
®
Micro Drive FC 51 De-coupling Plate Mounting
VLT
Instruction
VLT® Micro Drive FC 51 Remote Mounting Kit
Mounting Instruction
®
Micro Drive FC 51 DIN Rail Kit Mounting
VLT
Instruction
VLT® Micro Drive FC 51 IP21 Kit Mounting
Instruction
®
VLT
Micro Drive FC 51 Nema1 Kit Mounting
Instruction
VLT® Micro Drive FC 51 Line Filter MCC 107 Installation Instruction
The rated output current supplied by the frequency
converter.
U
VLT,MAX
The maximum output voltage.
1.4.2 Input
Control command
The connected motor can be started and stopped with LCP
and the digital inputs.
Functions are divided into 2 groups.
Functions in group 1 have higher priority than functions in
group 2.
Group 1Reset, coast stop, reset and coast stop, quick
stop, DC brake, stop, and the [O] key.
Group 2Start, pulse start, reversing, start reversing, jog,
and freeze output.
Table 1.3 Function Groups
Illustration 1.1 Break-away Torque
η
VLT
The eciency of the frequency converter is dened as the
ratio between the power output and the power input.
Start-disable command
A stop command belonging to the group 1 control
commands, see Table 1.3.
Stop command
See Table 1.3.
1.4.3 Motor
f
JOG
The motor frequency when the jog function is activated
(via digital terminals).
f
M
The motor frequency.
f
MAX
The maximum motor frequency.
f
MIN
The minimum motor frequency.
f
M,N
The rated motor frequency (nameplate data).
I
M
The motor current.
I
M,N
The rated motor current (nameplate data).
n
M,N
The nominal motor speed (nameplate data).
P
M,N
The rated motor power (nameplate data).
U
M
The instant motor voltage.
U
M,N
The rated motor voltage (nameplate data).
1.4.4 References
Analog reference
A signal transmitted to the analog inputs 53 or 54, can be
voltage or current.
Bus reference
A signal transmitted to the serial communication port (FC
port).
Preset reference
A dened preset reference to be set from -100% to +100%
of the reference range. Selection of 8 preset references via
the digital terminals.
Ref
MAX
Determines the relationship between the reference input at
100% full scale value (typically 10 V, 20 mA) and the
resulting reference. The maximum reference value set in
parameter 3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input at
0% value (typically 0 V, 0 mA, 4 mA) and the resulting
reference. The minimum reference value set in
parameter 3-02 Minimum Reference.
The analog inputs are used for controlling various
functions of the frequency converter.
There are 2 types of analog inputs:
Current input, 0–20 mA and 4–20 mA
•
Voltage input, 0–10 V DC.
•
Analog outputs
The analog outputs can supply a signal of 0–20 mA, 4–20
mA, or a digital signal.
Automatic Motor Tuning, AMT
AMT algorithm determines the electrical parameters for the
connected motor at standstill.
Brake resistor
The brake resistor is a module capable of absorbing the
brake power generated in regenerative braking. This
regenerative brake power increases the DC-link voltage,
and a brake chopper ensures that the power is transmitted
to the brake resistor.
CT characteristics
Constant torque characteristics used for all applications
such as conveyor belts, displacement pumps, and cranes.
Digital inputs
The digital inputs can be used for controlling various
functions of the frequency converter.
Relay outputs
The frequency converter features 2 programmable relay
outputs.
ETR
Electronic thermal relay is a thermal load calculation based
on present load and time. Its purpose is to estimate the
motor temperature.
Initializing
If initializing is carried out (parameter 14-22 Operation
Mode), the programmable parameters of the frequency
converter return to their default settings.
Initializing parameter 14-22 Operation Mode does not
initialize communication parameters.
Intermittent duty cycle
An intermittent duty rating refers to a sequence of duty
cycles. Each cycle consists of an on-load and an
period. The operation can be either periodic duty or noneperiodic duty.
LCP
The local control panel makes up a complete interface for
control and programming of the frequency converter. The
control panel is detachable and can be installed up to 3 m
from the frequency converter, that is, in a front panel with
the installation kit option.
lsb
Least signicant bit.
o-load
MCM
Short for Mille Circular Mil, an American measuring unit for
cable cross-section. 1 MCM ≡ 0.5067 mm2.
msb
Most signicant bit.
On-line/O-line parameters
Changes to on-line parameters are activated immediately
after the data value is changed. To activate changes to o-line parameters, press [OK].
PI controller
The PI controller maintains the speed, pressure,
temperature, and so on, by adjusting the output frequency
to match the varying load.
RCD
Residual current device.
Set-up
Save parameter settings in 2 set-ups. Change between the
2 parameter set-ups and edit 1 set-up, while another setup is active.
Slip compensation
The frequency converter compensates for the motor slip by
giving the frequency a supplement that follows the
measured motor load keeping the motor speed almost
constant.
