Danfoss Fault Location Installation guide

REFRIGERATION AND AIR CONDITIONING
Technical information
Fault Location on PL, TL, NL, FR Compressors
COMPRESSORS
This Hermetic Note is directed especially to the service network, for house­hold appliances and similar. For detailed information on compressors see the data sheets.
Compressors type PL, TL, NL, FR and partly SC are equipped with a PTC starting device (fig. 1) or a relay and start capacitor (fig. 2). The motor protector is built into the windings. In the event of a start failure, with a cold compressor, up to 15 minutes can elapse before the protector cuts out the compressor. When the protector cuts out and the compressor is warm, it can take up to 1 hour before the protector cuts in the compressor again.
The compressor must not be started without the electrical equipment.
Before beginning systematic fault location, a good rule is to cut the supply voltage for at least 5 minutes. This ensures that the PTC starting device has cooled off and is ready for start. A voltage drop or blackout within the first minutes of a pull down of the appliance with cold compressor, can lead to an interlocking situation. A compressor with PTC can not start at non equalized pressure and the PTC does not cool down so fast. It can take more than 1 hour until the appliance then operates normally again.
To avoid unneccessary protector operation and consequent waiting time, it is important to carry out fault location in the sequence given below. Tests are made according to desriptions on following page.
• Remove electrical equipment
• Check electrical connection between main and start pins of compressor terminal
• Check electrical connection between main and common pins of compressor terminal
• Replace compressor, if above connection checks failed
• Else, replace electrical equipment
If the compressor still does not operate, most probably it is no electrical compressor failure. For more detailed fault location, see the tables.
General
Fault location
Electrical compressor quick check
Fig. 1: PTC starting device Fig. 2: Starting relay
Fault location table :
Most common fault reasons, detectable before dis-mounting compressor.
Customer claim
No/reduced cooling
First analysis
Compressor does not run
Compressor runs 100%
Compressor runs on/off
Possible cause
Compressor gets no or bad power supply
Defective starting equipment
Compressor with PTC can not start at pressure difference PTC defective
Relay defective
Compressor overloaded
Defective motor windings Defective protector Mechanically blocked compressor
No or low refrigerant charge
Too high ambient temperature Too high condensing temperature Capillary partly blocked
Valves coked or damaged Thermostat not OK Wrong refrigerant charge
Ice block built up on evaporator
Compressors trips on motor protector
Check
Voltage at plug and fuse Aplicance energized Thermostat function Cables and connections in appliance Voltage at compressor terminals Relay function by shaking to hear if armature is working Start capacitor function PTC by shaking PTC resistance 10 to 100 Ohm between M and S pin Stop time long enough for pressure equalization
PTC resistance 10 to 100 Ohm between M and S pin Relay function by shaking, to hear moving of armature Condenser pressure and ventilation Ambient temperature too high according to type label of appliance Check winding resistances
Check protector with ohmmeter Start with proper starting equip­ment, voltage and conditions, windings and protector OK Recharge and search for leaks
Ambient temperature according to type label of appliance Condenser and compressor ventilation Recharge and search for leaks, measure suction pressure. Capillary blocked, if pressure very low Recharge and search for leaks
Thermostat type and function Recharge and search for leaks
Check for ice on evaporator Thermostat function and settings Internal no-frost fan function Compressor load, compressor and condenser ventilation Compressor voltage supply for minimum 187 V Compressor voltage supply for drop outs. Check thermostat and appli­ance cables for loose connections Motor windings resistance for partly short circuit or earth connection
Activity (depends on result)
Replace relay
Replace start capacitor Replace if noise appears Replace PTC
Adjust thermostat difference
Replace PTC
Replace relay and capacitor Ensure proper ventilation
Replace compressor
Replace compressor Replace compressor
Ensure leakfree system and proper charge, replace drieer
Ensure proper ventilation and wall distance
Replace compressor, if still not cooling properly Replace thermostat Ensure leakfree system and proper charge, replace drier Defrost properly Replace thermostat
Ensure proper ventilation and wall distance Ensure proper power supply Fix all connections
Replace compressor
Customer claim
Noise
Fuses are blown by appliance
First analysis
