This guide can be used with all VLT® Refrigeration Drive FC 103
frequency converters with software version 1.x.
The actual software version number can be read from
parameter 15-43 Software Version.
Table 1.1 Software Version
The following symbols are used in this manual.
WARNING
Indicates a potentially hazardous situation which could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could
result in minor or moderate injury. It may also be used
to alert against unsafe practices.
NOTICE
Indicates important information, including situations that
may result in damage to equipment or property.
60° AVM60° asynchronous vector modulation
AAmpere/AMP
ACAlternating current
ADAir discharge
AEOAutomatic energy optimization
AIAnalog input
AICAmpere interrupting current
AMAAutomatic motor adaptation
AWGAmerican wire gauge
°C
CBCircuit breaker
CDConstant discharge
CDMComplete drive module: The frequency converter,
DMDierential mode
D-TYPEDrive dependent
EMCElectromagnetic compatibility
EMFElectromotive force
ETRElectronic thermal relay
°F
f
JOG
f
M
f
MAX
f
MIN
f
M,N
FCFrequency converter
Hiperface®Hiperface® is a registered trademark by Stegmann
HOHigh overload
hpHorse power
HTLHTL encoder (10–30 V) pulses - High-voltage
HzHertz
I
INV
I
LIM
I
M,N
I
VLT,MAX
I
VLT,N
kHzKilohertz
LCPLocal control panel
lsbLeast signicant bit
mMeter
mAMilliampere
MCMMille circular mil
MCTMotion control tool
mHInductance in milli Henry
mmMillimeter
msMillisecond
msbMost signicant bit
η
VLT
nFCapacitance in nano Farad
NLCPNumerical local control panel
NmNewton meter
NONormal overload
n
s
Online/
Oine
Parameters
P
br,cont.
PCBPrinted circuit board
PCDProcess data
Degrees Fahrenheit
Motor frequency when jog function is activated
Motor frequency
Maximum output frequency, the frequency
converter applies on its output
Minimum motor frequency from the frequency
converter
Nominal motor frequency
transistor logic
Rated inverter output current
Current limit
Nominal motor current
Maximum output current
Rated output current supplied by the frequency
converter
Eciency of the frequency converter dened as
ratio between power output and power input
Synchronous motor speed
Changes to online parameters are activated
immediately after the data value is changed
Rated power of the brake resistor (average power
during continuous braking)
ULUnderwriters Laboratories (US organization for the
VVolts
VTVariable torque
VVC+
Frequency converter nominal output power as
high overload (HO)
Nominal motor power
that maintains the speed, pressure, temperature,
and so on
Nominal resistor value that ensures a brake power
on the motor shaft of 150/160% for 1 minute
Minimum permissible brake resistor value by
frequency converter
Recommended brake resistor resistance of
Danfoss brake resistors
modulation
Torque limit
logic
Nominal motor voltage
safety certication)
Voltage vector control plus
and electrical installation of the frequency
converter.
VLT® Refrigeration Drive FC 103 Design Guide holds
•
all technical information about the frequency
converter, customer design, and applications.
®
Refrigeration Drive FC 103 Programming Guide
VLT
•
provides information on how to program and
includes complete parameter descriptions.
MCT 10 Set-up Software Operating Instructions
•
enables the user to congure the frequency
converter from a Windows™-based PC
environment.
VLT® HVAC Drive FC 102/VLT® AQUA Drive FC 202
•
Metasys N2, Operating Instructions.
1.1 Denitions
1.1.1 Frequency Converter
I
VLT,MAX
Maximum output current.
I
VLT,N
Rated output current supplied by the frequency converter.
U
VLT,MAX
Maximum output voltage.
1.1.2 Input
Control command
Start and stop the connected motor with LCP and digital
inputs.
Functions are divided into 2 groups.
Functions in group 1 have higher priority than functions in
group 2.
11
Table 1.2 Abbreviations
Conventions
Numbered lists indicate procedures.
Group 1Reset, coast stop, reset and coast stop, quick stop,
DC brake, stop, the [OFF] key.
Group 2Start, pulse start, reversing, start reversing, jog,
freeze output.
Bullet lists indicate other information and description of
illustrations.
Table 1.3 Function Groups
Italicized text indicates:
Cross-reference.
•
Link.
•
Footnote.
•
Parameter name, parameter group name,
•
parameter option.
All dimensions in drawings are in mm (in).
* Indicates a default setting of a parameter.
®
VLT
•
Refrigeration Drive FC 103 Operating
Instructions provides information on mechanical
1.1.3 Motor
Motor running
Torque generated on output shaft and speed from 0 RPM
to maximum speed on motor.
f
JOG
Motor frequency when the jog function is activated (via
digital terminals).
A signal transmitted to the analog inputs 53 or 54 (voltage
or current).
Binary reference
A signal transmitted to the serial communication port.
Preset reference
A dened preset reference to be set from -100% to +100%
of the reference range. Selection of 8 preset references via
the digital terminals.
Pulse reference
A pulse frequency signal transmitted to the digital inputs
(terminal 29 or 33).
Ref
MAX
Determines the relationship between the reference input at
100% full scale value (typically 10 V, 20 mA) and the
resulting reference. The maximum reference value is set in
parameter 3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input at
0% value (typically 0 V, 0 mA, 4 mA) and the resulting
reference. The minimum reference value is set in
parameter 3-02 Minimum Reference.
Rated motor voltage (nameplate data).
Break-away torque
1.1.5 Miscellaneous
Illustration 1.1 Break-away Torque
η
VLT
The eciency of the frequency converter is dened as the
ratio between the power output and the power input.
Start-disable command
A stop command belonging to Group 1 control commands
- see Table 1.3.
Stop command
A stop command belonging to Group 1 control commands
- see Table 1.3.
Analog inputs
The analog inputs are used for controlling various
functions of the frequency converter.
There are 2 types of analog inputs:
Current input, 0–20 mA, and 4–20 mA
Voltage input, -10 V DC to +10 V DC.