Smart logic control (SLC)
The SLC is a sequence of user-dened actions executed
when the associated user-dened events are evaluated as
true by the SLC.
Thermistor
A temperature-dependent resistor.
STW
Status word.
FC standard bus
Includes RS485 bus with FC protocol.
Trip
A state entered in fault situations, for example, if the
frequency converter is subject to an overtemperature or
when the frequency converter is protecting the motor,
process, or mechanism. Restart is prevented until the cause
of the fault has disappeared and the trip state is canceled
by activating reset or, sometimes, by being programmed to
reset automatically. Do not use trip for personal safety.
Trip lock
A state entered in fault situations when the frequency
converter is protecting itself and requiring physical
intervention, for example, if the frequency converter is
subject to a short circuit on the output. A trip lock can
only be canceled by cutting o mains, removing the cause
of the fault, and reconnecting the frequency converter.
Restart is prevented until the trip state is canceled by
activating reset or, sometimes, by being programmed to
reset automatically. Trip lock may not be used for personal
safety.
Variable torque characteristics used for pumps and fans.
+
VVC
If compared with standard voltage/frequency ratio control,
voltage vector control (VVC+) improves the dynamics and
the stability, both when the speed reference is changed
and in relation to the load torque.
1.5 Power Factor
The power factor is the relation between I
3 × U × I
Power factor =
3 × U × I
1 ×COS ϕ
RMS
The power factor for 3-phase control:
Power factor =
I1 × cosϕ1
I
1
=
I
RMS
sincecosϕ1 = 1
I
RMS
The power factor indicates to which extent the frequency
converter imposes a load on the supply.
The lower the power factor, the higher the I
same kW performance.
2
2
2
I
= I
+ I
RMS
+ I
1
5
+ . . + I
7
2
n
In addition, a high-power factor indicates that the dierent
harmonic currents are low.
Indicates a potentially hazardous situation that could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
NOTICE
Indicates important information, including situations that
can result in damage to equipment or property.
2.1.1 Safety Precautions
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains,
DC supply, or load sharing, the motor may start at any
time. Unintended start during programming, service, or
repair work can result in death, serious injury, or
property damage. The motor can start with an external
switch, a eldbus command, an input reference signal
from the LCP or LOP, via remote operation using MCT 10
Set-up Software, or after a cleared fault condition.
To prevent unintended motor start:
Press [O/Reset] on the LCP before
•
programming parameters.
Disconnect the frequency converter from the
•
mains.
Completely wire and assemble the frequency
•
converter, motor, and any driven equipment
before connecting the frequency converter to
AC mains, DC supply, or load sharing.
22
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input, DC supply, or load sharing.
Failure to perform installation, start-up, and maintenance
by qualied personnel can result in death or serious
injury.
Only qualied personnel must perform instal-
•
lation, start-up, and maintenance.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. High voltage can be present
even when the warning LED indicator lights are o.
Failure to wait the specied time after power has been
removed before performing service or repair work can
result in death or serious injury.
Stop the motor.
•
Disconnect AC mains and remote DC-link power
•
supplies, including battery back-ups, UPS, and
DC-link connections to other frequency
converters.
Disconnect or lock PM motor.
•
Wait for the capacitors to discharge fully. The
•
minimum duration of waiting time is specied
in Table 2.1.
Before performing any service or repair work,
•
use an appropriate voltage measuring device to
make sure that the capacitors are fully
discharged.
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
Ensure the correct grounding of the equipment
•
by a certied electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment
can result in death or serious injury.
Ensure that only trained and qualied personnel
•
perform installation, start-up, and maintenance.
Ensure that electrical work conforms to national
•
and local electrical codes.
Follow the procedures in this guide.
•
WARNING
UNINTENDED MOTOR ROTATION
WINDMILLING
Unintended rotation of permanent magnet motors
creates voltage and can charge the unit, resulting in
death, serious injury, or equipment damage.
Ensure that permanent magnet motors are
•
blocked to prevent unintended rotation.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result
in serious injury when the frequency converter is not
properly closed.
Ensure that all safety covers are in place and
•
securely fastened before applying power.
2.2 Disposal Instruction
Equipment containing electrical
components cannot be disposed of
together with domestic waste.
It must be separately collected with
electrical and electronic waste according
to local and currently valid legislation.
The frequency converter complies with UL 508C thermal
memory retention requirements. For more information
refer to chapter 3.5.1 Motor Thermal Protection.
2.4 CE Labeling
2.4.1 CE Conformity and Labeling
What is CE conformity and labeling?
