Danfoss FC 103 Programming guide

Programming Guide
VLT® Refrigeration Drive FC 103
vlt-drives.danfoss.com
Contents Programming Guide
Contents
1 Introduction
1.1.1 Frequency Converter 5
1.1.2 Input 5
1.1.3 Motor 5
1.1.4 References 6
1.1.5 Miscellaneous 6
1.2 Safety
1.3 Electrical Wiring
2 How to Program
2.1 Local Control Panel
2.1.1 How to Operate Graphical LCP (GLCP) 13
2.1.2 Quick Transfer of Parameter Settings between Multiple Frequency Converters 17
2.1.3 Parameter Set-Up 17
2.1.4 Quick Menu Mode 17
2.1.5 Function Set-ups 19
2.1.6 Main Menu Mode 21
4
5
8
10
13
13
2.1.7 Parameter Selection 21
2.1.8 Changing Data 22
2.1.9 Changing a Text Value 22
2.1.10 Changing a Group of Numeric Data Values 22
2.1.11 Value, Step-by-step 22
2.1.12 Read out and Programming of Indexed Parameters 22
2.1.13 Initialization to Default Settings 22
3 Parameter Description
3.1 Parameter Selection
3.1.1 Main Menu Structure 24
3.2 Parameters: 0-** Operation and Display
3.3 Parameters: 1-** Load and Motor
3.4 Parameters: 2-** Brakes
3.5 Parameters: 3-** Reference/Ramps
3.6 Parameters: 4-** Limits/Warnings
3.7 Parameters: 5-** Digital In/Out
3.8 Parameters: 6-** Analog In/Out
24
24
24
36
53
55
61
65
79
3.9 Parameters: 8-** Communications and Options
3.10 Parameters: 11-** FC 103 LON
3.11 Parameters: 13-** Smart Logic
3.12 Parameters: 14-** Special Functions
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 1
87
94
94
106
Contents
VLT® Refrigeration Drive FC 103
3.13 Parameters: 15-** Frequency Converter Information
3.14 Parameters: 16-** Data Readouts
3.15 Parameters: 18-** Data Readouts 2
3.16 Parameters: 20-** FC Closed Loop
3.17 Parameters: 21-** Extended Closed Loop
3.18 Parameters: 22-** Application Functions
3.19 Parameters: 23-** Time-based Functions
3.20 Parameters: 25-** Pack Controller
3.21 Parameters: 26-** Analog I/O Option MCB 109
3.22 Parameters: 28-** Compressor Functions
3.23 Parameters: 29-** Application Functions
3.24 Parameters: 30-** Special Features
4 Parameter Lists
4.1 Parameter Options
4.1.1 Default Settings 196
4.1.2 0-** Operation and Display 197
4.1.3 1-** Load/Motor 198
113
118
125
127
137
145
159
170
180
187
191
192
196
196
4.1.4 2-** Brakes 199
4.1.5 3-** Reference/Ramps 200
4.1.6 4-** Limits/Warnings 201
4.1.7 5-** Digital In/Out 201
4.1.8 6-** Analog In/Out 203
4.1.9 8-** Communication and Options 204
4.1.10 11-** FC 103 LON 205
4.1.11 13-** Smart Logic Controller 205
4.1.12 14-** Special Functions 206
4.1.13 15-** FC Information 207
4.1.14 16-** Data Readouts 208
4.1.15 18-** Info & Readouts 210
4.1.16 20-** FC Closed Loop 210
4.1.17 21-** Ext. Closed Loop 211
4.1.18 22-** Application Functions 212
4.1.19 23-** Time Based Funtions 214
4.1.20 25-** Pack Controller 214
4.1.21 26-** Analog I/O Option MCB 109 216
4.1.22 28-** Compressor Functions 217
4.1.23 29-** Compressor Functions 2 217
4.1.24 30-** Special Features 218
5 Troubleshooting
2 Danfoss A/S © 05/2016 All rights reserved. MG16H202
219
Contents Programming Guide
5.1 Status Messages
Index
219
5.1.1 Alarms and Warnings 219
5.1.2 Alarm Words 222
5.1.3 Warning Words 223
5.1.4 Extended Status Words 224
5.1.5 Fault Messages 225
229
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 3
Introduction
VLT® Refrigeration Drive FC 103
11
1 Introduction
VLT® Refrigeration Drive
FC 103
This guide can be used with all VLT® Refrigeration Drive FC 103
frequency converters with software version 1.x.
The actual software version number can be read from
parameter 15-43 Software Version.
Table 1.1 Software Version
The following symbols are used in this manual.
WARNING
Indicates a potentially hazardous situation which could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that may result in damage to equipment or property.
60° AVM 60° asynchronous vector modulation A Ampere/AMP AC Alternating current AD Air discharge AEO Automatic energy optimization AI Analog input AIC Ampere interrupting current AMA Automatic motor adaptation AWG American wire gauge °C CB Circuit breaker CD Constant discharge CDM Complete drive module: The frequency converter,
CE European Conformity (European safety standards) CM Common mode CT Constant torque DC Direct current DI Digital input
Degrees Celsius
feeding section, and auxiliaries
DM Dierential mode D-TYPE Drive dependent EMC Electromagnetic compatibility EMF Electromotive force ETR Electronic thermal relay °F f
JOG
f
M
f
MAX
f
MIN
f
M,N
FC Frequency converter
Hiperface®Hiperface® is a registered trademark by Stegmann HO High overload hp Horse power HTL HTL encoder (10–30 V) pulses - High-voltage
Hz Hertz I
INV
I
LIM
I
M,N
I
VLT,MAX
I
VLT,N
kHz Kilohertz LCP Local control panel lsb Least signicant bit m Meter mA Milliampere MCM Mille circular mil MCT Motion control tool mH Inductance in milli Henry mm Millimeter ms Millisecond msb Most signicant bit
η
VLT
nF Capacitance in nano Farad NLCP Numerical local control panel Nm Newton meter NO Normal overload n
s
Online/ Oine
Parameters P
br,cont.
PCB Printed circuit board PCD Process data
Degrees Fahrenheit Motor frequency when jog function is activated Motor frequency Maximum output frequency, the frequency converter applies on its output Minimum motor frequency from the frequency converter Nominal motor frequency
transistor logic
Rated inverter output current Current limit Nominal motor current Maximum output current Rated output current supplied by the frequency converter
Eciency of the frequency converter dened as ratio between power output and power input
Synchronous motor speed Changes to online parameters are activated immediately after the data value is changed
Rated power of the brake resistor (average power during continuous braking)
4 Danfoss A/S © 05/2016 All rights reserved. MG16H202
Introduction Programming Guide
PDS Power drive system: A CDM and a motor PELV Protective extra low voltage P
m
P
M,N
PM motor Permanent magnet motor Process PID PID (proportional integrated dierential) regulator
R
br,nom
RCD Residual current device Regen Regenerative terminals R
min
RMS Root mean square RPM Revolutions per minute R
rec
s Second SCCR Short circuit current rating SFAVM Stator ux-oriented asynchronous vector
STW Status word SMPS Switch mode power supply THD Total harmonic distortion T
LIM
TTL TTL encoder (5 V) pulses - transistor transistor
U
M,N
UL Underwriters Laboratories (US organization for the
V Volts VT Variable torque
VVC+
Frequency converter nominal output power as high overload (HO) Nominal motor power
that maintains the speed, pressure, temperature, and so on Nominal resistor value that ensures a brake power on the motor shaft of 150/160% for 1 minute
Minimum permissible brake resistor value by frequency converter
Recommended brake resistor resistance of Danfoss brake resistors
modulation
Torque limit
logic Nominal motor voltage
safety certication)
Voltage vector control plus
and electrical installation of the frequency converter.
VLT® Refrigeration Drive FC 103 Design Guide holds
all technical information about the frequency converter, customer design, and applications.
®
Refrigeration Drive FC 103 Programming Guide
VLT
provides information on how to program and includes complete parameter descriptions.
MCT 10 Set-up Software Operating Instructions
enables the user to congure the frequency converter from a Windows-based PC environment.
VLT® HVAC Drive FC 102/VLT® AQUA Drive FC 202
Metasys N2, Operating Instructions.
1.1 Denitions
1.1.1 Frequency Converter
I
VLT,MAX
Maximum output current.
I
VLT,N
Rated output current supplied by the frequency converter.
U
VLT,MAX
Maximum output voltage.
1.1.2 Input
Control command
Start and stop the connected motor with LCP and digital inputs. Functions are divided into 2 groups.
Functions in group 1 have higher priority than functions in group 2.
1 1
Table 1.2 Abbreviations
Conventions
Numbered lists indicate procedures.
Group 1 Reset, coast stop, reset and coast stop, quick stop,
DC brake, stop, the [OFF] key.
Group 2 Start, pulse start, reversing, start reversing, jog,
freeze output.