Analog outputs
The analog outputs can supply a signal of 0–20 mA, 4–20
mA.
Automatic motor adaptation, AMA
AMA algorithm determines the electrical parameters for
the connected motor at standstill.
CT characteristics
Constant torque characteristics used for all applications
such as conveyor belts, displacement pumps, and cranes.
Digital inputs
The digital inputs can be used for controlling various
functions of the frequency converter.
Digital outputs
The frequency converter features 2 solid-state outputs that
can supply a 24 V DC (maximum 40 mA) signal.
Electronic thermal relay is a thermal load calculation based
on present load and time. Its purpose is to estimate the
motor temperature.
Hiperface
Hiperface® is a registered trademark by Stegmann.
Initializing
If initializing is carried out (parameter 14-22 Operation
Mode), the frequency converter returns to the default
setting.
Intermittent duty cycle
An intermittent duty rating refers to a sequence of duty
cycles. Each cycle consists of an on-load and an o-load
period. The operation can be either periodic duty or nonperiodic duty.
LCP
The local control panel makes up a complete interface for
control and programming of the frequency converter. The
control panel is detachable and can be installed up to 3 m
(10 ft) from the frequency converter, that is, in a front
panel with the installation kit option.
NLCP
Numerical local control panel interface for control and
programming of the frequency converter. The display is
numerical and the panel is used to show process values.
The NLCP has no storage and copy functions.
lsb
Least signicant bit.
msb
Most signicant bit.
MCM
Short for mille circular mil, an American measuring unit for
cable cross-section. 1 MCM=0.5067 mm2.
Online/oine parameters
Changes to online parameters are activated immediately
after the data value is changed. Press [OK] to activate
changes to o-line parameters.
Process PID
The PID control maintains the required speed, pressure,
temperature, and so on, by adjusting the output frequency
to match the varying load.
PCD
Process control data.
Power cycle
Switch o the mains until display (LCP) is dark – then turn
power on again.
Pulse input/incremental encoder
An external, digital pulse transmitter used for feeding back
information on motor speed. The encoder is used in
applications where great accuracy in speed control is
required.
®
RCD
Residual current device.
Set-up
Save parameter settings in 4 set-ups. Change between the
4 parameter set-ups and edit 1 set-up, while another setup is active.
The frequency converter compensates for the motor slip by
giving the frequency a supplement that follows the
measured motor load keeping the motor speed almost
constant.
SLC
The SLC (smart logic control) is a sequence of user-dened
actions executed when the associated user-dened events
are evaluated as true by the SLC. (See
chapter 3.11 Parameters: 13-** Smart Logic).
STW
Status word.
FC standard bus
Includes RS485 bus with FC protocol or MC protocol. See
parameter 8-30 Protocol.
THD
Total harmonic distortion states the total contribution of
harmonic.
Thermistor
A temperature-dependent resistor placed on the frequency
converter or the motor.
Trip
A state entered in fault situations, for example if the
frequency converter is subject to an overtemperature or
when the frequency converter is protecting the motor,
process, or mechanism. The frequency converter prevents a
restart until the cause of the fault has disappeared. To
cancel the trip state, restart the frequency converter. Do
not use the trip state for personal safety.
Trip lock
The frequency converter enters this state in fault situations
to protect itself. The frequency converter requires physical
intervention, for example when there is a short circuit on
the output. A trip lock can only be canceled by disconnecting mains, removing the cause of the fault, and
reconnecting the frequency converter. Restart is prevented
until the trip state is canceled by activating reset or,
sometimes, by being programmed to reset automatically.
Do not use the trip lock state for personal safety.
VT characteristics
Variable torque characteristics used for pumps and fans.
If compared with standard voltage/frequency ratio control,
voltage vector control (VVC+) improves the dynamics and
the stability, both when the speed reference is changed
and in relation to the load torque.
The power factor indicates to which extent the frequency
converter imposes a load on the mains supply.
The lower the power factor, the higher the I
RMS
for the
same kW performance.
2
2
2
I
= I
+ I
RMS
+ I
1
5
+ .. + I
7
2
n
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. High voltage can be present
even when the warning indicator lights are o. Failure to
wait the specied time after power has been removed
before performing service or repair work, could result in
death or serious injury.
1.Stop the motor.
2.Disconnect AC mains, permanent magnet type
motors, and remote DC-link power supplies,
including battery back-ups, UPS, and DC-link
connections to other frequency converters.
3.Wait for the capacitors to discharge fully, before
performing any service or repair work. The
duration of waiting time is specied in Table 1.4.
In addition, a high-power factor indicates that the dierent
harmonic currents are low.
Voltage [V]Minimum waiting time (minutes)
The DC coils in the frequency converters produce a highpower factor, which minimizes the imposed load on the
mains supply.
Target position
The nal target position specied by positioning
commands. The prole generator uses this position to
calculate the speed prole.
Commanded position
The actual position reference calculated by the prole
generator. The frequency converter uses the commanded
4715
200–2400.25–3.7 kW
(0.34–5 hp)
380–5000.25–7.5 kW
(0.34–10 hp)
525–6000.75–7.5 kW
(1–10 hp)
525–690–1.5–7.5 kW
–5.5–37 kW
(7.5–50 hp)
–11–75 kW
(15–100 hp)
–11–75 kW
(15–100 hp)
(2–10 hp)
(15–100 hp)
11–75 kW
position as setpoint for position PI.
Actual position
The actual position from an encoder, or a value that the
motor control calculates in open loop. The frequency
converter uses the actual position as feedback for position
PI.
Position error
Position error is the dierence between the actual position
and the commanded position. The position error is the
input for the position PI controller.
Position unit
The physical unit for position values.
Voltage
[V]
380–50090–250 kW
525–69055–315 kW (frame size D)
Table 1.4 Discharge Time
PowerMinimum waiting
time (minutes)
20
(125–350 hp)
315–800 kW
(450–1075 hp)
(75–450 hp)
355–1200 kW
(475–1600 hp)
40
20
30
Safety regulations
Disconnect mains supply to the frequency
•
converter whenever repair work is to be carried
out. Check that the mains supply has been
disconnected and that the necessary time has
elapsed before removing motor and mains supply
plugs. For information about the discharge time,
see Table 1.4.