The purpose of CE labelling is to avoid technical trade
obstacles within EFTA and the EU. The EU has introduced
the CE label as a simple way of showing whether a
product complies with the relevant EU directives. The CE
label says nothing about the specications or quality of
the product. Frequency converters are regulated by 3 EU
directives:
The Machinery Directive (98/37/EEC)
All machines with critical moving parts are covered by the
machinery directive of January 1, 1995. Since a frequency
converter is largely electrical, it does not fall under the
machinery directive. However, if a frequency converter is
supplied for use in a machine, Danfoss provides
information on safety aspects relating to the frequency
converter. Danfoss does this with a manufacturer's
declaration.
The Low Voltage Directive (73/23/EEC)
Frequency converters must be CE labeled in accordance
with the Low Voltage Directive of January 1, 1997. The
directive applies to all electrical equipment and appliances
used in the 50–1000 V AC and the 75–1500 V DC voltage
ranges. Danfoss CE-labels in accordance with the directive
and issues a declaration of conformity on request.
The EMC Directive (2004/108/EC)
EMC is short for electromagnetic compatibility. The
presence of electromagnetic compatibility means that the
mutual interference between
appliances does not aect the way the appliances work.
The EMC directive came into eect January 1, 1996.
Danfoss CE-labels in accordance with the directive and
issues a declaration of conformity after request. To carry
out EMC-correct installation, see the instructions in this
design guide. In addition, Danfoss species which
standards our products comply with. Danfoss oers the
lters presented in the specications and provide other
types of assistance to ensure the optimum EMC result.
The frequency converter is most often used by professionals of the trade as a complex component forming part
of a larger appliance, system, or installation. Note that the
responsibility for the nal EMC properties of the appliance,
system or installation rests with the installer.
The EU Guidelines on the Application of Council Directive89/336/EEC outline 3 typical situations of using a frequency
converter. See chapter 2.4.3 Danfoss Frequency Converterand CE Labelling for EMC coverage and CE labelling.
The frequency converter is sold directly to the
•
end-consumer. The frequency converter is for
example sold to a DIY market. The end-consumer
is a layman. The end-consumer installs the
frequency converter himself for use with a hobby
machine, a kitchen appliance, and so on. For such
applications, the frequency converter must be CE
labeled in accordance with the EMC directive.
The frequency converter is sold for installation in
•
a plant. The plant is built up by professionals of
the trade. It could be a production plant or a
heating/ventilation plant designed and installed
by professionals of the trade. Neither the
frequency converter nor the
be CE labeled under the EMC directive. However,
the unit must comply with the basic EMC
requirements of the directive. This is ensured by
using components, appliances, and systems that
are CE labeled under the EMC directive.
The frequency converter is sold as part of a
•
complete system. The system is being marketed
as complete and could for example, be an airconditioning system. The complete system must
be CE labeled in accordance with the EMC
directive. The manufacturer can ensure CE
labelling under the EMC directive either by using
CE labeled components or by testing the EMC of
the system. It is not necessary to test the entire
system if only CE labeled components are
selected.
nished plant has to
2.4.3 Danfoss Frequency Converter and CE
Labelling
guarantees compliance with the Low Voltage Directive.
Danfoss issues a declaration of conformity that conrms
our CE labelling in accordance with the Low Voltage
Directive.
The CE label also applies to the EMC directive if the
instructions for EMC-correct installation and ltering are
followed. On this basis, a declaration of conformity in
accordance with the EMC directive is issued.
The design guide
to ensure EMC-correct installation. Furthermore, Danfoss
species which our dierent products comply with.
Danfoss provides other types of assistance that can help to
obtain the best EMC result.
oers detailed instructions for installation
2.4.4 Compliance with EMC Directive
2004/108/EC
As mentioned, the frequency converter is mostly used by
professionals of the trade as a complex component
forming part of a larger appliance, system, or installation.
Note that the responsibility for the nal EMC properties of
the appliance, system, or installation rests with the installer.
As an aid to the installer, Danfoss has prepared EMC installation guidelines for the power drive system. If the EMCcorrect instructions for installation are followed, the
standards and test levels stated for power drive systems
are complied with.
Air Humidity
2.5
The frequency converter has been designed to meet the
IEC/EN 60068-2-3 standard, EN 50178 9.4.2.2 at 50 °C
(122 °F).
Aggressive Environments
2.6
A frequency converter contains many mechanical and
electronic components. All are to some extent vulnerable
to environmental eects.
22
CE labelling is a positive feature when used for its original
purpose, that is, to facilitate trade within the EU and EFTA.
However, CE labelling may cover many dierentspeci-cations. Check what a given CE label specically covers.
The covered specications can be dierent and a CE label
may therefore give the installer a false feeling of security
when using a frequency converter as a component in a
system or an appliance.
Danfoss CE labels the frequency converters in accordance
with the Low Voltage Directive. This means that if the
frequency converter is installed correctly, Danfoss
Do not install the frequency converter in environments
with airborne liquids, particles, or gases that may aect
or damage the electronic components. Failure to take
necessary protective measures increases the risk of
stoppages, potentially causing equipment damage and
personnel injury.