Bullet lists indicate other information and description of illustrations.
Table 1.3 Function Groups
Italicized text indicates:
Cross-reference.
Link.
Footnote.
Parameter name, parameter group name,
parameter option.
All dimensions in drawings are in mm (in). * Indicates a default setting of a parameter.
®
VLT
Refrigeration Drive FC 103 Operating
Instructions provides information on mechanical
1.1.3 Motor
Motor running
Torque generated on output shaft and speed from 0 RPM to maximum speed on motor.
f
JOG
Motor frequency when the jog function is activated (via digital terminals).
f
M
Motor frequency.
f
MAX
Maximum motor frequency.
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 5
175ZA078.10
Pull-out
rpm
Torque
Introduction
VLT® Refrigeration Drive FC 103
11
f
MIN
1.1.4 References
Minimum motor frequency.
f
M,N
Rated motor frequency (nameplate data).
I
M
Motor current (actual).
I
M,N
Rated motor current (nameplate data).
n
M,N
Nominal motor speed (nameplate data).
n
s
Synchronous motor speed.
2 × par . 1 23 × 60s
ns=
par . 1 39
n
slip
Motor slip.
P
M,N
Rated motor power (nameplate data in kW or hp).
T
M,N
Rated torque (motor).
U
M
Instant motor voltage.
U
M,N
Analog reference
A signal transmitted to the analog inputs 53 or 54 (voltage or current).
Binary reference
A signal transmitted to the serial communication port.
Preset reference
A dened preset reference to be set from -100% to +100% of the reference range. Selection of 8 preset references via the digital terminals.
Pulse reference
A pulse frequency signal transmitted to the digital inputs (terminal 29 or 33).
Ref
MAX
Determines the relationship between the reference input at 100% full scale value (typically 10 V, 20 mA) and the resulting reference. The maximum reference value is set in parameter 3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input at 0% value (typically 0 V, 0 mA, 4 mA) and the resulting reference. The minimum reference value is set in parameter 3-02 Minimum Reference.
Rated motor voltage (nameplate data).
Break-away torque
1.1.5 Miscellaneous
Illustration 1.1 Break-away Torque
η
VLT
The eciency of the frequency converter is dened as the ratio between the power output and the power input.
Start-disable command
A stop command belonging to Group 1 control commands
- see Table 1.3.
Stop command
A stop command belonging to Group 1 control commands
- see Table 1.3.
Analog inputs
The analog inputs are used for controlling various functions of the frequency converter. There are 2 types of analog inputs: Current input, 0–20 mA, and 4–20 mA Voltage input, -10 V DC to +10 V DC.
Analog outputs
The analog outputs can supply a signal of 0–20 mA, 4–20 mA.
Automatic motor adaptation, AMA
AMA algorithm determines the electrical parameters for the connected motor at standstill.
CT characteristics
Constant torque characteristics used for all applications such as conveyor belts, displacement pumps, and cranes.
Digital inputs
The digital inputs can be used for controlling various functions of the frequency converter.
Digital outputs
The frequency converter features 2 solid-state outputs that can supply a 24 V DC (maximum 40 mA) signal.
DSP
Digital signal processor.
6 Danfoss A/S © 05/2016 All rights reserved. MG16H202
Introduction Programming Guide
ETR
Electronic thermal relay is a thermal load calculation based on present load and time. Its purpose is to estimate the motor temperature.
Hiperface
Hiperface® is a registered trademark by Stegmann.
Initializing
If initializing is carried out (parameter 14-22 Operation Mode), the frequency converter returns to the default
setting.
Intermittent duty cycle
An intermittent duty rating refers to a sequence of duty cycles. Each cycle consists of an on-load and an o-load period. The operation can be either periodic duty or non­periodic duty.
LCP
The local control panel makes up a complete interface for control and programming of the frequency converter. The control panel is detachable and can be installed up to 3 m (10 ft) from the frequency converter, that is, in a front panel with the installation kit option.
NLCP
Numerical local control panel interface for control and programming of the frequency converter. The display is numerical and the panel is used to show process values. The NLCP has no storage and copy functions.
lsb
Least signicant bit.
msb
Most signicant bit.
MCM
Short for mille circular mil, an American measuring unit for cable cross-section. 1 MCM=0.5067 mm2.
Online/oine parameters
Changes to online parameters are activated immediately after the data value is changed. Press [OK] to activate changes to o-line parameters.
Process PID
The PID control maintains the required speed, pressure, temperature, and so on, by adjusting the output frequency to match the varying load.
PCD
Process control data.
Power cycle
Switch o the mains until display (LCP) is dark – then turn power on again.
Pulse input/incremental encoder
An external, digital pulse transmitter used for feeding back information on motor speed. The encoder is used in applications where great accuracy in speed control is required.
®
RCD
Residual current device.
Set-up
Save parameter settings in 4 set-ups. Change between the 4 parameter set-ups and edit 1 set-up, while another set­up is active.
SFAVM
Switching pattern called stator ux-oriented asynchronous vector modulation (parameter 14-00 Switching Pattern).
Slip compensation
The frequency converter compensates for the motor slip by giving the frequency a supplement that follows the measured motor load keeping the motor speed almost constant.
SLC
The SLC (smart logic control) is a sequence of user-dened actions executed when the associated user-dened events are evaluated as true by the SLC. (See chapter 3.11 Parameters: 13-** Smart Logic).
STW
Status word.
FC standard bus
Includes RS485 bus with FC protocol or MC protocol. See parameter 8-30 Protocol.
THD
Total harmonic distortion states the total contribution of harmonic.
Thermistor
A temperature-dependent resistor placed on the frequency converter or the motor.
Trip
A state entered in fault situations, for example if the frequency converter is subject to an overtemperature or when the frequency converter is protecting the motor, process, or mechanism. The frequency converter prevents a restart until the cause of the fault has disappeared. To cancel the trip state, restart the frequency converter. Do not use the trip state for personal safety.
Trip lock
The frequency converter enters this state in fault situations to protect itself. The frequency converter requires physical intervention, for example when there is a short circuit on the output. A trip lock can only be canceled by discon­necting mains, removing the cause of the fault, and reconnecting the frequency converter. Restart is prevented until the trip state is canceled by activating reset or, sometimes, by being programmed to reset automatically. Do not use the trip lock state for personal safety.
VT characteristics
Variable torque characteristics used for pumps and fans.
1 1
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 7
Introduction
VLT® Refrigeration Drive FC 103
11
VVC
+
1.2
Safety
If compared with standard voltage/frequency ratio control, voltage vector control (VVC+) improves the dynamics and the stability, both when the speed reference is changed and in relation to the load torque.
60° AVM
60° asynchronous vector modulation (parameter 14-00 Switching Pattern).
Power factor
The power factor is the relation between I1 and I
Powerfactor = 
3xUxI1cosϕ
3xUxI
RMS
RMS
.
The power factor for 3-phase control:
Powerfactor = 
I1xcosϕ1
I
RMS
 = 
I
RMS
I
1
sincecosϕ1 =  1
The power factor indicates to which extent the frequency converter imposes a load on the mains supply. The lower the power factor, the higher the I
RMS
for the
same kW performance.
2
2
2
I
=  I
 + I
RMS
 + I
1
5
 + .. + I
7
2
n
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning indicator lights are o. Failure to wait the specied time after power has been removed before performing service or repair work, could result in death or serious injury.
1. Stop the motor.
2. Disconnect AC mains, permanent magnet type motors, and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
3. Wait for the capacitors to discharge fully, before performing any service or repair work. The duration of waiting time is specied in Table 1.4.
In addition, a high-power factor indicates that the dierent harmonic currents are low.
Voltage [V] Minimum waiting time (minutes)
The DC coils in the frequency converters produce a high­power factor, which minimizes the imposed load on the mains supply.
Target position
The nal target position specied by positioning commands. The prole generator uses this position to calculate the speed prole.
Commanded position
The actual position reference calculated by the prole generator. The frequency converter uses the commanded
4 7 15
200–240 0.25–3.7 kW
(0.34–5 hp)
380–500 0.25–7.5 kW
(0.34–10 hp)
525–600 0.75–7.5 kW
(1–10 hp)
525–690 1.5–7.5 kW
5.5–37 kW
(7.5–50 hp)
11–75 kW
(15–100 hp)
11–75 kW
(15–100 hp)
(2–10 hp)
(15–100 hp)
11–75 kW
position as setpoint for position PI.
Actual position
The actual position from an encoder, or a value that the motor control calculates in open loop. The frequency converter uses the actual position as feedback for position PI.
Position error
Position error is the dierence between the actual position and the commanded position. The position error is the input for the position PI controller.
Position unit
The physical unit for position values.