Rattle or humming
Banging at start or stop of compressor
Relay clicking frequently after start
Short circuit in appliance
Short circuit in compressor
Fuse blows at compressor start
Starting capa­citor exploded
Starting relay cap blown off
Possible cause
Tube touching cabinet
Compressor touching cabinet
Broken internal suspension spring or discharge tube Resonance Fan noise
Compressor block hit­ting housing internally
Compressor over­loaded
Relay defective Defective cabling in appliance
Defective thermostat Ground connection Defective terminals
Short circuit between cables at terminals Short circuit in compressor motor
Supply voltage too low Fuse loaded by too many appliances Resettable fuse too quick acting Partly short circuit to earth Defective relay
Wrong relay type Extremely many starts and stops of com­pressor Short circuit in com­pressor motor
Check
Tube placing
Compressor mounting and rubber feet
Listen to compressor with screw­driver against compressor with edge and to your ear with grip Find vibrating mounting parts Vibration of fan or fan mounting
Compressor overload by pressure
Fan function Refrigerant charge Pressure equalization before start and number of on/off cycles Ambient temperature according to type label
Ventilation to compressor and con­denser. Check fan function
Right relay type for compressor All connecting cables and power supply cord for loose connections, short circuits Thermostat connections Resistance from line/neutral to earth For burns on the terminal pins
Connectors and cables at com­pressor Resistance values in windings Resistance between terminals and earth Supply voltage at compresor start >187 V Total fuse load
Fuse load and type
Resistance between terminals and earth Relay function by shaking, to hear moving of armature Relay type Relay type Thermostat defect or differences too small Compressor motor resistances
Activity (depends on result)
Bend tube to their right place, carefully Place rubber feet and mounting accessories correctly Replace compressor, if abnormal sounds
Place or fix correctly Fix fan and blade, replace, if defective Clean condenser if dusty. Make sure, that ventilation gaps for air circulation are satisfactory
Recharge, if too high Adjust thermostat, if stop time less than 5 min Take appliance out of function, if ambient too hot Clean condenser if dusty. Make sure, that ventilation gaps for air circulation are satisfactory Replace relay, if wrong Fix connections properly
Fix connections properly
Replace electrical accessories Insulate cables and connectors Replace compressor, if short circuited
Connect applaince to different fuse If possible replace by slightly slower type Replace compressor, if short circuited Replace relay and capacitor Replace relay and cap Replace relay and cap Adjust or replace thermostat Replace compressor
Resistance between pins M (main) and S (start) on compressor terminals is measured with an ohm-meter, see figure 3.
• Connection: Main and start
windings normally OK
• No connection: Main or start winding
defective: Replace compressor
At cold compressor (ca. 25°C) the values are ca. 10 to 100 Ohm for 220-240 V compressors. For partial short circuit detection, exact values are needed from data sheets of the specific compressor, which can be found on the Danfoss Compressors homepage.
Resistance between pins M (main) and C (common) on compressor terminals is measured with an ohm-meter, see figure 3 and 4.
• Connection: Protector OK
• No connection: Compressor cold: Protector defective: Replace
compressor
Compressor hot: Protector could be
OK, but cut out: Wait for reset
Remove relay from compressor. Measure connection between connectors 10 and 12 (see figure 5):
• No connection: Relay defective: Replace relay
Measure connection between connectors 10 and 11: In normal vertical position (like mounted, solenoid upward):
• Connection: Relay defective: Replace relay
• No connection: OK
In top-down position (solenoid downward):
• Connection: OK
• No connection: Relay defective: Replace relay
Remove PTC from compressor. Shake by hand. Pin C can slightly rattle.
• Internal rattle noise (except pin C): PTC defect: Replace PTC
Measure resistance between pins M and S, see figure 6. Resistance value between 10 and 100 Ohm at room temperature for 220 V PTC.
• Connection: PTC working: OK
• No connection: PTC defect: Replace PTC
Check main and start winding
Check protector
Check relay
Check PTC
Fig. 4: Windings and protectorFig. 3: Compressor terminals
Fig. 5: Relay connections Fig. 6: PTC connections (backside)
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss Compressors GmbH
Mads-Clausen-Strasse 7 Postfach 1443, D-24939 Flensburg Telefon: (0461) 4941-0 International +49 461 4941-0 Telefax: +49 461 44715 Telex: 227 43 dancom d
CN.71.B5.02
Produced by Danfoss G1 Advertising Agency 01.07.UF.JN.AO
www.danfoss.com/compressors
Loading...