Liquids can be carried through the air and condense in the
frequency converter and may cause corrosion of
components and metal parts. Steam, oil, and salt water
may cause corrosion of components and metal parts. In
such environments, use equipment with enclosure rating
130BA780.11
SYSTEM CURVE
FAN CURVE
PRESSURE %
A
B
C
0
20
40
60
80
100
120
20406080 100 120 140 160 180
VOLUME %
Safety and Conformity
VLT® Micro Drive FC 51
IP54. As an extra protection, coated printed circuit boards
Advantages
2.8
can be ordered as an option (standard on some power
sizes).
22
2.8.1 Why use a Frequency Converter for
Controlling Fans and Pumps?
Airborne particles such as dust may cause mechanical,
electrical, or thermal failure in the frequency converter. A
typical indicator of excessive levels of airborne particles is
dust particles around the frequency converter fan. In dusty
environments, use equipment with enclosure rating IP54 or
A frequency converter takes advantage of the fact that
centrifugal fans and pumps follow the laws of proportionality for such fans and pumps. For further information,
see chapter 2.8.3 Example of Energy Savings.
a cabinet for IP20/TYPE 1 equipment.
2.8.2 The Clear Advantage - Energy Savings
In environments with high temperatures and humidity,
corrosive gases such as sulphur, nitrogen, and chlorine
compounds cause chemical processes on the frequency
converter components.
Such chemical reactions rapidly
aect and damage the
electronic components. In such environments, mount the
equipment in a cabinet with fresh air ventilation, keeping
aggressive gases away from the frequency converter.
An extra protection in such areas is a coating of the
printed circuit boards, which can be ordered as an option.
Before installing the frequency converter, check the
ambient air for liquids, particles, and gases. This is done by
observing existing installations in this environment. Typical
indicators of harmful airborne liquids are water or oil on
metal parts, or corrosion of metal parts.
The clear advantage of using a frequency converter for
controlling the speed of fans or pumps lies in the
electricity savings.
When comparing with alternative control systems and
technologies, a frequency converter is the optimum energy
control system for controlling fan and pump systems.
Excessive dust particle levels are often found on installation cabinets and existing electrical installations. One
indicator of aggressive airborne gases is blackening of
copper rails and cable ends on existing installations.
Vibration and Shock
2.7
Illustration 2.1 Fan Curves (A, B, and C) for Reduced Fan
Volumes
The frequency converter has been tested according to the
procedure based on the shown standards, Table 2.2.
The frequency converter complies with requirements that
exist for units mounted on the walls and oors of
production premises, and in panels bolted to walls or
Illustration 2.2 Energy Savings with Frequency Converter
Solution
When using a frequency converter to reduce fan capacity
to 60% - more than 50% energy savings may be obtained
in typical applications.
2.8.3 Example of Energy Savings
As shown in Illustration 2.3, the ow is controlled by
changing the RPM. By reducing the speed by only 20%
from the rated speed, the ow is also reduced by 20%.
This is because the ow is directly proportional to the
RPM. The consumption of electricity, however, is reduced
by 50%.
If the system in question only needs to be able to supply a
ow that corresponds to 100% a few days in a year, while
the average is below 80% of the rated ow for the
remainder of the year, the amount of energy saved is even
more than 50%.
Illustration 2.3 describes the dependence of
and power consumption on RPM.
ow, pressure,
Q=FlowP=Power
Q1=Rated owP1=Rated power
Q2=Reduced owP2=Reduced power
H=Pressuren=Speed control
H1=Rated pressuren1=Rated speed
H2=Reduced pressuren2=Reduced speed
Table 2.3 The Laws of Proportionality
2.8.4 Comparison of Energy Savings
The Danfoss frequency converter solution oers major
savings compared with traditional energy saving solutions
such as discharge damper solution and inlet guide vanes
(IGV) solution. This is because the frequency converter is
able to control fan speed according to thermal load on the
system, and the frequency converter has a built-in facility
that enables the frequency converter to function as a
building management system, BMS.
Illustration 2.3 shows typical energy savings obtainable
with 3 well-known solutions when fan volume is reduced
to 60%.
As the graph shows, more than 50% energy savings can be
achieved in typical applications.
This example is calculated based on pump characteristics
obtained from a pump datasheet.
The result obtained shows energy savings more than 50%
at the given ow distribution over a year. The payback
period depends on the price per kWh and the price of
frequency converter. In this example, it is less than a year
when compared with valves and constant speed.
Energy savings
P
shaft=Pshaft output
Illustration 2.4 The 3 Common Energy Saving Systems
Illustration 2.6 Flow Distribution over 1 Year
Illustration 2.5 Energy Savings
Discharge dampers reduce power consumption. Inlet guide
vanes oer a 40% reduction, but are expensive to install.