Voltage
[V]
380–500 90–250 kW
525–690 55–315 kW (frame size D)
Table 1.4 Discharge Time
Power Minimum waiting
time (minutes)
20 (125–350 hp) 315–800 kW (450–1075 hp)
(75–450 hp) 355–1200 kW (475–1600 hp)
40
20
30
Safety regulations
Disconnect mains supply to the frequency
converter whenever repair work is to be carried out. Check that the mains supply has been disconnected and that the necessary time has elapsed before removing motor and mains supply
8 Danfoss A/S © 05/2016 All rights reserved. MG16H202
Introduction Programming Guide
plugs. For information about the discharge time, see Table 1.4.
[O] does not disconnect the mains supply and
must not be used as a safety switch.
Ground the equipment properly, protect the user
against supply voltage, and protect the motor against overload in accordance with applicable national and local regulations.
The ground leakage current exceeds 3.5 mA.
Ensure correct grounding of the equipment by a certied electrical installer.
Do not remove the plugs for the motor and
mains supply while the frequency converter is connected to mains. Check that the mains supply has been disconnected and that the necessary time has elapsed before removing motor and mains plugs.
The frequency converter has more voltage
sources than L1, L2, and L3, when load sharing (linking of DC intermediate circuit) or external 24 V DC is installed. Check that all voltage sources have been disconnected and that the necessary time has elapsed before commencing repair work. For information about the discharge time, see Table 1.4.
NOTICE
When using the Safe Torque O, always follow the
instructions in VLT® Frequency Converters - Safe Torque
O Operating Instructions.
NOTICE
Hazardous situations must be identied by the machine builder/integrator who is responsible for considering the necessary preventive means. More monitoring and protective devices may be included, always according to valid national safety regulations, for example, law on mechanical tools and regulations for the prevention of accidents.
Protection mode
Once a hardware limit on motor current or DC-link voltage is exceeded, the frequency converter enters the protection mode. Protection mode means a change of the PWM modulation strategy and a low switching frequency to minimize losses. This continues for 10 s after the last fault and increases the reliability and the robustness of the frequency converter while re-establishing full control of the motor. Protection mode can be disabled by setting parameter 14-26 Trip Delay at Inverter Fault to 0, which means that the frequency converter trips immediately if 1 of the hardware limits is exceeded.
NOTICE
Disabling protection mode in hoisting applications (parameter 14-26 Trip Delay at Inverter Fault = 0) is recommended.
1 1
NOTICE
Control signals from, or internally within, the frequency converter may in rare cases be activated in error, be delayed, or fail to occur entirely. When used in situations where safety is critical, for example, when controlling the electromagnetic brake function of a hoist application, these control signals must not be relied on exclusively.
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 9
*
91 (L1) 92 (L2) 93 (L3)
PE
88 (-) 89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4–20 mA
12 (+24 V OUT)
13 (+24 V OUT)
18 (D IN)
20 (COM D IN)
15 mA 200 mA
(U) 96
(V) 97 (W) 98 (PE) 99
(COM A OUT) 39
(A OUT) 42
0/4–20 mA
03
0–10 V DC
+10 V DC
0-10 V DC
0/4–20 mA
240 V AC, 2 A
24 V DC
02
01
05
04
06
240 V AC, 2 A
24 V (NPN) 0 V (PNP)
0 V (PNP)
24 V (NPN)
19 (D IN)
24 V (NPN) 0 V (PNP)
27
24 V
0 V
(D IN/OUT)
0 V (PNP)
24 V (NPN)
(D IN/OUT)
0 V
24 V
29
24 V (NPN) 0 V (PNP)
0 V (PNP)
24 V (NPN)
33 (D IN)
32 (D IN)
1 2
ON
S201
ON
21
S202
ON=0–20 mA OFF=0–10 V
95
400 V AC, 2 A
P 5-00
(R+) 82
(R-) 81
37 (D IN)
+ - + -
130BA544.13
(P RS485) 68
(N RS485) 69
(COM RS485) 61
0V
5 V
S801
RS485
RS485
21
ON
S801
3-phase power
input
DC bus
Switch mode power supply
Motor
Analog output
Interface
Relay1
Relay2
ON=Terminated OFF=Open
Brake resistor
(NPN) = Sink
(PNP) = Source
Introduction
VLT® Refrigeration Drive FC 103
11
1.3 Electrical Wiring
Illustration 1.2 Basic Wiring Schematic Drawing
A=Analog, D=Digital Terminal 37 is used for Safe Torque O. For Safe Torque O installation instructions, refer to the VLT® Frequency Converters -
Safe Torque O Operating Instructions.
Very long control cables and analog signals may in rare cases, and depending on installation, result in 50/60 Hz ground loops due to noise from mains supply cables.
If this occurs, it may be necessary to break the shield or insert a 100 nF capacitor between shield and enclosure.
Connect the digital and analog inputs and outputs separately to the common inputs (terminals 20, 55, and 39) of the frequency converter to avoid ground currents from both groups to digital input may disturb the analog input signal.
10 Danfoss A/S © 05/2016 All rights reserved. MG16H202
aect other groups. For example, switching on the
12 13 18 19 27 29 32 33 20 37
+24 VDC
0 VDC
130BT106.10
PNP (Source)
Digital input wiring
NPN (Sink) Digital input wiring
12 13 18 19 27 29 32 33 20 37
+24 VDC
0 VDC
130BT107.11
130BA681.10
12 13 18 37
130BA155.12
322719 29 33 20
P 5-12 [0]
P 5-10 [8]
Start/Stop
+24V
Speed
Safe Stop
Start/Stop [18]
Introduction Programming Guide
Input polarity of control terminals
Illustration 1.3 PNP (Source)
1 1
Illustration 1.5 Grounding of Shielded/Armored Control Cables
Illustration 1.4 NPN (Sink)
NOTICE
Use shielded/armored control cables.
1.3.1 Start/Stop
Terminal 18 = parameter 5-10 Terminal 18 Digital Input [8] Start. Terminal 27 = parameter 5-12 Terminal 27 Digital Input [0] No operation (Default [2] Coast inverse). Terminal 37 = Safe Torque O (where available).
Illustration 1.6 Start/Stop
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 11
12 13 18 37
130BA156.12
322719 29 33 20
P 5 - 12 [6]
P 5 - 10[9]
+24V
Speed
Start Stop inverse Safe Stop
Start (18)
Start (27)
12
18
27
29
32
37
+24V
Par. 5-10
Par. 5-12
Par. 5-13
Par. 5-14
130BA021.12
130BA154.11
555039 42 53 54
Speed RPM P 6-15
1 kΩ
+10V/30mA
Ref. voltage P 6-11 10V
Introduction
VLT® Refrigeration Drive FC 103
11
1.3.2 Pulse Start/Stop
Terminal 18 = parameter 5-10 Terminal 18 Digital Input, [9] Latched start. Terminal 27 = parameter 5-12 Terminal 27 Digital Input, [6] Stop inverse. Terminal 37 = Safe Torque O (where available).
Illustration 1.8 Speed up/Speed down
1.3.4 Potentiometer Reference
Voltage reference via a potentiometer
Reference source 1 = [1] Analog input 53 (default).
Terminal 53, low voltage = 0 V.
Terminal 53, high voltage = 10 V.
Terminal 53, low reference/feedback = 0 RPM.
Terminal 53, high reference/feedback = 1500 RPM.
Switch S201 = OFF (U)
Illustration 1.7 Pulse Start/Stop
1.3.3 Speed up/Speed Down
Terminals 29/32 = Speed up/Speed down
Terminal 18 = Parameter 5-10 Terminal 18 Digital Input [9] Start (default).
Terminal 27 = Parameter 5-12 Terminal 27 Digital Input [19] Freeze reference.
Terminal 29 = Parameter 5-13 Terminal 29 Digital Input [21] Speed up.
Terminal 32 = Parameter 5-14 Terminal 32 Digital Input [22] Speed down.
NOTICE
Terminal 29 only in FC x02 (x=series type).
Illustration 1.9 Potentiometer Reference
12 Danfoss A/S © 05/2016 All rights reserved. MG16H202
Auto
on
Reset
Hand
on
O
Status
Quick Menu
Main
Menu
Alarm
Log
Back
Cancel
Info
OK
Status
1(0)
1234rpm 10,4A 43,5Hz
Run OK
43,5Hz
On
Alarm
Warn.
130BA018.13
1
2
3
4
b
a
c
How to Program Programming Guide
2 How to Program
2.1 Local Control Panel
2.1.1 How to Operate Graphical LCP (GLCP)
The GLCP is divided into 4 functional groups:
1. Graphical display with status lines.
2. Menu keys and indicator lights (LEDs) - selecting mode, changing parameters, and switching between display functions.
3. Navigation keys and indicator lights (LEDs).
4. Operation keys and indicator lights (LEDs).
Graphical display
The LCD display is backlit with a total of 6 alpha-numeric lines. All data is shown on the LCP, which can show up to 5 operating variables while in Status mode.
