Danfoss FC 101 Fact sheet

Fact Sheet
VLT® HVAC Basic Drive FC 101 Convenient and compact control
IP54
Quiet
cooling fan operation over the entire power range
IP20
Product range
3 x 200-240 V ...................................0.25-45 kW
3 x 380-480 V ...................................0.37-90 kW
3 x 525-600 V ..................................... 2.2-90 kW
Optimized for basic operation of fans, pumps and compressors, the VLT® HVAC Basic Drive has built-in functions that reduce initial costs and increase productivity.
Available enclosure ratings
IP20
IP21/UL Type 1 (separate option kit)
IP54
This drive is the most compact unit in its class, and can deliver up to 25% energy savings. Integrated DC coils re­duce harmonics without the extra cost and space required for external devices.
Feature Benefit
All built-in – low investment
Most common HVAC protocols for BMS controller connectivity are embedded
Built-in PI controller No external PI controller required Smart Logic Controller Often makes PLC unnecessary Sensorless pump control No need for external pressure transmitter
Save energy – less operation cost
Flow compensation function Saves energy Automatic Energy Optimizer function Saves additional 5-15% energy PM motor control in open loop Increased efficiency especially at part load Sleep mode Saves energy and extends lifetime
Unequalled robustness – maximum uptime
Robust single enclosure Maintenance-free Unique variable-speed cooling concept with no
forced air flow over electronics Max ambient temp. up to 50° C No external cooling Flying Start Reduced mechanical wear on equipment Fire override mode Enhanced safety Thermistor input Prevents motor overheating
User friendly – save commissioning and operating cost
Operate both PM and induction motors Versatile, only one drive type required Easy connectability and start-up wizard Effective commissioning and operation
Alpha-numeric display/improved HMI
Cooling fan operation adjusts precisely to load Silent or low noise level only Auto restart Saves time and money Bypass frequencies Less noise and vibrations/resonances Global HVAC support organization Local service – globally
Built-in DC coils and EMC filters – no harmonic concerns
Built-in EMC filter Meets protection class C1, C2 or C3 Integrated DC choke Small power cables. Meets EN 61000-3-12
Fewer extra gateway solutions needed
Problem-free operation in harsh environments
Display in multiple languages and metric/imperial units
drives.danfoss.com
Easy commissioning
n Configure with a start-up wizard n Easy-to-program parameters n Alphanumeric display n Hand – Off – Auto keys n Status LCDs n Easy to install and wire up n 7 languages and numeric
programming
Your choice
n Enclosures: IP20/Chassis or
IP21/Type 1 or IP54
n Optional harmonic filters
for 5% or 10% THDi
n Minimum 25 m C3
as standard built-in
Optional: C1/C2 filters
Specifications
Mains supply (L1, L2, L3)
Supply voltage
Supply frequency 50/60 Hz Displacement power factor (cos φ) Near unity (> 0.98) Switching frequency on input supply L1, L2, L3 1 time/minute max.
Output data (U, V, W)
Output voltage 0-100% of supply voltage Switching on output Unlimited Ramp times 1-3600 sec. Open/closed loop 0-400 Hz
Digital inputs
Programmable digital inputs 4 Logic PNP or NPN Voltage level 0-24 V DC
Analog inputs
Analog inputs 2 Modes 1 voltage or current Voltage level 0 V to +10 V (scaleable) Current level 0/4 to 20 mA (scaleable)
Analog output (can be used as digital output)
Programmable analog outputs 2 Current range at analog output 0/4 to 20 mA
Relay outputs
Programmable relay outputs 2 (240 VAC, 2 A and 400 VAC, 2 A)
Fieldbus communication
Standard built-in: BACnet mstp FC Protocol
200–240 V ±10% 380–480 V ±10% 525–600 V ±10%
N2 Metasys FLN Apogee Modbus RTU
Dimensions
Power
Frame IP Class 3 x 200-240 V 3 x 380-480 V 3 x 525-600 V Incl. decoupling plate
H1 IP20 0.25-1.5 kW/0.3-2 HP 0.37-1.5 kW/0.5-2 HP - 195/7.7 273/10.7 75/2.9 168/6.6 H2 IP20 2.2 kW/3 HP 2.2-4 kW/3-5.4 HP - 227/8.9 303/11.9 90/3.5 190/7.5 H3 IP20 3.7 kW/5 HP 5.5-7.5 kW/7.5-10 HP - 255/10.0 329/13.0 100/3.9 206/8.1 H4 IP20 5.5-7.5 kW/7.5-10 HP 11-15 kW/15-20 HP - 296/11.7 359/14.1 135/5.3 241/9.5 H5 IP20 11 kW/15 HP 18.5-22 kW/25-30 HP - 334/13.1 402/15.8 150/5.9 255/10.0 H6 IP20 15-18.5 kW/20-25 HP 30-45 kW/40-60 HP 18.5-30 kW/25-40 HP 518/20.4 595/23.4-635/25.0 239/9.4 242/9.5 H7 IP20 22-30 kW/30-40 HP 55-75 kW/75-100 HP 37-55 kW/50-75 HP 550/21.7 630/24.8-690/27.2 313/12.3 335/13.2 H8 IP20 37-45 kW/50-60 HP 90 kW/125 HP 75-90 kW/100-125 HP 660/26.0 800/31.5 375/14.8 335/13.2 H9 IP20 2.2-7.5 kW/3-10 HP 372/14.6 374/14.7 130/5.1 205/8.0
H10 IP20 11-15 kW/15-20 HP 475/18.7 419/16.5 165/6.5 249/9.8
I2 IP54 0.75-4 kW/1-5.4 HP 332/13.1 115/4.5 225/8.8 I3 IP54 5.5-7.5 kW/7.5-10 HP 368/14.5 135/5.3 237/9.3 I4 IP54 11-18.5 kW/15-25 HP 476/18.7 180/7.1 290/11.4 I6 IP54 22-37 kW/30-50 HP 650/25.6 242/9.5 260/10.2 I7 IP54 45-55 kW/60-75 HP 680/26.8 308/12.1 310/12.2 I8 IP54 75-90 kW/100-125 HP 770/30.3 370/14.6 335/13.2
DKDD.PFP.100.A4.02 © Copyright Danfoss Drives | 2017.07
(kW/HP)
Height
(mm/inch)
Width
(mm/inch)
Depth
(mm/inch)
EtherNet/IP™ and DeviceNet™ are trademarks of ODVA, Inc.
Loading...