[O] does not disconnect the mains supply and
•
must not be used as a safety switch.
Ground the equipment properly, protect the user
•
against supply voltage, and protect the motor
against overload in accordance with applicable
national and local regulations.
The ground leakage current exceeds 3.5 mA.
•
Ensure correct grounding of the equipment by a
certied electrical installer.
Do not remove the plugs for the motor and
•
mains supply while the frequency converter is
connected to mains. Check that the mains supply
has been disconnected and that the necessary
time has elapsed before removing motor and
mains plugs.
The frequency converter has more voltage
•
sources than L1, L2, and L3, when load sharing
(linking of DC intermediate circuit) or external 24
V DC is installed. Check that all voltage sources
have been disconnected and that the necessary
time has elapsed before commencing repair work.
For information about the discharge time, see
Table 1.4.
NOTICE
When using the Safe Torque O, always follow the
instructions in VLT® Frequency Converters - Safe Torque
O Operating Instructions.
NOTICE
Hazardous situations must be identied by the machine
builder/integrator who is responsible for considering the
necessary preventive means. More monitoring and
protective devices may be included, always according to
valid national safety regulations, for example, law on
mechanical tools and regulations for the prevention of
accidents.
Protection mode
Once a hardware limit on motor current or DC-link voltage
is exceeded, the frequency converter enters the protection
mode. Protection mode means a change of the PWM
modulation strategy and a low switching frequency to
minimize losses. This continues for 10 s after the last fault
and increases the reliability and the robustness of the
frequency converter while re-establishing full control of the
motor.
Protection mode can be disabled by setting
parameter 14-26 Trip Delay at Inverter Fault to 0, which
means that the frequency converter trips immediately if 1
of the hardware limits is exceeded.
NOTICE
Disabling protection mode in hoisting applications
(parameter 14-26 Trip Delay at Inverter Fault = 0) is
recommended.
11
NOTICE
Control signals from, or internally within, the frequency
converter may in rare cases be activated in error, be
delayed, or fail to occur entirely. When used in situations
where safety is critical, for example, when controlling the
electromagnetic brake function of a hoist application,
these control signals must not be relied on exclusively.
A=Analog, D=Digital
Terminal 37 is used for Safe Torque O. For Safe Torque O installation instructions, refer to the VLT® Frequency Converters -
Safe Torque O Operating Instructions.
Very long control cables and analog signals may in rare cases, and depending on installation, result in 50/60 Hz ground
loops due to noise from mains supply cables.
If this occurs, it may be necessary to break the shield or insert a 100 nF capacitor between shield and enclosure.
Connect the digital and analog inputs and outputs separately to the common inputs (terminals 20, 55, and 39) of the
frequency converter to avoid ground currents from both groups to
digital input may disturb the analog input signal.
2.Menu keys and indicator lights (LEDs) - selecting
mode, changing parameters, and switching
between display functions.
3.Navigation keys and indicator lights (LEDs).
4.Operation keys and indicator lights (LEDs).
Graphical display
The LCD display is backlit with a total of 6 alpha-numeric
lines. All data is shown on the LCP, which can show up to
5 operating variables while in Status mode.
Display lines:
a.Status line
Status messages displaying icons and graphics.
b.Line 1–2
Operator data lines displaying data and variables
dened or selected by the user. Press [Status] to
add 1 extra line.
c.Status line
Status messages displaying text.
22
Illustration 2.1 LCP
The display is divided into 3 sections:
Top section
(a) shows the status when in Status mode, or up to 2
variables when not in Status mode, and in the case of
alarm/warning.
The number of the active set-up (selected as the active
set-up in parameter 0-10 Active Set-up) is shown. When
programming in another set-up than the active set-up, the
number of the set-up being programmed appears to the
right in brackets.
Middle section
(b) shows up to 5 variables with related unit, regardless of
status. In case of alarm/warning, the warning is shown
instead of the variables.
Bottom section
(c) always shows the state of the frequency converter in
status mode.
Press [Status] to toggle between 3 status readout displays.
Operating variables with dierent formatting are shown in
each status screen.
22
Several values or measurements can be linked to each of
the shown operating variables.
Dene the values/measurements to be shown via:
Parameter 0-20 Display Line 1.1 Small
•
Parameter 0-21 Display Line 1.2 Small
•
Parameter 0-22 Display Line 1.3 Small
•
Parameter 0-23 Display Line 2 Large
•
Parameter 0-24 Display Line 3 Large
•
which can be accessed via [Quick Menu], Q3 Function Setups, Q3-1 General Settings, Q3-13 Display Settings.
Each value/measurement readout parameter selected in
Illustration 2.3 Example of Status Display II
Status display III
This state displays the event and action of the smart logic
control.
parameter 0-20 Display Line 1.1 Small to
parameter 0-24 Display Line 3 Large has its own scale and
number of digits after a possible decimal point. Larger
numeric values are shown with few digits after the decimal
point.
Ex.: Current readout
5.25 A; 15.2 A 105 A.
Status display I
Illustration 2.4 Example of Status Display III
This readout state is standard after start-up or initialization.
Press [INFO] to obtain information about the value/
measurement linked to the shown operating variables (1.1,
1.2, 1.3, 2, and 3).
See the operating variables shown in the display in
Display contrast adjustment
Press [Status] and [▲] for darker display.
Press [Status] and [▼] for brighter display.
Illustration 2.2. 1.1, 1.2, and 1.3 are shown in small size. 2
and 3 are shown in medium size.
Illustration 2.5 Display Sections
Illustration 2.2 Example of Status Display I
Indicator lights (LEDs)
If certain threshold values are exceeded, the alarm and/or
warning LED lights up. A status and alarm text appear in
Status display II
See the operating variables (1.1, 1.2, 1.3, and 2) shown in
the display in Illustration 2.3.