Display lines:
a. Status line
Status messages displaying icons and graphics.
b. Line 1–2
Operator data lines displaying data and variables dened or selected by the user. Press [Status] to add 1 extra line.
c. Status line
Status messages displaying text.
2 2
Illustration 2.1 LCP
The display is divided into 3 sections: Top section
(a) shows the status when in Status mode, or up to 2 variables when not in Status mode, and in the case of alarm/warning.
The number of the active set-up (selected as the active set-up in parameter 0-10 Active Set-up) is shown. When programming in another set-up than the active set-up, the number of the set-up being programmed appears to the right in brackets.
Middle section
(b) shows up to 5 variables with related unit, regardless of status. In case of alarm/warning, the warning is shown instead of the variables.
Bottom section
(c) always shows the state of the frequency converter in status mode.
Press [Status] to toggle between 3 status readout displays.
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 13
1.1
2
3
1.3
1.2
130BP041.10
799 RPM
Auto Remote Ramping
1 (1)
36.4 kw7.83 A
0.000
53.2 %
Status
1.1
1.2
2
1.3
130BP062.10
207RPM
Auto Remote Running
1 (1)
24.4 kW5.25A
6.9
Hz
Status
130BP063.10
778 RPM
Auto Remote Running
1 (1)
4.0 kW0.86 A
State: 0 o 0 (o) When: ­Do: -
Status
Top section
Middle section
Bottom section
Status
43 RPM
1.4 Hz
Auto Remote Running
! Pwr.card temp (W29)
2.9%
5.44 A 25.3kW
1(1)
130BP074.10
!
How to Program
VLT® Refrigeration Drive FC 103
Operating variables with dierent formatting are shown in each status screen.
22
Several values or measurements can be linked to each of the shown operating variables.
Dene the values/measurements to be shown via:
Parameter 0-20 Display Line 1.1 Small
Parameter 0-21 Display Line 1.2 Small
Parameter 0-22 Display Line 1.3 Small
Parameter 0-23 Display Line 2 Large
Parameter 0-24 Display Line 3 Large
which can be accessed via [Quick Menu], Q3 Function Set­ups, Q3-1 General Settings, Q3-13 Display Settings.
Each value/measurement readout parameter selected in
Illustration 2.3 Example of Status Display II
Status display III
This state displays the event and action of the smart logic control.
parameter 0-20 Display Line 1.1 Small to parameter 0-24 Display Line 3 Large has its own scale and
number of digits after a possible decimal point. Larger numeric values are shown with few digits after the decimal point. Ex.: Current readout
5.25 A; 15.2 A 105 A.
Status display I
Illustration 2.4 Example of Status Display III
This readout state is standard after start-up or initialization. Press [INFO] to obtain information about the value/ measurement linked to the shown operating variables (1.1,
1.2, 1.3, 2, and 3). See the operating variables shown in the display in
Display contrast adjustment
Press [Status] and [▲] for darker display. Press [Status] and [▼] for brighter display.
Illustration 2.2. 1.1, 1.2, and 1.3 are shown in small size. 2 and 3 are shown in medium size.
Illustration 2.5 Display Sections
Illustration 2.2 Example of Status Display I
Indicator lights (LEDs)
If certain threshold values are exceeded, the alarm and/or warning LED lights up. A status and alarm text appear in
Status display II
See the operating variables (1.1, 1.2, 1.3, and 2) shown in the display in Illustration 2.3. In the example, speed, motor current, motor power, and frequency are selected as variables in the rst and second lines.
1.1, 1.2, and 1.3 are shown in small size. 2 is shown in large size.
14 Danfoss A/S © 05/2016 All rights reserved. MG16H202
the display. The On LED is activated when the frequency converter receives power from mains voltage, a DC bus terminal, or a 24 V external supply. At the same time, the backlight is on.
Green LED/On: Control section is working.
Yellow LED/Warn.: Indicates a warning.
Flashing Red LED/Alarm: Indicates an alarm.
On
Warn.
Alarm
130BP044.10
130BP045.10
Status
Quick Menu
Main
Menu
Alarm
Log
How to Program Programming Guide
Illustration 2.6 Indicator Lights
GLCP keys Menu keys
The menu keys are divided into functions. The keys below the display and indicator lights are used for parameter set­up, including selection of display indication during normal operation.
Illustration 2.7 Menu Keys
Most VAV and CAV supply and return fans.
Cooling tower fans.
Primary, secondary, and condenser water pumps.
Other pump, fan, and compressor applications.
Among other features, it also includes parameters for selecting which variables to display in the LCP:
Digital preset speeds.
Scaling of analog references.
Closed-loop single-zone and multi-zone
applications.
Specic functions related to fans, pumps, and
compressors.
The Quick Menu parameters can be accessed immediately unless a password has been created via:
Parameter 0-60 Main Menu Password.
Parameter 0-61 Access to Main Menu w/o Password.
Parameter 0-65 Personal Menu Password.
Parameter 0-66 Access to Personal Menu w/o
Password.
It is possible to switch directly between Quick Menu mode and Main Menu mode.
2 2
[Status]
[Status] indicates the status of the frequency converter and/or the motor.
3 dierent readouts can be selected by pressing the [Status] key:
5-line readouts.
4-line readouts.
Smart logic control.
Press [Status] to select the display mode or for changing back to Display mode from either Quick Menu mode, Main Menu mode, or Alarm mode. Also press [Status] to toggle between single or double readout mode.
[Quick Menu]
[Quick Menu] allows quick set-up of the frequency converter. The most common functions can be programmed here.
The Quick Menu consists of:
My personal menu.
Quick set-up.
Function set-up.
Changes made.
Loggings.
The Function Set-up provides quick and easy access to all parameters required for most applications including:
[Main Menu]
Press [Main Menu] to program all parameters. The main menu parameters can be accessed immediately unless a password has been created via:
Parameter 0-60 Main Menu Password.
Parameter 0-61 Access to Main Menu w/o Password.
Parameter 0-65 Personal Menu Password.
Parameter 0-66 Access to Personal Menu w/o
Password.
For most applications, it is not necessary to access the main menu parameters. Instead, the Quick Menu, Quick Set- up and Function Set-up provide the simplest and quickest access to the most required parameters. It is possible to switch directly between Main Menu mode and Quick Menu mode. Parameter shortcut can be carried out by pressing [Main Menu] for 3 s. The parameter shortcut allows direct access to any parameter.
[Alarm Log]
[Alarm Log] displays an alarm list of the 10 most recent alarms (numbered A1-A10). To obtain more details about an alarm, press the navigation keys to manoeuvre to the alarm number and press [OK]. Information is shown about the condition of the frequency converter before it enters the alarm mode.
The [Alarm Log] key on the LCP allows access to both alarm log and maintenance log.
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 15
B
a
c
k
C
a
n
c
e
l
I
n
f
o
130BT117.10
OK
Back
Info
Warn
Alarm
On
Cancel
130BP046.10
Hand
on
O
Auto
on
Reset
How to Program
VLT® Refrigeration Drive FC 103
[Back]
[Back] reverts to the previous step or layer in the navigation structure.
Operation keys
Operation keys for local control are found at the bottom of the control panel.
22
Illustration 2.8 Back Key
Illustration 2.12 Operation Keys
[Cancel]
[Cancel] cancels the last change or command as long as the display has not been changed.
Illustration 2.9 Cancel Key
[Info]
[Info] displays information about a command, parameter, or function in any display window. [Info] provides detailed information when needed. Exit Info mode by pressing either [Info], [Back], or [Cancel].
Illustration 2.10 Info Key
[Hand On]
[Hand On] enables control of the frequency converter via the GLCP. [Hand On] also starts the motor and allows entering the motor speed data with the navigation keys. The key can be selected as [1] Enable or [0] Disable via parameter 0-40 [Hand on] Key on LCP.
The following control signals are still active when [Hand On] is activated:
[Hand On] - [O] - [Auto On].
Reset.
Coasting stop inverse.
Reversing.
Set-up select lsb - Set-up select msb.
Stop command from serial communication.
Quick stop.
DC brake.
Navigation Keys
The 4 navigation keys are used to navigate between the dierent options available in the Quick Menu, Main Menu, and Alarm Log. Press the keys to move the cursor.
[OK]
Press [OK] to select a parameter marked by the cursor and for enabling the change of a parameter.
Illustration 2.11 Navigation Keys
NOTICE
External stop signals activated with control signals or a
eldbus override a start command via the LCP.
[O]
[O] stops the connected motor. The key can be selected as [1] Enabled or [0] Disabled via parameter 0-41 [O] Key on LCP. If no external stop function is selected, and the [O] key is inactive, the motor can only be stopped by discon­necting the mains supply.
[Auto On]
[Auto On] enables the frequency converter to be controlled via the control terminals and/or serial communication. When a start signal is applied on the control terminals and/or the bus, the frequency converter starts. The key can be selected as [1] Enabled or [0] Disabled via parameter 0-42 [Auto on] Key on LCP.