The Danfoss frequency converter solution reduces energy
consumption with more than 50% and is easy to install. It
and extends the life span of the entire application.
also reduces noise, mechanical stress and wear-and-tear,
175HA209.11
60
50
40
30
20
10
H
s
0100200300400
(mwg)
B
C
A
750rpm
1050rpm
1350rpm
1650rpm
0
10
20
30
(kW)
40
50
60
200100300
(
m3 /h
)
(
m3 /h
)
400
750rpm
1050rpm
1350rpm
1650rpm
P
shaft
C
1
B
1
A
1
Full load
% Full-load current
& speed
500
100
0
012,52537,550Hz
200
300
400
600
700
800
4
3
2
1
175HA227.10
Safety and ConformityDesign Guide
Simple control of process (ow, level, or pressure) utilizing
the built-in PI control.
2.8.7 Star/Delta Starter or Soft Starter not
Required
When larger motors are started, it is necessary in many
countries to use equipment that limits the start-up current.
In more traditional systems, a star/delta starter or soft
starter is widely used. Such motor starters are not required
if a frequency converter is used.
As illustrated in Illustration 2.8, a frequency converter does
not consume more than rated current.
22
Illustration 2.7 Energy
m3/
h
Distri-
bution
Valve regulationFrequency converter
% Hours PowerConsump-
A1 - B
350543842.518.61542.518.615
300 15 131438.550.58929.038.106
1
250 20 175235.061.32018.532.412
200 20 175231.555.18811.520.148
150 20 175228.049.0566.511.388
100 20 175223.040.2963.56.132
100 8760275.06426.801
Σ
Table 2.4 Result
2.8.6 Better Control
If a frequency converter is used for controlling the ow or
pressure of a system, improved control is obtained.
A frequency converter can vary the speed of the fan or
pump, obtaining variable control of ow and pressure.
Furthermore, a frequency converter can quickly adapt the
speed of the fan or pump to new ow or pressure
conditions in the system.
The example in chapter 2.8.9 Without a Frequency Converter
shows that a frequency converter replaces other
equipment. It is possible to calculate the cost of installing
the 2 dierent systems. In the example, the 2 systems can
be established at roughly the same price.
Use the VLT® Energy Box software that is introduced in
chapter 1.1 Available Literature to calculate the cost savings
that can be achieved by using a frequency converter.
Select the conguration mode in parameter 1-00 Conguration Mode.
3.1.1 Control Structure Open Loop
Illustration 3.1 Open-loop Structure
In the conguration shown in Illustration 3.1,
parameter 1-00 Conguration Mode is set to [0] Open loop.
The resulting reference from the reference handling system
or the local reference is received and fed through the ramp
limitation and speed limitation before being sent to the
motor control. The output from the motor control is then
limited by the maximum frequency limit.
frequency converter via the digital inputs and RS485. See
more about starting, stopping, changing ramps and
parameter set-ups, and so on, in parameter group 5-1*
Digital Inputs or parameter group 8-5* Serial Communication.
3.1.2 Local (Hand On) and Remote (Auto
On) Control
The frequency converter can be operated manually via the
local control panel (LCP) or remotely via analog/digital
inputs or eldbus. If allowed in parameter 0-40 [Hand on]
Key on LCP, parameter 0-44 [O/Reset] Key on LCP, and
parameter 0-42 [Auto on] Key on LCP, it is possible to start
and stop the frequency converter by pressing the [Hand
On] and [O/Reset] keys. Alarms can be reset via the [O/Reset] key. After pressing the [Hand On] key, the frequency
converter goes into hand mode and follows (by default)
the local reference set using the LCP potentiometer (LCP
12) or [▲]/[▼] (LCP 11). The potentiometer can be disabled
using parameter 6-80 LCP Potmeter Enable. If the potenti-
ometer is disabled, use the navigation keys for adjusting
reference.
After pressing the [Auto On] key, the frequency converter
goes into auto mode and follows (by default) the remote
reference. In this mode, it is possible to control the
Local reference forces the conguration mode to open
loop, independent on the setting of 1-00 CongurationMode.
Local reference is restored at power-down.
3.1.3 Control Structure Closed Loop
The internal controller allows the frequency converter to
become a part of the controlled system. The frequency
converter receives a feedback signal from a sensor in the
system. It then compares this feedback to a setpoint
reference value and determines the error, if any, between
these 2 signals. It then adjusts the speed of the motor to
correct this error.