In the example, speed, motor current, motor power, and
frequency are selected as variables in the rst and second
lines.
1.1, 1.2, and 1.3 are shown in small size. 2 is shown in
large size.
the display.
The On LED is activated when the frequency converter
receives power from mains voltage, a DC bus terminal, or a
24 V external supply. At the same time, the backlight is on.
Green LED/On: Control section is working.
•
Yellow LED/Warn.: Indicates a warning.
•
Flashing Red LED/Alarm: Indicates an alarm.
•
On
Warn.
Alarm
130BP044.10
130BP045.10
Status
Quick
Menu
Main
Menu
Alarm
Log
How to ProgramProgramming Guide
Illustration 2.6 Indicator Lights
GLCP keys
Menu keys
The menu keys are divided into functions. The keys below
the display and indicator lights are used for parameter setup, including selection of display indication during normal
operation.
Illustration 2.7 Menu Keys
Most VAV and CAV supply and return fans.
•
Cooling tower fans.
•
Primary, secondary, and condenser water pumps.
•
Other pump, fan, and compressor applications.
•
Among other features, it also includes parameters for
selecting which variables to display in the LCP:
Digital preset speeds.
•
Scaling of analog references.
•
Closed-loop single-zone and multi-zone
•
applications.
Specic functions related to fans, pumps, and
•
compressors.
The Quick Menu parameters can be accessed immediately
unless a password has been created via:
Parameter 0-60 Main Menu Password.
•
Parameter 0-61 Access to Main Menu w/o Password.
•
Parameter 0-65 Personal Menu Password.
•
Parameter 0-66 Access to Personal Menu w/o
•
Password.
It is possible to switch directly between Quick Menu mode
and Main Menu mode.
22
[Status]
[Status] indicates the status of the frequency converter
and/or the motor.
3 dierent readouts can be selected by pressing the
[Status] key:
5-line readouts.
•
4-line readouts.
•
Smart logic control.
•
Press [Status] to select the display mode or for changing
back to Display mode from either Quick Menu mode, MainMenu mode, or Alarm mode. Also press [Status] to toggle
between single or double readout mode.
[Quick Menu]
[Quick Menu] allows quick set-up of the frequency
converter. The most common functions can be
programmed here.
The Quick Menu consists of:
My personal menu.
•
Quick set-up.
•
Function set-up.
•
Changes made.
•
Loggings.
•
The Function Set-up provides quick and easy access to all
parameters required for most applications including:
[Main Menu]
Press [Main Menu] to program all parameters. The main
menu parameters can be accessed immediately unless a
password has been created via:
Parameter 0-60 Main Menu Password.
•
Parameter 0-61 Access to Main Menu w/o Password.
•
Parameter 0-65 Personal Menu Password.
•
Parameter 0-66 Access to Personal Menu w/o
•
Password.
For most applications, it is not necessary to access the
main menu parameters. Instead, the Quick Menu, Quick Set-up and Function Set-up provide the simplest and quickest
access to the most required parameters.
It is possible to switch directly between Main Menu mode
and Quick Menu mode.
Parameter shortcut can be carried out by pressing [Main
Menu] for 3 s. The parameter shortcut allows direct access
to any parameter.
[Alarm Log]
[Alarm Log] displays an alarm list of the 10 most recent
alarms (numbered A1-A10). To obtain more details about
an alarm, press the navigation keys to manoeuvre to the
alarm number and press [OK]. Information is shown about
the condition of the frequency converter before it enters
the alarm mode.
The [Alarm Log] key on the LCP allows access to both
alarm log and maintenance log.
[Back] reverts to the previous step or layer in the
navigation structure.
Operation keys
Operation keys for local control are found at the bottom of
the control panel.
22
Illustration 2.8 Back Key
Illustration 2.12 Operation Keys
[Cancel]
[Cancel] cancels the last change or command as long as
the display has not been changed.
Illustration 2.9 Cancel Key
[Info]
[Info] displays information about a command, parameter,
or function in any display window. [Info] provides detailed
information when needed.
Exit Info mode by pressing either [Info], [Back], or [Cancel].
Illustration 2.10 Info Key
[Hand On]
[Hand On] enables control of the frequency converter via
the GLCP. [Hand On] also starts the motor and allows
entering the motor speed data with the navigation keys.
The key can be selected as [1] Enable or [0] Disable via
parameter 0-40 [Hand on] Key on LCP.
The following control signals are still active when [Hand
On] is activated:
[Hand On] - [O] - [Auto On].
•
Reset.
•
Coasting stop inverse.
•
Reversing.
•
Set-up select lsb - Set-up select msb.
•
Stop command from serial communication.
•
Quick stop.
•
DC brake.
•
Navigation Keys
The 4 navigation keys are used to navigate between the
dierent options available in the Quick Menu, Main Menu,
and Alarm Log. Press the keys to move the cursor.
[OK]
Press [OK] to select a parameter marked by the cursor and
for enabling the change of a parameter.
Illustration 2.11 Navigation Keys
NOTICE
External stop signals activated with control signals or a
eldbus override a start command via the LCP.
[O]
[O] stops the connected motor. The key can be selected
as [1] Enabled or [0] Disabled via parameter 0-41 [O] Key onLCP. If no external stop function is selected, and the [O]
key is inactive, the motor can only be stopped by disconnecting the mains supply.
[Auto On]
[Auto On] enables the frequency converter to be controlled
via the control terminals and/or serial communication.
When a start signal is applied on the control terminals
and/or the bus, the frequency converter starts. The key can
be selected as [1] Enabled or [0] Disabled via
parameter 0-42 [Auto on] Key on LCP.
An active HAND-OFF-AUTO signal via the digital inputs
has higher priority than the control keys [Hand On] –
[Auto On].
[Reset]
Press [Reset] to reset the frequency converter after an
alarm (trip). It can be selected as [1] Enable or [0] Disable
via parameter 0-43 [Reset] Key on LCP.