16 Danfoss A/S © 05/2016 All rights reserved. MG16H202
Auto
on
Reset
Hand
on
O
Status
Quick Menu
Main
Menu
Alarm
Log
Back
Cancel
Info
OK
On
Alarm
Warn.
130BA027.10
How to Program Programming Guide
NOTICE
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the control keys [Hand On] – [Auto On].
[Reset]
Press [Reset] to reset the frequency converter after an alarm (trip). It can be selected as [1] Enable or [0] Disable via parameter 0-43 [Reset] Key on LCP.
The parameter shortcut can be carried out by pressing the [Main Menu] key for 3 s. The parameter shortcut allows direct access to any parameter.
2.1.2 Quick Transfer of Parameter Settings between Multiple Frequency Converters
Once the set-up of a frequency converter is complete, store the data in the LCP or on a PC via MCT 10 Set-up Software.
All parameter settings are now stored in the LCP indicated by the progress bar. When 100% is reached, press [OK].
Connect the LCP to another frequency converter and copy the parameter settings to this frequency converter as well.
Data transfer from LCP to frequency converter
NOTICE
Stop the motor before performing this operation.
To transfer the data from the LCP to the frequency converter:
1. Go to parameter 0-50 LCP Copy.
2. Press the [OK] key.
3. Select [2] All from LCP.
4. Press the [OK] key.
The parameter settings stored in the LCP are now transferred to the frequency converter indicated by the progress bar. When 100% is reached, press [OK].
2.1.3 Parameter Set-Up
The frequency converter can be used for practically all assignments, thus oering a signicant number of parameters. The series oers a choice between 2 programming modes - the Quick Menu mode and the Main Menu mode. The Main Menu provides access to all parameters. The Quick Menu takes the user through a few parameters making it possible to program the majority of applications. Regardless of the programming mode, parameters can be changed in both Quick Menu mode and in Main Menu mode.
2 2
2.1.4 Quick Menu Mode
Parameter data
The graphical display (GLCP) provides access to all parameters listed in the Quick Menu. The numeric display (NLCP) only provides access to the Quick Set-up parameters.
To set parameters pressing [Quick Menu] - enter or change
Illustration 2.13 LCP
Data storage in LCP
NOTICE
Stop the motor before performing this operation.
To store the data in the LCP:
1. Go to parameter 0-50 LCP Copy.
2. Press the [OK] key.
3. Select [1] All to LCP.
4. Press the [OK] key.
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 17
parameter data or settings in accordance with the following procedure:
1. Press [Quick Menu].
2.
Press [▲] or [▼] to nd the parameter to change.
3. Press [OK].
4.
Press [▲] or [▼] to select the correct parameter setting.
5. Press [OK].
6. To move to a dierent digit within a parameter setting, use the [◀] and [▶].
130BP064.10
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
40.0% 4.84 A 1(1)
Quick Menus
How to Program
VLT® Refrigeration Drive FC 103
7. Highlighted area indicates digit selected for change.
22
8. Press [Cancel] to disregard change, or press [OK] to accept change and enter the new setting.
Example of changing parameter data
Assume that parameter 22-60 Broken Belt Function is set to [0] O. To monitor the fan-belt condition, non-broken or
broken, follow this procedure:
1. Press [Quick Menu].
2.
Press [▼] to select Function Set-ups.
3. Press [OK].
4.
Press [▼] to select Application Settings.
5. Press [OK].
6. Press [OK] again for Fan Functions.
7. Press [OK] to select Broken Belt Function.
8.
Press [▼], to select [2] Trip.
Example of using the quick set-up
To set the ramp-down time to 100 s, follow this procedure:
1. Select Quick Set-up. Parameter 0-01 Language in Quick Set-up appears.
2.
Press [▼] repeatedly until parameter 3-42 Ramp 1 Ramp Down Time appears with the default setting of 20 s.
3. Press [OK].
4.
Press [◀] to highlight the third digit before the comma.
5.
Change 0 to 1 by pressing [▲].
6.
Press [▶] to highlight the digit 2.
7.
Change 2 to 0 by pressing [▼].
8. Press [OK].
The new ramp-down time is now set to 100 s.
If a broken fan belt is detected, the frequency converter trips.
Select Q1 My Personal Menu to display personal parameters
For example, an AHU or pump OEM may have pre­programmed personal parameters to be in My Personal
Illustration 2.14 Quick Menu View
Menu during factory commissioning to make on-site
commissioning/ne-tuning simpler. These parameters are selected in parameter 0-25 My Personal Menu. Up to 20 dierent parameters can be programmed in this menu.
Select Changes Made for information about:
The last 10 changes. Press [▲] and [▼] to scroll
between the last 10 changed parameters.
The changes made since default setting.
Loggings
Loggings show information about the display line readouts. The information is shown as graphs. Only display parameters selected in parameter 0-20 Display Line 1.1 Small and parameter 0-24 Display Line 3 Large can be viewed. Up to 120 samples can be stored in the memory for later reference.
Quick set-up
Ecient parameter set-up for refrigeration applications
The parameters can easily be set up for most refrigeration applications only by using the Quick Set-up. After pressing [Quick Menu], the dierent options in the Quick Menu are listed. See also Illustration 2.14.
Access the 18 most important set-up parameters of the frequency converter via Quick Set-up. After programming, the frequency converter is ready for operation. The 18 Quick Set-up parameters are shown in Table 2.1.
Parameter [Units]
Parameter 0-01 Language – Parameter 1-03 Torque Characteristics – Parameter 1-20 Motor Power [kW ] [kW] Parameter 1-21 Motor Power [HP] [hp] Parameter 1-22 Motor Voltage [V] Parameter 1-23 Motor Frequency [Hz] Parameter 1-24 Motor Current [A] Parameter 1-25 Motor Nominal Speed [RPM] Parameter 1-39 Motor Poles – Parameter 4-12 Motor Speed Low Limit [Hz] [Hz] Parameter 4-14 Motor Speed High Limit [Hz] [Hz] Parameter 3-02 Minimum Reference – Parameter 3-03 Maximum Reference – Parameter 3-41 Ramp 1 Ramp Up Time [s] Parameter 3-42 Ramp 1 Ramp Down Time [s] Parameter 3-13 Reference Site – Parameter 5-10 Terminal 18 Digital Input – Parameter 1-29 Automatic Motor Adaptation (AMA)
Table 2.1 Quick Set-up Parameters
18 Danfoss A/S © 05/2016 All rights reserved. MG16H202
28.8%
14.4Hz
Auto Remote Running
5.66A
2.63kW
0kWh
1 (1)
130BT110.11
Status
130BT111.10
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
13.7% 13.0A 1(1)
Quick Menus
130BT112.10
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
69.3% 5.20A 1(1)
Quick Menus
Q3
130BT113.10
Q3-1 General Settings
Q3-2 Open Loop Settings
Q3-3 Closed Loop Settings
Q3-4 Application Settings
28.4% 2.05A 1(1)
Function Setups
130BT114.10
26.0%
Q3 - 10 Adv. Motor Settings
Q3 - 11 Analog Output
Q3 - 12 Clock Settings
Q3 - 13 Display Settings
7.14A 1(1) Q3-1
General Settings
130BA115.10
6 - 50 Terminal 42 Output
(100) Output frequency
26.3%
5.82A 1(1)
Analog Output
03.11
130BT116.10
43.4%
6-50 Terminal 42 Output
[107]
Speed
Analog Output
7.99A Q3-11
1(1)
How to Program Programming Guide
2.1.5 Function Set-ups
The function set-up provides quick and easy access to all parameters required for most refrigiration applications including:
Most VAV and CAV supply and return fans.
Cooling tower fans.
Primary pumps.
Secondary pumps.
Condenser water pumps.
Other pump, fan, and compressor applications.
How to access Function Set-up - example
1. Turn on the frequency converter (yellow LED lights).
4. Function Set-ups options appear. Select Q3-1 General Settings. Press [OK].
Illustration 2.18 Function Set-ups Options
5.
Press [▲] and [▼] to scroll down to Q3-11 Analog Outputs. Press [OK].
Illustration 2.19 General Settings Options
2 2
Illustration 2.15 Frequency Converter Turned On
2. Press [Quick Menus].
Illustration 2.16 Quick Menu Selected
3.
Press [▲] and [▼] to scroll down to Function Set- ups. Press [OK].
6. Select parameter 6-50 Terminal 42 Output. Press [OK].
Illustration 2.20 Parameter 6-50 Terminal 42 Output Selected
7.
Press [▲] and [▼] to select between the
dierent
options. Press [OK].