7-30 PI
Normal/Inverse
Control
PI
Reference
Feedback
Scale to
speed
P 4-10
Motor speed
direction
To motor
control
130BB894.11
S
100%
0%
-100%
100%
*[-1]
_
+
Product OverviewDesign Guide
For example, consider a pump application where the speed
of a pump is to be controlled so that the static pressure in
a pipe is constant. The static pressure value is supplied to
the frequency converter as the setpoint reference. A static
pressure sensor measures the actual static pressure in the
pipe and supplies this data to the frequency converter as a
feedback signal. If the feedback signal is greater than the
Illustration 3.3 Control Structure Closed Loop
While the default values for the closed-loop controller of
the frequency converter often provide satisfactory
performance, the control of the system can often be
optimized by adjusting parameters.
setpoint reference, the frequency converter slows the
pump down to reduce the pressure. In a similar way, if the
pipe pressure is lower than the setpoint reference, the
frequency converter automatically speeds the pump up to
increase the pressure provided by the pump.
Up to 8 preset references can be programmed in the
frequency converter. The active preset reference can be
selected using digital inputs or the serial communications
bus. The reference can also be supplied externally, most
commonly from an analog input. This external source is
selected by 1 of the 3 reference source parameters
(parameter 3-15 Reference 1 Source,
parameter 3-16 Reference 2 Source, and
parameter 3-17 Reference 3 Source). All reference resources
and the bus reference are added to produce the total
external reference. The external reference, the preset
reference, or the sum of the 2 can be selected to be the
External references (analog inputs and serial
communication bus references).
The preset relative reference.
Feedback-controlled setpoint.
active reference. Finally, this reference can by be scaled
using parameter 3-14 Preset Relative Reference.
The scaled reference is calculated as follows:
Reference = X + X ×
Where X is the external reference, the preset reference or
100
Y
the sum of these and Y is parameter 3-14 Preset Relative
Reference in [%].
If Y, parameter 3-14 Preset Relative Reference, is set to 0%,
the reference is not
aected by the scaling.
1
2
z
z
z
L1
L2
L3
PE
U
V
W
C
S
I
2
I
1
I
3
I
4
C
S
C
S
C
S
C
S
I
4
C
S
z
PE
3
4
5
6
175ZA062.12
Product OverviewDesign Guide
3.2 General Aspects of EMC
3.2.1 General Aspects of EMC Emissions
Frequency converters (and other electrical devices)
generate electronic or magnetic elds that may interfere
with their environment. The electromagnetic compatibility
(EMC) of these eects depends on the power and the
harmonic characteristics of the devices.
Uncontrolled interaction between electrical devices in a
system can degrade compatibility and impair reliable
operation. Interference may take the form of mains
harmonics distortion, electrostatic discharges, rapid voltage
uctuations, or high frequency interference. Electrical
devices generate interference along with being aected by
interference from other generated sources.
Electrical interference usually occurs at frequencies in the
range 150 kHz to 30 MHz. Airborne interference from the
frequency converter system in the range 30 MHz to 1 GHz
is generated from the inverter, motor cable, and the motor.
Capacitive currents in the motor cable coupled with a high
dU/dt from the motor voltage generate leakage currents,
as shown in Illustration 3.5.
The use of a shielded motor cable increases the leakage
current (see Illustration 3.5) because shielded cables have
higher capacitance to ground than unshielded cables. If
the leakage current is not
interference on the mains in the radio frequency range
below approximately 5 MHz. Since the leakage current (I1)
is carried back to the unit through the shield (I3), there is,
in principle, only a small electro-magnetic eld (I4) from
the shielded motor cable according to Illustration 3.5.
ltered, it causes greater
The shield reduces the radiated interference, but increases
the low-frequency interference on the mains. Connect the
motor cable shield to the frequency converter enclosure
and to the motor enclosure. Use the integrated shield
clamps to avoid twisted-pair ends (pigtails). Pigtails
increase the shield impedance at higher frequencies, which
reduces the shield eect and increases the leakage current
(I4).
If a shielded cable is used for relay, control cable, signal
interface, and brake, mount the shield on the enclosure at
both ends. In some situations, it is necessary to break the
shield to avoid current loops.
When placing the shield on a mounting plate for the
frequency converter, ensure that the mounting plate is
made of metal, to convey the shield currents back to the
unit. Ensure good electrical contact from the mounting
plate through the mounting screws to the frequency
converter chassis.
When using unshielded cables, some emission
requirements are not complied with, although most
immunity requirements are observed.
To reduce the interference level from the entire system
(unit+installation), make motor and brake cables as short
as possible. Avoid placing cables with a sensitive signal
level alongside motor cables and brake cables. The control
electronics generate radio interference at frequencies
higher than 50 MHz (airborne).
33
1Ground wire3AC mains supply5 Shielded motor cable
The EMC product standard for frequency converters
denes 4 categories (C1, C2, C3, and C4) with specied
requirements for emission and immunity. Table 3.1 states
the denition of the 4 categories and the equivalent classi-
33
cation from EN 55011.
CategoryDenition
C1Frequency converters installed in
the rst environment (home and
oce) with a supply voltage less
than 1000 V.
C2Frequency converters installed in
the rst environment (home and
oce) with a supply voltage less
than 1000 V, which are not plug-in
and not movable, and must be
installed and commissioned by a
professional.