The parameter shortcut can be carried out by pressing the
[Main Menu] key for 3 s. The parameter shortcut allows
direct access to any parameter.
2.1.2 Quick Transfer of Parameter Settings
between Multiple Frequency
Converters
Once the set-up of a frequency converter is complete,
store the data in the LCP or on a PC via MCT 10 Set-up
Software.
All parameter settings are now stored in the LCP indicated
by the progress bar. When 100% is reached, press [OK].
Connect the LCP to another frequency converter and copy
the parameter settings to this frequency converter as well.
Data transfer from LCP to frequency converter
NOTICE
Stop the motor before performing this operation.
To transfer the data from the LCP to the frequency
converter:
1.Go to parameter 0-50 LCP Copy.
2.Press the [OK] key.
3.Select [2] All from LCP.
4.Press the [OK] key.
The parameter settings stored in the LCP are now
transferred to the frequency converter indicated by the
progress bar. When 100% is reached, press [OK].
2.1.3 Parameter Set-Up
The frequency converter can be used for practically all
assignments, thus oering a signicant number of
parameters. The series oers a choice between 2
programming modes - the Quick Menu mode and the MainMenu mode.
The Main Menu provides access to all parameters. TheQuick Menu takes the user through a few parameters
making it possible to program the majority of applications.
Regardless of the programming mode, parameters can be
changed in both Quick Menu mode and in Main Menu
mode.
22
2.1.4 Quick Menu Mode
Parameter data
The graphical display (GLCP) provides access to all
parameters listed in the Quick Menu. The numeric display
(NLCP) only provides access to the Quick Set-up parameters.
To set parameters pressing [Quick Menu] - enter or change
parameter data or settings in accordance with the
following procedure:
1.Press [Quick Menu].
2.
Press [▲] or [▼] to nd the parameter to change.
3.Press [OK].
4.
Press [▲] or [▼] to select the correct parameter
setting.
5.Press [OK].
6.To move to a dierent digit within a parameter
setting, use the [◀] and [▶].
130BP064.10
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
40.0% 4.84 A 1(1)
Quick Menus
How to Program
VLT® Refrigeration Drive FC 103
7.Highlighted area indicates digit selected for
change.
22
8.Press [Cancel] to disregard change, or press [OK]
to accept change and enter the new setting.
Example of changing parameter data
Assume that parameter 22-60 Broken Belt Function is set to
[0] O. To monitor the fan-belt condition, non-broken or
broken, follow this procedure:
1.Press [Quick Menu].
2.
Press [▼] to select Function Set-ups.
3.Press [OK].
4.
Press [▼] to select Application Settings.
5.Press [OK].
6.Press [OK] again for Fan Functions.
7.Press [OK] to select Broken Belt Function.
8.
Press [▼], to select [2] Trip.
Example of using the quick set-up
To set the ramp-down time to 100 s, follow this procedure:
1.Select Quick Set-up. Parameter 0-01 Language in
Quick Set-up appears.
2.
Press [▼] repeatedly until parameter 3-42 Ramp 1Ramp Down Time appears with the default setting
of 20 s.
3.Press [OK].
4.
Press [◀] to highlight the third digit before the
comma.
5.
Change 0 to 1 by pressing [▲].
6.
Press [▶] to highlight the digit 2.
7.
Change 2 to 0 by pressing [▼].
8.Press [OK].
The new ramp-down time is now set to 100 s.
If a broken fan belt is detected, the frequency converter
trips.
Select Q1 My Personal Menu to display personal
parameters
For example, an AHU or pump OEM may have preprogrammed personal parameters to be in My Personal
Illustration 2.14 Quick Menu View
Menu during factory commissioning to make on-site
commissioning/ne-tuning simpler. These parameters are
selected in parameter 0-25 My Personal Menu. Up to 20
dierent parameters can be programmed in this menu.
Select Changes Made for information about:
The last 10 changes. Press [▲] and [▼] to scroll
•
between the last 10 changed parameters.
The changes made since default setting.
•
Loggings
Loggings show information about the display line
readouts. The information is shown as graphs.
Only display parameters selected in parameter 0-20 DisplayLine 1.1 Small and parameter 0-24 Display Line 3 Large can
be viewed. Up to 120 samples can be stored in the
memory for later reference.
Quick set-up
Ecient parameter set-up for refrigeration applications
The parameters can easily be set up for most refrigeration
applications only by using the Quick Set-up.
After pressing [Quick Menu], the dierent options in the
Quick Menu are listed. See also Illustration 2.14.
Access the 18 most important set-up parameters of the
frequency converter via Quick Set-up. After programming,
the frequency converter is ready for operation. The 18
Quick Set-up parameters are shown in Table 2.1.
Parameter[Units]
Parameter 0-01 Language–
Parameter 1-03 Torque Characteristics–
Parameter 1-20 Motor Power [kW ][kW]
Parameter 1-21 Motor Power [HP][hp]
Parameter 1-22 Motor Voltage[V]
Parameter 1-23 Motor Frequency[Hz]
Parameter 1-24 Motor Current[A]
Parameter 1-25 Motor Nominal Speed[RPM]
Parameter 1-39 Motor Poles–
Parameter 4-12 Motor Speed Low Limit [Hz][Hz]
Parameter 4-14 Motor Speed High Limit [Hz][Hz]
Parameter 3-02 Minimum Reference–
Parameter 3-03 Maximum Reference–
Parameter 3-41 Ramp 1 Ramp Up Time[s]
Parameter 3-42 Ramp 1 Ramp Down Time[s]
Parameter 3-13 Reference Site–
Parameter 5-10 Terminal 18 Digital Input–
Parameter 1-29 Automatic Motor Adaptation (AMA)–
Function
Parameter 20-41 Cut-out ValueParameter 20-30 Refrigerant–
Parameter 20-42 Cut-in ValueParameter 20-40 Thermostat/Pressostat Function –
Parameter 25-00 Pack ControllerParameter 20-41 Cut-out Value–
Parameter 25-06 Number of CompressorsParameter 20-42 Cut-in Value–
Parameter 25-20 Neutral Zone [unit]––
Parameter 25-21 + Zone [unit]––
Parameter 25-22 - Zone [unit]––
Table 2.5 Q3-4 Application Settings
Parameter 20-02 Feedback 1 Source Unit–
22
2.1.6 Main Menu Mode
To select the Main Menu mode, press the [Main Menu] key.