Illustration 2.21 Setting a Parameter
Illustration 2.17 Scrolling to Function Set-up
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 19
How to Program
VLT® Refrigeration Drive FC 103
Function set-up parameters
The function set-up parameters are grouped in the following way:
22
Q3-10 Adv. Motor Settings Q3-11 Analog Output Q3-12 Clock Settings Q3-13 Display Settings
Parameter 1-90 Motor Thermal
Protection
Parameter 1-93 Thermistor
Source
Parameter 1-29 Automatic Motor
Adaptation (AMA)
Parameter 14-01 Switching
Frequency
Parameter 0-76 DST/
Parameter 0-77 DST/
Parameter 0-38 Display Text 2 Parameter 0-39 Display Text 3
Table 2.2 Q3-1 General Settings
Q3-2 Open Loop Settings
Parameter 1-00 Conguration Mode
Parameter 3-02 Minimum Reference
Parameter 3-03 Maximum Reference
Parameter 3-15 Reference 1 Source
Parameter 6-10 Terminal 53 Low Voltage
Parameter 6-11 Terminal 53 High Voltage
Parameter 6-14 Terminal 53 Low Ref./Feedb. Value
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
Parameter 3-10 Preset Reference
Parameter 6-50 Terminal 42
Output
Parameter 6-51 Terminal 42
Output Min Scale
Parameter 6-52 Terminal 42
Output Max Scale – Parameter 0-74 DST/
Parameter 0-70 Set Date and
Time
Parameter 0-71 Date Format Parameter 0-21 Display Line 1.2 Small
Parameter 0-72 Time Format Parameter 0-22 Display Line 1.3 Small
Summertime
Summertime Start
Summertime End
Parameter 0-20 Display Line 1.1 Small
Parameter 0-23 Display Line 2 Large
Parameter 0-24 Display Line 3 Large
Parameter 0-37 Display Text 1
Table 2.3 Q3-2 Open Loop Settings
Q3-3 Closed Loop Settings
Parameter 1-00 Conguration Mode
Parameter 20-00 Feedback 1 Source
Parameter 20-12 Reference/Feedback Unit
Parameter 6-20 Terminal 54 Low Voltage
Parameter 6-21 Terminal 54 High Voltage
Parameter 6-22 Terminal 54 Low Current
Parameter 6-23 Terminal 54 High Current
Parameter 6-24 Terminal 54 Low Ref./Feedb. Value
Parameter 6-25 Terminal 54 High Ref./Feedb. Value
Parameter 3-02 Minimum Reference
Parameter 3-03 Maximum Reference
Parameter 20-21 Setpoint 1
Parameter 20-93 PID Proportional Gain
Parameter 20-94 PID Integral Time
Parameter 3-13 Reference Site
Table 2.4 Q3-3 Closed Loop Settings
20 Danfoss A/S © 05/2016 All rights reserved. MG16H202
130BP066.10
1107 RPM
0 -
**
Operation/Display
1 -
**
Load/Motor
2 -
**
Brakes
3 -
**
Reference / Ramps
3.84 A 1 (1)
Main Menu
How to Program Programming Guide
Compressor Condenser Single fan/pump
Parameter 22-75 Short Cycle Protection Parameter 22-40 Minimum Run Time Parameter 22-40 Minimum Run Time
Parameter 22-76 Interval between Starts Parameter 22-41 Minimum Sleep Time Parameter 22-41 Minimum Sleep Time
Parameter 22-77 Minimum Run Time Parameter 22-42 Wake-up Speed [RPM] Parameter 22-42 Wake-up Speed [RPM]
Parameter 20-00 Feedback 1 Source Parameter 22-43 Wake-up Speed [Hz] Parameter 22-43 Wake-up Speed [Hz]
Parameter 20-01 Feedback 1 Conversion Parameter 22-44 Wake-up Ref./FB Dierence Parameter 22-44 Wake-up Ref./FB Dierence Parameter 20-02 Feedback 1 Source Unit Parameter 20-00 Feedback 1 Source – Parameter 20-30 Refrigerant Parameter 20-01 Feedback 1 Conversion
Parameter 20-40 Thermostat/Pressostat
Function Parameter 20-41 Cut-out Value Parameter 20-30 Refrigerant – Parameter 20-42 Cut-in Value Parameter 20-40 Thermostat/Pressostat Function – Parameter 25-00 Pack Controller Parameter 20-41 Cut-out Value – Parameter 25-06 Number of Compressors Parameter 20-42 Cut-in Value – Parameter 25-20 Neutral Zone [unit] – Parameter 25-21 + Zone [unit] – Parameter 25-22 - Zone [unit]
Table 2.5 Q3-4 Application Settings
Parameter 20-02 Feedback 1 Source Unit
2 2
2.1.6 Main Menu Mode
To select the Main Menu mode, press the [Main Menu] key. Lines 2–5 on the display show parameter groups which can be selected by pressing [▲] and [▼].
Illustration 2.22 Display Example
Each parameter has a name and a number which remain the same regardless of the programming mode. In the Main Menu mode, the parameters are divided into groups.
All parameters can be changed in the Main Menu. The
conguration of the unit (parameter 1-00 Conguration Mode) determines other parameters available for programming. For example, selecting [3] Process Closed Loop enables additional parameters related to closed-loop
operation. Options installed on the frequency converter enable extra parameters associated with the option.
2.1.7 Parameter Selection
In the Main Menu mode, the parameters are divided into groups. Press the navigation keys to select parameter group. The following parameter groups are accessible:
Group number Parameter group
0-** Operation/Display 1-** Load/Motor 2-** Brakes 3-** References/Ramps 4-** Limits/Warnings 5-** Digital In/Out 6-** Analog In/Out 8-** Comm. and Options 11-** LonWorks 13-** Smart Logic 14-** Special Functions 15-** Drive Information 16-** Data Readouts 18-** Info & Readouts 20-** Drive Closed Loop 21-** Ext. Closed Loop 22-** Application Functions 23-** Time-based Functions 25-** Pack Controller 26-** Analog I/O Option 28-** Compressor Functions
Table 2.6 Parameter Groups
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 21
After selecting a parameter group, press the navigation keys to select a parameter.
130BP067.10
740RPM
0 -01 Language
[0] English
10.64A 1 [1] 0-0
*
Basic Settings
130BP068.10
740RPM
0 -01 Language
[0] English
10.64 A 1 [1] 0-0
*
Basic Settings
130BP069.10
1- 6*
113 RPM 1.78 A 1(1)
Load depen. setting
1 - 60 Low speed load
compensation
100%
130BP070.10
1 - 60 Low speed load compensation
1 0%
Load depen. setting 1- 6*
729RPM 6.21A 1(1)
6
How to Program
VLT® Refrigeration Drive FC 103
The middle section on the display shows the parameter number and name, as well as the selected parameter value.
Press the [▲] [▼] keys to change the data value. [▲] increases the data value, and [▼] decreases the data value. Place the cursor on the value to save and press [OK].
22
Illustration 2.23 Parameter Selection
Illustration 2.26 Changing a Group of Numeric Data Values
2.1.8 Changing Data
2.1.11 Value, Step-by-step
Press [OK] to change the selected parameter. The procedure for changing data depends on whether the selected parameter represents a numerical data value or a text value.
2.1.9 Changing a Text Value
If the selected parameter is a text value, change the text value with the [▲] [▼] keys. Place the cursor on the value that should be saved and press [OK].
Certain parameters can be changed step by step. This applies to:
Parameter 1-20 Motor Power [kW].
Parameter 1-22 Motor Voltage.
Parameter 1-23 Motor Frequency.
The parameters are changed both as a group of numeric data values and as numeric data values that are
innitely
varying.
2.1.12 Read out and Programming of Indexed Parameters
Parameters are indexed when placed in a rolling stack.
Parameter 15-30 Alarm Log: Error Code to parameter 15-33 Alarm Log: Date and Time contain a fault
log which can be read out. Select a parameter, press [OK], and use the []/[] navigation keys to scroll through the
Illustration 2.24 Changing a Text Value
value log.
Use parameter 3-10 Preset Reference as another example:
2.1.10 Changing a Group of Numeric Data Values
Select the parameter, press [OK], and use the []/[] navigation keys to scroll through the indexed values. To change the parameter value, select the indexed value and
If the selected parameter represents a numeric data value, change the data value pressing the [◀] [▶] navigation keys, as well as the [▲] [▼] navigation keys. Press [◀] [▶] keys to
press [OK]. To change the value, press the []/[] keys. Press [OK] to accept the new setting. Press [Cancel] to abort. Press [Back] to leave the parameter.
move the cursor horizontally.
2.1.13 Initialization to Default Settings
Initialize the frequency converter to default settings in 2 ways.