C3Frequency converters installed in
the second environment (industrial)
with a supply voltage lower than
1000 V.
Equivalent
emission class
in EN 55011
Class B
Class A Group 1
Class A Group 2
C4Frequency converters installed in
the second environment with a
supply voltage equal to or above
1000 V, or rated current equal to or
above 400 A, or intended for use in
complex systems.
Table 3.1 Correlation between IEC 61800-3 and EN 55011
When the generic (conducted) emission standards are
used, the frequency converters are required to comply with
the limits in Table 3.2.
Environment
First
environment
(home and
oce)
Second
environment
(industrial
environment)
Generic emission
standard
EN/IEC 61000-6-3 Emission
standard for residential,
commercial, and light
industrial environments.
EN/IEC 61000-6-4 Emission
standard for industrial
environments.
Equivalent
emission class
in EN 55011
No limit line.
Make an EMC
plan.
Equivalent
emission class in
EN 55011
Class B
Class A Group 1
Table 3.2 Correlation between Generic Emission Standards and
EN 55011
3.2.3 EMC Test Results (Emission)
FC typeConducted emission. Maximum shielded cable length [m]Radiated emission
Industrial environment
EN 55011 Class A2EN 55011 Class A1EN 55011 Class BEN 55011 Class A2EN 55011 Class A1
Without a power option, the frequency converter may
not comply with harmonics emission requirements.
OptionsDenition
1IEC/EN 61000-3-2 Class A for 3-phase balanced
equipment (for professional equipment only up to 1
kW total power).
2IEC/EN 61000-3-12 Equipment 16 A-75 A and profes-
sional equipment as from 1 kW up to 16 A phase
current.
Table 3.4 Harmonics Emission Requirements
3.2.5 Immunity Requirements
The immunity requirements for frequency converters
depend on the environment where they are installed. The
requirements for the industrial environment are higher
than the requirements for the home and oce
environment. All Danfoss frequency converters comply
with the requirements for the industrial environment and
therefore comply also with the lower requirements for
home and oce environment with a large safety margin.
0.25–22 kW (0.34–30 hp)
33
1 Supply (SMPS)
2 Optocouplers, communication between AOC and BOC
3 Custom relays
a Control card terminals
Illustration 3.6 Galvanic Isolation
30–90 kW (40–120 hp)
Galvanic Isolation (PELV)
3.3
PELV oers protection through extra low voltage.
Protection against electric shock is ensured when the
electrical supply is of the PELV type and the installation is
made as described in local/national regulations on PELV
supplies.
All control terminals and relay terminals 01-03/04-06
comply with PELV (protective extra low voltage) (does not
apply to grounded delta leg above 440 V).
Galvanic (ensured) isolation is obtained by
fullling
requirements for higher isolation and by providing the
relevant creapage/clearance distances. These requirements
are described in the EN 61800-5-1 standard.
The components that make up the electrical isolation, as
described, also comply with the requirements for higher
isolation and the relevant test as described in EN
61800-5-1.
The PELV galvanic isolation can be shown in Illustration 3.7.
To maintain PELV, all connections made to the control
terminals must be PELV, for example, thermistor must be
reinforced/double insulated.
1 Supply (SMPS) including signal isolation of UDC, indicating
the intermediate current voltage
2 Gate drive that runs the IGBTs (trigger transformers/opto-
couplers)
3 Current transducers
4 Internal soft-charge, RFI, and temperature measurement
circuits
5 Custom relays
a Control card terminals
Illustration 3.7 Galvanic Isolation
The functional galvanic isolation (see Illustration 3.6) is for
the RS485 standard bus interface.
At altitudes above 2000 m (6500 ft), contact Danfoss
regarding PELV.
33
3.4 Ground Leakage Current
WARNING
DISCHARGE TIME
Touching the electrical parts could be fatal - even after
the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been
disconnected, such as load sharing (linkage of DC
intermediate circuit), and the motor connection for
kinetic back-up.
Before touching any electrical parts, wait at least the
amount of time indicated in Table 2.1.
Shorter time is allowed only if indicated on the
nameplate for the specic unit.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
Ensure the correct grounding of the equipment
•
by a certied electrical installer.
WARNING
RESIDUAL CURRENT DEVICE PROTECTION
This product can cause a DC current in the protective
conductor. Where a residual current device (RCD) is used
for protection in case of direct or indirect contact, only
an RCD of Type B is allowed on the supply side of this
product. Otherwise, apply another protective measure,
such as separation from the environment by double or
reinforced insulation, or isolation from the supply system
by a transformer. See also application note Protectionagainst Electrical Hazards.
Protective grounding of the frequency converter and the
use of RCDs must always follow national and local
regulations.