Lines 2–5 on the display show parameter groups which
can be selected by pressing [▲] and [▼].
Illustration 2.22 Display Example
Each parameter has a name and a number which remain
the same regardless of the programming mode. In the
Main Menu mode, the parameters are divided into groups.
All parameters can be changed in the Main Menu. The
conguration of the unit (parameter 1-00 Conguration
Mode) determines other parameters available forprogramming. For example, selecting [3] Process Closed
Loop enables additional parameters related to closed-loop
operation. Options installed on the frequency converter
enable extra parameters associated with the option.
2.1.7 Parameter Selection
In the Main Menu mode, the parameters are divided into
groups. Press the navigation keys to select parameter
group.
The following parameter groups are accessible:
After selecting a parameter group, press the navigation
keys to select a parameter.
130BP067.10
740RPM
0 -01 Language
[0] English
10.64A1 [1]
0-0
*
Basic Settings
130BP068.10
740RPM
0 -01 Language
[0] English
10.64 A1 [1]
0-0
*
Basic Settings
130BP069.10
1- 6*
113 RPM 1.78 A 1(1)
Load depen. setting
1 - 60 Low speed load
compensation
100%
130BP070.10
1 - 60 Low speed load
compensation
1 0%
Load depen. setting1- 6*
729RPM 6.21A 1(1)
6
How to Program
VLT® Refrigeration Drive FC 103
The middle section on the display shows the parameter
number and name, as well as the selected parameter
value.
Press the [▲] [▼] keys to change the data value. [▲]
increases the data value, and [▼] decreases the data value.
Place the cursor on the value to save and press [OK].
22
Illustration 2.23 Parameter Selection
Illustration 2.26 Changing a Group of Numeric Data Values
2.1.8 Changing Data
2.1.11 Value, Step-by-step
Press [OK] to change the selected parameter. The
procedure for changing data depends on whether the
selected parameter represents a numerical data value or a
text value.
2.1.9 Changing a Text Value
If the selected parameter is a text value, change the text
value with the [▲] [▼] keys.
Place the cursor on the value that should be saved and
press [OK].
Certain parameters can be changed step by step. This
applies to:
Parameter 1-20 Motor Power [kW].
•
Parameter 1-22 Motor Voltage.
•
Parameter 1-23 Motor Frequency.
•
The parameters are changed both as a group of numeric
data values and as numeric data values that are
innitely
varying.
2.1.12 Read out and Programming of
Indexed Parameters
Parameters are indexed when placed in a rolling stack.
Parameter 15-30 Alarm Log: Error Code to
parameter 15-33 Alarm Log: Date and Time contain a fault
log which can be read out. Select a parameter, press [OK],
and use the [▲]/[▼] navigation keys to scroll through the
Illustration 2.24 Changing a Text Value
value log.
Use parameter 3-10 Preset Reference as another example:
2.1.10 Changing a Group of Numeric Data
Values
Select the parameter, press [OK], and use the [▲]/[▼]
navigation keys to scroll through the indexed values. To
change the parameter value, select the indexed value and
If the selected parameter represents a numeric data value,
change the data value pressing the [◀] [▶] navigation keys,
as well as the [▲] [▼] navigation keys. Press [◀] [▶] keys to
press [OK]. To change the value, press the [▲]/[▼] keys.
Press [OK] to accept the new setting. Press [Cancel] to
abort. Press [Back] to leave the parameter.
move the cursor horizontally.
2.1.13 Initialization to Default Settings
Initialize the frequency converter to default settings in 2
ways.
Parameters for the frequency converter are grouped into
various parameter groups for easy selection of the correct
parameters for optimized operation of the frequency
converter.
Most refrigeration applications can be programmed by
pressing [Quick Menu] and selecting the parameters under
Quick Setup and Function Set-ups.
Descriptions and default settings of parameters are in
chapter 4 Parameter Lists.
Parameter groups
0-** Operation/Display
•
1-** Load and Motor
•
2-** Brakes
•
3-** Reference/Ramps
•
4-** Limits/Warnings
•
5-** Digital In/Out
•
6-** Analog In/Out
•
8-** Comm. and Options
•
11-** LonWorks
•
13-** Smart Logic
•
14-** Special Functions
•
15-** Drive Information
•
16-** Data Readouts
•
18-** Info & Readouts
•
20-** Drive Closed Loop
•
21-** Ext. Closed Loop
•
22-** Appl. Functions
•
23-** Time-based Functions
•
25-** Pack Controller
•
26-** Analog I/O Option
•
28-** Compressor Functions
•
Parameters: 0-** Operation and Display
3.2
Parameters related to the fundamental functions of the
frequency converter, function of the LCP keys, and congu-ration of the LCP display.
0-01 Language
Option:Function:
Denes the language to be used in the
display.
The frequency converter is delivered with
2 dierent language packages. English and
German are included in both packages.
English cannot be erased or manipulated.
This parameter cannot be adjusted while the
motor is running.
The information shown in the display depends on
settings in parameter 0-02 Motor Speed Unit and parameter 0-03 Regional Settings. The default settings
of parameter 0-02 Motor Speed Unit and
parameter 0-03 Regional Settings depend on to which
region of the world the frequency converter is
supplied.
NOTICE
Changing the motor speed unit resets certain
parameters to their initial value. Select the
motor speed unit before modifying other
parameters.
[0]RPM Select to show motor speed variables and parameters
using motor speed (RPM).
[1] * HzSelect to show motor speed variables and parameters
using output frequency (Hz).