Recommended initialization (via parameter 14-22 Operation Mode)
1. Select parameter 14-22 Operation Mode.
Illustration 2.25 Changing a Group of Numeric Data Values
22 Danfoss A/S © 05/2016 All rights reserved. MG16H202
2. Press [OK].
3. Select [2] Initialization.
How to Program Programming Guide
4. Press [OK].
5. Cut o the mains supply and wait until the display turns o.
6. Reconnect the mains supply - the frequency converter is now reset.
7. Change parameter 14-22 Operation Mode back to [0] Normal Operation.
NOTICE
Resets parameters selected in Personal Menu with default factory setting.
Parameter 14-22 Operation Mode initializes all except:
Parameter 14-50 RFI Filter.
Parameter 8-30 Protocol.
Parameter 8-31 Address.
Parameter 8-32 Baud Rate.
Parameter 8-35 Minimum Response Delay.
Parameter 8-36 Maximum Response Delay.
Parameter 8-37 Maximum Inter-Char Delay.
Parameter 15-00 Operating hours to parameter 15-05 Over Volt's.
Parameter 15-20 Historic Log: Event to parameter 15-22 Historic Log: Time.
Parameter 15-30 Alarm Log: Error Code to parameter 15-32 Alarm Log: Time.
Manual initialization
1. Disconnect from mains and wait until the display turns o.
2. 2a Press [Status] - [Main Menu] - [OK] at
the same time while powering up (LCP 102, graphical display).
2b Press [Menu] while powering up (LCP
101, numerical display).
3. Release the keys after 5 s.
4. The frequency converter is now programmed according to default settings.
This procedure initializes all except:
Parameter 15-00 Operating hours.
Parameter 15-03 Power Up's.
Parameter 15-04 Over Temp's.
Parameter 15-05 Over Volt's.
NOTICE
Manual initialization:
Resets serial communication.
Resets parameter 14-50 RFI Filter and fault log
settings.
Removes parameters selected in
parameter 25-00 Pack Controller.
NOTICE
After initialization and power cycling, the display does not show any information until after a couple of minutes.
2 2
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 23
Parameter Description
3 Parameter Description
VLT® Refrigeration Drive FC 103
3.1 Parameter Selection
33
3.1.1 Main Menu Structure
Parameters for the frequency converter are grouped into various parameter groups for easy selection of the correct parameters for optimized operation of the frequency converter. Most refrigeration applications can be programmed by pressing [Quick Menu] and selecting the parameters under Quick Setup and Function Set-ups. Descriptions and default settings of parameters are in chapter 4 Parameter Lists.
Parameter groups
0-** Operation/Display
1-** Load and Motor
2-** Brakes
3-** Reference/Ramps
4-** Limits/Warnings
5-** Digital In/Out
6-** Analog In/Out
8-** Comm. and Options
11-** LonWorks
13-** Smart Logic
14-** Special Functions
15-** Drive Information
16-** Data Readouts
18-** Info & Readouts
20-** Drive Closed Loop
21-** Ext. Closed Loop
22-** Appl. Functions
23-** Time-based Functions
25-** Pack Controller
26-** Analog I/O Option
28-** Compressor Functions
Parameters: 0-** Operation and Display
3.2
Parameters related to the fundamental functions of the frequency converter, function of the LCP keys, and congu- ration of the LCP display.
0-01 Language
Option: Function:
Denes the language to be used in the display.
The frequency converter is delivered with 2 dierent language packages. English and German are included in both packages. English cannot be erased or manipulated.
[0] * English Part of language packages 1–2.
[1] Deutsch Part of language packages 1–2.
[2] Francais Part of language package 1.
[3] Dansk Part of language package 1.
[4] Spanish Part of language package 1.
[5] Italiano Part of language package 1.
[6] Svenska Part of language package 1.
[7] Nederlands Part of language package 1.
[10] Chinese Part of language package 2.
[20] Suomi Part of language package 1.
[22] English US Part of language package 1.
[27] Greek Part of language package 1.
[28] Bras.port Part of language package 1.
[36] Slovenian Part of language package 1.
[39] Korean Part of language package 2.
[40] Japanese Part of language package 2.
[41] Turkish Part of language package 1.
[42] Trad.Chinese Part of language package 2.
[43] Bulgarian Part of language package 1.
[44] Srpski Part of language package 1.
[45] Romanian Part of language package 1.
[46] Magyar Part of language package 1.
[47] Czech Part of language package 1.
[48] Polski Part of language package 1.
[49] Russian Part of language package 1.
[50] Thai Part of language package 2.
[51] Bahasa
Indonesia
[52] Hrvatski Part of language package 2.
Part of language package 2.
24 Danfoss A/S © 05/2016 All rights reserved. MG16H202
Parameter Description Programming Guide
0-02 Motor Speed Unit
Option: Function:
NOTICE
This parameter cannot be adjusted while the motor is running.
The information shown in the display depends on settings in parameter 0-02 Motor Speed Unit and parameter 0-03 Regional Settings. The default settings of parameter 0-02 Motor Speed Unit and parameter 0-03 Regional Settings depend on to which region of the world the frequency converter is supplied.
NOTICE
Changing the motor speed unit resets certain parameters to their initial value. Select the motor speed unit before modifying other parameters.
[0] RPM Select to show motor speed variables and parameters
using motor speed (RPM).
[1] * Hz Select to show motor speed variables and parameters
using output frequency (Hz).
0-03 Regional Settings
Option: Function:
NOTICE
This parameter cannot be adjusted while the motor is running.
The display output depends on the settings in
parameter 0-02 Motor Speed Unit and parameter 0-03 Regional Settings. The default settings of parameter 0-02 Motor Speed Unit and parameter 0-03 Regional Settings depend on which
region of the world the frequency converter is supplied to. Reprogram the settings as required.
The settings not used are made invisible.
[0] Interna-
tional
[1] North
America
0-04 Operating State at Power-up
Option: Function:
Sets parameter 1-20 Motor Power [kW] units to [kW] and the default value of parameter 1-23 Motor Frequency [50 Hz].
Sets parameter 1-21 Motor Power [HP] units to [hp] and the default value of parameter 1-23 Motor Frequency to 60 Hz.
Select the operating mode after reconnection of the frequency converter to mains voltage after power-down when operating in hand-on (local) mode.
0-04 Operating State at Power-up
Option: Function:
[0] * Resume Resumes operation of the frequency converter
maintaining the same local reference and the same start/stop condition (applied by [Hand On]/[O] on the LCP or local start via a digital input as before the frequency converter was powered down.
[1] Forced
stop, ref=old
Stops the frequency converter, but at the same time retains the local speed reference before power-down in the memory. After mains voltage is reconnected and after receiving a start command (pressing [Hand On] or local start command via a digital input), the frequency converter restarts and operates at the retained speed reference.
0-05 Local Mode Unit
Option: Function:
Denes if the local reference unit is shown in terms of the motor shaft speed (in RPM/Hz) or as percent.
[0] * As Motor
Speed Unit
[1] %
3.2.1 0-1* Set-up Operations
Dene and control the individual parameter set-ups. The frequency converter has 4 parameter set-ups that can be programmed independently of each other. This makes the frequency converter very exible and able to meet the requirements of many dierent refrigeration system control schemes, often saving the cost of external control equipment. For example, these can be used to program the frequency converter to operate according to 1 control scheme in 1 set-up (for example daytime operation) and another control scheme in another set-up (for example night setback). Alternatively, they can be used by an AHU or packaged unit OEM to identically program all their factory tted frequency converters for dierent equipment models within a range to have the same parameters, and then during production/commissioning simply select a specic set-up depending on which model within that range the frequency converter is installed on. The active set-up (that is the set-up in which the frequency converter is currently operating) can be selected in
parameter 0-10 Active Set-up and is shown in the LCP. Use [9] Multi set-up to switch between set-ups with the
frequency converter running or stopped, via digital input or serial communication commands (for example for night setback). If it is necessary to change setups while running, ensure that parameter 0-12 This Set-up Linked to is programmed as required. For most refrigeration applications it is not necessary to program parameter 0-12 This Set-up Linked to even if change of set-
3 3
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 25
Parameter Description
VLT® Refrigeration Drive FC 103
up while running is required. However, for complex applications, using the full exibility of the multiple set­ups, programming parameter 0-12 This Set-up Linked to may be required. Using parameter 0-11 Programming Set-up, it is possible to edit parameters within any of the set-ups while continuing the frequency converter operation in its active
33
set-up which can be a dierent set-up to the one being edited. Using parameter 0-51 Set-up Copy, it is possible to copy parameter settings between the set-ups to enable quicker commissioning if similar parameter settings are required in dierent set-ups.
0-10 Active Set-up
Option: Function:
Select the set-up in which the frequency converter is to operate. Use parameter 0-51 Set-up Copy to copy a set-up to 1 or all other set-ups. To avoid conicting settings of the same parameter within 2 dierent set-ups, link the set-ups using parameter 0-12 This Set-up Linked to. Stop the frequency converter before switching between set-ups where parameters marked not changeable during operation have dierent values. Parameters which are not changeable during
operation are marked FALSE in chapter 4 Parameter Lists.