3.5 Extreme Running Conditions
Short circuit (motor phase-phase)
Current measurement in each of the 3 motor phases or in
the DC-link, protects the frequency converter against short
circuits. A short circuit between 2 output phases causes an
overcurrent in the inverter. The inverter is turned o
individually when the short circuit current exceeds the
allowed value (Alarm 16 Trip Lock).
For information about protecting the frequency converter
against a short circuit at the load sharing and brake
outputs, see chapter 6.6 Fuses.
Switching on the output
Switching on the output between the motor and the
frequency converter is fully permitted. The frequency
converter is not damaged in any way by switching on the
output. However, fault messages may appear.
Motor-generated overvoltage
The voltage in the DC link is increased when the motor
acts as a generator. This occurs in following cases:
The load drives the motor (at constant output
•
frequency from the frequency converter), that is
the load generates energy.
During deceleration (ramp-down) if the inertia
•
moment is high, the friction is low, and the rampdown time is too short for the energy to be
dissipated as a loss in the frequency converter,
the motor, and the installation.
Incorrect slip compensation setting
•
(parameter 1-62 Slip Compensation) may cause
higher DC-link voltage.
The control unit may attempt to correct the ramp if
parameter 2-17 Over-voltage Control is enabled.
The frequency converter turns o to protect the transistors
and the DC link capacitors when a certain voltage level is
reached.
Mains drop-out
During a mains drop-out, the frequency converter keeps
running until the DC-link voltage drops below the
minimum stop level, which is typically 15% below the
frequency converter's lowest rated supply voltage. The
mains voltage before the drop-out and the motor load
determines how long it takes for the frequency converter
to coast.
3.5.1 Motor Thermal Protection
Motor thermal protection can be provided in 2 ways.
Using a motor thermistor, via 1 of the following:
Thermistor input on a standard AI.
•
VLT® Sensor Input MCB 114.
•
VLT® PTC Thermistor Card MCB 112.
•
The frequency converter monitors motor temperature as
the speed and load vary to detect overheating conditions.
The other method calculates motor temperature by
measuring current, frequency, and operating time. The
frequency converter shows the thermal load on the motor
in percentage and can issue a warning at a programmable
overload setpoint. Programmable options at the overload
allow the frequency converter to stop the motor, reduce
output, or ignore the condition. Even at low speeds, the
frequency converter meets I2t Class 20 electronic motor
overload standards.
This method is called electronic thermal relay (ETR).
33
Illustration 3.8 ETR Characteristics
The X-axis shows the ratio between I
motor
and I
motor
nominal. The Y axis shows the time in s before the ETR cut
of and trips the frequency converter. The curves show the
characteristic nominal speed, at twice the nominal speed
and at 0.2 x the nominal speed.
At lower speed, the ETR cuts o at lower heat due to less
cooling of the motor. In that way, the motor is protected
from being overheated even at low speed. The ETR feature
is calculating the motor temperature based on actual
current and speed. The calculated temperature is visible as
a readout parameter in parameter 16-18 Motor Thermal in
the product-specicProgramming Guide.
A special version of the ETR is also available for EX-e
motors in ATEX areas. This function makes it possible to
enter a specic curve to protect the Ex-e motor. The
Programming Guide takes the user through the set-up.
For detailed information on programming, see VLT® Micro
44
Drive FC 51 Programming Guide.
NOTICE
The frequency converter can also be programmed from a
PC via RS485 port by installing the MCT 10 Set-up
Software.
This software can either be ordered using code number
130B1000 or downloaded from the Danfoss website:
A yellow indicator light above the operation keys indicates
the active key.
[Hand On]: Starts the motor and enables control of the
frequency converter via the LCP.
[O/Reset]: Stops the motor (o). If in alarm mode, the
alarm is reset.
[Auto On]: The frequency converter is controlled either via
control terminals or serial communication.
[Potentiometer] (LCP 12): The potentiometer works in 2
ways:
In auto mode the potentiometer acts as an extra
programmable analog input.
In hand-on mode, the potentiometer controls local
reference.
4.1.2 Remote Mounting Kit for LCP
The LCP can be moved to the front of a cabinet by using
the remote built-in kit. The enclosure is IP55.
EnclosureIP55 front
Maximum cable length between LCP and
unit3 m
Communication standard:RS485
Ordering number132B0102
Illustration 4.1 Description of LCP Keys and Display
Press [Menu] to select one of the following menus:
Status
For readouts only.
Quick Menu
For access to Quick Menus 1 and 2.
Main Menu
For access to all parameters.
Navigation keys
[Back]: For moving to the previous step or layer in the
navigation structure.
[▲] [▼]: For maneuvering between parameter groups,
parameters and within parameters.
[OK]: For selecting a parameter and for accepting changes
to parameter settings.
Table 4.1 Technical Data
4.1.3 FC 51 Remote Mounting Kit Mounting
Instruction
Step 1
Fit the gasket on the LCP in the frequency converter.