0-03 Regional Settings
Option:Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
The display output depends on the settings in
parameter 0-02 Motor Speed Unit and
parameter 0-03 Regional Settings. The defaultsettings of parameter 0-02 Motor Speed Unit and
parameter 0-03 Regional Settings depend on which
region of the world the frequency converter is
supplied to. Reprogram the settings as required.
The settings not used are made invisible.
[0] Interna-
tional
[1] North
America
0-04 Operating State at Power-up
Option:Function:
Sets parameter 1-20 Motor Power [kW] units to
[kW] and the default value of
parameter 1-23 Motor Frequency [50 Hz].
Sets parameter 1-21 Motor Power [HP] units to [hp]
and the default value of parameter 1-23 MotorFrequency to 60 Hz.
Select the operating mode after reconnection of
the frequency converter to mains voltage after
power-down when operating in hand-on (local)
mode.
0-04 Operating State at Power-up
Option:Function:
[0] * ResumeResumes operation of the frequency converter
maintaining the same local reference and the
same start/stop condition (applied by [Hand
On]/[O] on the LCP or local start via a digital
input as before the frequency converter was
powered down.
[1]Forced
stop,
ref=old
Stops the frequency converter, but at the same
time retains the local speed reference before
power-down in the memory. After mains
voltage is reconnected and after receiving a
start command (pressing [Hand On] or local
start command via a digital input), the
frequency converter restarts and operates at the
retained speed reference.
0-05 Local Mode Unit
Option:Function:
Denes if the local reference unit is shown
in terms of the motor shaft speed (in
RPM/Hz) or as percent.
[0] * As Motor
Speed Unit
[1]%
3.2.1 0-1* Set-up Operations
Dene and control the individual parameter set-ups.
The frequency converter has 4 parameter set-ups that can
be programmed independently of each other. This makes
the frequency converter very exible and able to meet the
requirements of many dierent refrigeration system control
schemes, often saving the cost of external control
equipment. For example, these can be used to program
the frequency converter to operate according to 1 control
scheme in 1 set-up (for example daytime operation) and
another control scheme in another set-up (for example
night setback). Alternatively, they can be used by an AHU
or packaged unit OEM to identically program all their
factory tted frequency converters for dierent equipment
models within a range to have the same parameters, and
then during production/commissioning simply select a
specic set-up depending on which model within that
range the frequency converter is installed on.
The active set-up (that is the set-up in which the frequency
converter is currently operating) can be selected in
parameter 0-10 Active Set-up and is shown in the LCP. Use
[9] Multi set-up to switch between set-ups with the
frequency converter running or stopped, via digital input
or serial communication commands (for example for night
setback). If it is necessary to change setups while running,
ensure that parameter 0-12 This Set-up Linked to is
programmed as required. For most refrigeration
applications it is not necessary to program
parameter 0-12 This Set-up Linked to even if change of set-
up while running is required. However, for complex
applications, using the full exibility of the multiple setups, programming parameter 0-12 This Set-up Linked to may
be required. Using parameter 0-11 Programming Set-up, it is
possible to edit parameters within any of the set-ups while
continuing the frequency converter operation in its active
33
set-up which can be a dierent set-up to the one being
edited. Using parameter 0-51 Set-up Copy, it is possible to
copy parameter settings between the set-ups to enable
quicker commissioning if similar parameter settings are
required in dierent set-ups.
0-10 Active Set-up
Option:Function:
Select the set-up in which the frequency
converter is to operate.
Use parameter 0-51 Set-up Copy to copy a set-up
to 1 or all other set-ups. To avoid conicting
settings of the same parameter within 2
dierent set-ups, link the set-ups using
parameter 0-12 This Set-up Linked to. Stop the
frequency converter before switching between
set-ups where parameters marked notchangeable during operation have dierent
values.
Parameters which are not changeable during
operation are marked FALSE in
chapter 4 Parameter Lists.
[0]Factory
setup
[1]*Set-up 1[1] Set-up 1 to [4] Set-up 4 are the 4 parameter
[2]Set-up 2
[3]Set-up 3
[4]Set-up 4
[9]Multi Set-upIs used for remote set-up selections using digital
Cannot be changed. It contains the Danfoss
data set, and can be used as a data source
when returning the other set-ups to a known
state.
set-ups within which all parameters can be
programmed.
inputs and the serial communication port. This
set-up uses the settings from
parameter 0-12 This Set-up Linked to.
0-11 Programming Set-up
Option:Function:
Select the set-up to be edited (that is
programmed) during operation; either the
active set-up or 1 of the inactive set-ups. The
set-up number being edited is shown in the
LCP in brackets.
[0]Factory
setup
Cannot be edited, but it is useful as a data
source to return the other set-ups to a known
state.
0-11 Programming Set-up
Option:Function:
[1]Set-up 1[1] Set-up 1 to [4] Set-up 4 can be edited freely
during operation, independently of the active
set-up.
[2]Set-up 2
[3]Set-up 3
[4]Set-up 4
[9] * Active Set-upThe set-up in which the frequency converter is
operating can be edited during operation.
Editing parameters in the selected set-up
would normally be done from the LCP, but it is
also possible from any of the serial communication ports.
0-12 This Set-up Linked to
Option:Function:
Use this parameter only if a change of set-ups
is required while the motor is running. This
parameter ensures that parameters which are
not changeable during operation have the
same setting in all relevant set-ups.
To enable conict-free changes from 1 set-up to
another while the frequency converter is
running, link set-ups containing parameters
which are not changeable during operation.
The link ensures synchronizing of the notchangeable during operation parameter values
when moving from 1 set-up to another during
operation. Not changeable during operation
parameters can be identied by the label FALSE
in the parameter lists in chapter 4 ParameterLists.
The parameter 0-12 This Set-up Linked to feature
is used when [9] Multi set-up in
parameter 0-10 Active Set-up is selected. Use [9]
Multi set-up to move from 1 set-up to another
during operation while the motor runs.
For example:
Use [9] Multi set-up to shift from set-up 1 to setup 2 while the motor runs. Program parameters
in set-up 1 rst, then ensure that set-up 1 and
set-up 2 are synchronized (or linked).