[0] Factory
setup
[1]*Set-up 1 [1] Set-up 1 to [4] Set-up 4 are the 4 parameter
[2] Set-up 2 [3] Set-up 3 [4] Set-up 4 [9] Multi Set-upIs used for remote set-up selections using digital
Cannot be changed. It contains the Danfoss data set, and can be used as a data source when returning the other set-ups to a known state.
set-ups within which all parameters can be programmed.
inputs and the serial communication port. This set-up uses the settings from parameter 0-12 This Set-up Linked to.
0-11 Programming Set-up
Option: Function:
Select the set-up to be edited (that is programmed) during operation; either the active set-up or 1 of the inactive set-ups. The set-up number being edited is shown in the LCP in brackets.
[0] Factory
setup
Cannot be edited, but it is useful as a data source to return the other set-ups to a known state.
0-11 Programming Set-up
Option: Function:
[1] Set-up 1 [1] Set-up 1 to [4] Set-up 4 can be edited freely
during operation, independently of the active set-up.
[2] Set-up 2 [3] Set-up 3 [4] Set-up 4 [9] * Active Set-upThe set-up in which the frequency converter is
operating can be edited during operation. Editing parameters in the selected set-up would normally be done from the LCP, but it is also possible from any of the serial communi­cation ports.
0-12 This Set-up Linked to
Option: Function:
Use this parameter only if a change of set-ups is required while the motor is running. This parameter ensures that parameters which are not changeable during operation have the same setting in all relevant set-ups.
To enable conict-free changes from 1 set-up to another while the frequency converter is running, link set-ups containing parameters which are not changeable during operation. The link ensures synchronizing of the not changeable during operation parameter values when moving from 1 set-up to another during operation. Not changeable during operation parameters can be identied by the label FALSE in the parameter lists in chapter 4 Parameter Lists.
The parameter 0-12 This Set-up Linked to feature is used when [9] Multi set-up in
parameter 0-10 Active Set-up is selected. Use [9] Multi set-up to move from 1 set-up to another
during operation while the motor runs. For example: Use [9] Multi set-up to shift from set-up 1 to set­up 2 while the motor runs. Program parameters in set-up 1 rst, then ensure that set-up 1 and set-up 2 are synchronized (or linked).
Synchronization can be performed in 2 ways:
Change the edit set-up to [2] Set-up 2
in parameter 0-11 Programming Set-up and set parameter 0-12 This Set-up Linked to to [1] Set-up 1. This starts the linking (synchronizing) process.
26 Danfoss A/S © 05/2016 All rights reserved. MG16H202
130BP075.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling 0-1*
[1]
Setup 1
130BP076.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[2]
Setup 2
Parameter Description Programming Guide
0-12 This Set-up Linked to
Option: Function:
Illustration 3.1 Set-up Handling
While still in set-up 1, using
parameter 0-50 LCP Copy, copy set-up 1 to set-up 2. Then set
parameter 0-12 This Set-up Linked to to [2] Set-up 2. This starts the linking
process.
Illustration 3.2 Set-up Handling
After the link is complete, parameter 0-13 Readout: Linked Set-ups reads set-ups 1 and 2 to indicate that all not changeable during operation parameters are now the same in set-up 1 and set-up 2. If there are changes to a not changeable during operation parameter in set-up 2, for example parameter 1-30 Stator Resistance (Rs), they are also changed automatically in set-up 1. A switch between set-up 1 and set-up 2 during operation is now possible.
[0] * Not linked [1] Set-up 1 [2] Set-up 2 [3] Set-up 3 [4] Set-up 4
0-13 Readout: Linked Set-ups
Array [5]
Range: Function:
0* [0 -
255]
View a list of all the set-ups linked by parameter 0-12 This Set-up Linked to. The parameter has 1 index for each parameter set-up. The value for each index shows which set-ups are linked to that parameter set-up.
0-13 Readout: Linked Set-ups
Array [5]
Range: Function:
Index LCP value
0 {0} 1 {1,2} 2 {1,2} 3 {3} 4 {4}
Table 3.1 Set-up Link Example
0-14 Readout: Prog. Set-ups / Channel
Range: Function:
0* [-2147483648
- 2147483647]
View the setting of parameter 0-11 Programming Set-up for each of the 4 dierent communication channels. When the number is shown in hex, as it is in the LCP, each number shows 1 channel. Numbers 1–4 show a set-up number; F stands for the factory setting, and A stands for an active set-up. The channels are, from right to left: LCP, eldbus, USB, HPFB1.5. Example: The value AAAAAA21h means that the eldbus channel uses set-up 2 in parameter 0-11 Programming Set-up, the LCP uses set-up 1, and all other channels use the active set-up.
3.2.2 0-2* LCP Display
Dene the variables shown in the LCP.
NOTICE
For information on how to write display texts, refer to:
Parameter 0-37 Display Text 1.
Parameter 0-38 Display Text 2.
Parameter 0-39 Display Text 3.
0-20 Display Line 1.1 Small
Option: Function:
Select a variable for display in line 1, left position.
[37] Display Text 1 Enables an individual text string to be
written for display in the LCP, or to be read via serial communication.
[38] Display Text 2 Enables an individual text string to be
written for display in the LCP, or to be read via serial communication.
3 3
MG16H202 Danfoss A/S © 05/2016 All rights reserved. 27
Parameter Description
VLT® Refrigeration Drive FC 103
0-20 Display Line 1.1 Small
Option: Function:
[39] Display Text 3 Enables an individual text string to be
written for display in the LCP, or to be read via serial communication.
33
[89] Date and Time
Readout
[953] Probus
Warning Word
[1397] Alert Alarm
Word
[1398] Alert Warning
Word
[1399] Alert Status
Word
[1501] Running Hours View the number of running hours of
[1502] kWh Counter View the mains power consumption in
[1580] Fan Running
Hours
[1600] Control Word View the control word sent from the
[1601] Reference [Unit] Total reference (sum of digital/analog/
[1602] Reference [%] Total reference (sum of digital/analog/
[1603] Status Word Present status word
[1605] Main Actual
Value [%]
[1609] Custom Readout View the user-dened readouts as
[1610] Power [kW ] Actual power consumed by the motor
[1611] Power [hp] Actual power consumed by the motor
[1612] Motor Voltage Voltage supplied to the motor.
[1613] Frequency Motor frequency, that is the output
Displays the current date and time.
Displays PROFIBUS communication warnings.
the motor.
kWh.
frequency converter via the serial communication port in hex code.
preset/bus/freeze reference/catch up, and slow-down) in selected unit.
preset/bus/freeze reference/catch up, and slow-down) in percent.
View the 2-byte word sent with the status word to the bus master reporting the main actual value.
dened in:
Parameter 0-30 Custom
Readout Unit.
Parameter 0-31 Custom
Readout Min Value.
Parameter 0-32 Custom
Readout Max Value.
in kW.
in hp.
frequency from the frequency converter in Hz.
0-20 Display Line 1.1 Small
Option: Function:
[1614] Motor current Phase current of the motor measured
as eective value.
[1615] Frequency [%] Motor frequency, that is the output
frequency from the frequency converter in percent.
[1616] Torque [Nm] Present motor load as a percentage of
the rated motor torque.
[1617] Speed [RPM] Motor speed reference. Actual speed
depends on slip compensation being used (compensation set in parameter 1-62 Slip Compensation). If not used, actual speed is the value read in the display minus motor slip.
[1618] Motor Thermal Thermal load on the motor, calculated
by the ETR function. See also parameter group 1-9* Motor Temperature.
[1622] Torque [%] Shows the actual torque produced, in
percentage.
[1624] Calibrated Stator
Resistance
[1630] DC Link Voltage Intermediate circuit voltage in the
frequency converter.
[1631] System Temp. [1632] Brake Energy /s Present brake power transferred to an
external brake resistor. Stated as an instant value.
[1633] Brake Energy /2
min
[1634] Heatsink Temp. Present heat sink temperature of the
[1635] Inverter Thermal Percentage load of the inverters.
[1636] Inv. Nom.
Current
[1637] Inv. Max.
Current
[1638] SL Controller
State
[1639] Control Card
Temp.
[1650] External
Reference
[1652] Feedback[Unit] Reference value from programmed
Brake power transferred to an external brake resistor. The average power is calculated continuously for the most recent 120 s.
frequency converter. The cutout limit is 95 ±5 °C (203 ±9 °F); cutting back in occurs at 70 ± 5 °C (158 ±9 °F).
Nominal current of the frequency converter.
Maximum current of the frequency converter.
State of the event executed by the control.
Temperature of the control card.
Sum of the external reference as a percentage, that is the sum of analog/ pulse/bus.
digital input(s).
28 Danfoss A/S © 05/2016 All rights reserved. MG16H202
Loading...
+ 204 hidden pages