Synchronization can be performed in 2 ways:
Change the edit set-up to [2] Set-up 2
•
in parameter 0-11 Programming Set-up
and set parameter 0-12 This Set-upLinked to to [1] Set-up 1. This starts the
linking (synchronizing) process.
parameter 0-50 LCP Copy, copy set-up
1 to set-up 2. Then set
parameter 0-12 This Set-up Linked to to
[2] Set-up 2. This starts the linking
process.
Illustration 3.2 Set-up Handling
After the link is complete,
parameter 0-13 Readout: Linked Set-ups reads
set-ups 1 and 2 to indicate that all notchangeable during operation parameters are now
the same in set-up 1 and set-up 2. If there are
changes to a not changeable during operation
parameter in set-up 2, for example
parameter 1-30 Stator Resistance (Rs), they are
also changed automatically in set-up 1. A
switch between set-up 1 and set-up 2 during
operation is now possible.
View a list of all the set-ups linked by
parameter 0-12 This Set-up Linked to. The parameter
has 1 index for each parameter set-up. The value
for each index shows which set-ups are linked to
that parameter set-up.
0-13 Readout: Linked Set-ups
Array [5]
Range:Function:
IndexLCP value
0{0}
1{1,2}
2{1,2}
3{3}
4{4}
Table 3.1 Set-up Link Example
0-14 Readout: Prog. Set-ups / Channel
Range:Function:
0* [-2147483648
- 2147483647]
View the setting of
parameter 0-11 Programming Set-up for each
of the 4 dierent communication channels.
When the number is shown in hex, as it is in
the LCP, each number shows 1 channel.
Numbers 1–4 show a set-up number; F
stands for the factory setting, and A stands
for an active set-up. The channels are, from
right to left: LCP, eldbus, USB, HPFB1.5.
Example: The value AAAAAA21h means that
the eldbus channel uses set-up 2 in
parameter 0-11 Programming Set-up, the LCP
uses set-up 1, and all other channels use the
active set-up.
3.2.2 0-2* LCP Display
Dene the variables shown in the LCP.
NOTICE
For information on how to write display texts, refer to:
Parameter 0-37 Display Text 1.
•
Parameter 0-38 Display Text 2.
•
Parameter 0-39 Display Text 3.
•
0-20 Display Line 1.1 Small
Option:Function:
Select a variable for display in line 1,
left position.
[37]Display Text 1Enables an individual text string to be
written for display in the LCP, or to be
read via serial communication.
[38]Display Text 2Enables an individual text string to be
written for display in the LCP, or to be
read via serial communication.
[39]Display Text 3Enables an individual text string to be
written for display in the LCP, or to be
read via serial communication.
33
[89]Date and Time
Readout
[953]Probus
Warning Word
[1397] Alert Alarm
Word
[1398] Alert Warning
Word
[1399] Alert Status
Word
[1501] Running HoursView the number of running hours of
[1502] kWh CounterView the mains power consumption in
[1580] Fan Running
Hours
[1600] Control WordView the control word sent from the
[1601] Reference [Unit] Total reference (sum of digital/analog/
[1602] Reference [%]Total reference (sum of digital/analog/
[1603] Status WordPresent status word
[1605] Main Actual
Value [%]
[1609] Custom Readout View the user-dened readouts as
[1610] Power [kW ]Actual power consumed by the motor
[1611] Power [hp]Actual power consumed by the motor
[1612] Motor VoltageVoltage supplied to the motor.
[1613] FrequencyMotor frequency, that is the output
Displays the current date and time.
Displays PROFIBUS communication
warnings.
the motor.
kWh.
frequency converter via the serial
communication port in hex code.
preset/bus/freeze reference/catch up,
and slow-down) in selected unit.
preset/bus/freeze reference/catch up,
and slow-down) in percent.
View the 2-byte word sent with the
status word to the bus master
reporting the main actual value.
dened in:
Parameter 0-30 Custom
•
Readout Unit.
Parameter 0-31 Custom
•
Readout Min Value.
Parameter 0-32 Custom
•
Readout Max Value.
in kW.
in hp.
frequency from the frequency converter
in Hz.
0-20 Display Line 1.1 Small
Option:Function:
[1614] Motor currentPhase current of the motor measured
as eective value.
[1615] Frequency [%]Motor frequency, that is the output
frequency from the frequency converter
in percent.
[1616] Torque [Nm]Present motor load as a percentage of
the rated motor torque.
[1617] Speed [RPM]Motor speed reference. Actual speed
depends on slip compensation being
used (compensation set in
parameter 1-62 Slip Compensation). If
not used, actual speed is the value
read in the display minus motor slip.
[1618] Motor ThermalThermal load on the motor, calculated
by the ETR function. See also parametergroup 1-9* Motor Temperature.
[1622] Torque [%]Shows the actual torque produced, in
percentage.
[1624] Calibrated Stator
Resistance
[1630] DC Link Voltage Intermediate circuit voltage in the
frequency converter.
[1631] System Temp.
[1632] Brake Energy /sPresent brake power transferred to an
external brake resistor.
Stated as an instant value.
[1633] Brake Energy /2
min
[1634] Heatsink Temp.Present heat sink temperature of the
[1635] Inverter Thermal Percentage load of the inverters.
[1636] Inv. Nom.
Current
[1637] Inv. Max.
Current
[1638] SL Controller
State
[1639] Control Card
Temp.
[1650] External
Reference
[1652] Feedback[Unit]Reference value from programmed
Brake power transferred to an external
brake resistor. The average power is
calculated continuously for the most
recent 120 s.
frequency converter. The cutout limit is
95 ±5 °C (203 ±9 °F); cutting back in
occurs at 70 ± 5 °C (158 ±9 °F).
Nominal current of the frequency
converter.
Maximum current of the frequency
converter.
State of the event executed by the
control.
Temperature of the control card.
Sum of the external reference as a
percentage, that is the sum of analog/
pulse/bus.