Danfoss Expansion Module Installation guide [da]

Installation Guide
Expansion Module
for Danfoss Icon™ Master
© Danfoss | FEC | 2018.12 | 1AN28953970588601-000201 | VIMDE20F | 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
2 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Content
Expansion Module for Danfoss Icon™ Master .................................................... 4
Expansion Module for Danfoss Icon™ Master ...................................................24
Expansion Module for Danfoss Icon™ Master ...................................................44
Expansion Module for Danfoss Icon™ Master ...................................................64
Expansion Module for Danfoss Icon™ Master ...................................................84
Expansion Module for Danfoss Icon™ Master ..................................................104
Expansion Module for Danfoss Icon™ Master ..................................................124
Expansion Module for Danfoss Icon™ Master ..................................................144
Expansion Module for Danfoss Icon™ Master ..................................................164
Expansion Module for Danfoss Icon™ Master ..................................................184
Expansion Module for Danfoss Icon™ Master ..................................................204
Expansion Module for Danfoss Icon™ Master ..................................................224
Expansion Module for Danfoss Icon™ Master ..................................................244
Expansion Module for Danfoss Icon™ Master ..................................................264
Expansion Module for Danfoss Icon™ Master ..................................................284
GB
FR
IT
NL
DK
SE
NO
IS
FI
CN
LT
PL
TR
UA
Expansion Module for Danfoss Icon™ Master ..................................................304
© Danfoss | FEC | 2018.12 | 3VIMDE20F / 088N2100
RU
Installation Guide Expansion Module for Danfoss Icon™ Master
Perform wirring according to electrical diagram, then insert the Expansion
1
APPLICATION
2
IN 1
SETTINGS
IN 2 IN 3
3
Module into the Danfoss Icon™ Master Controller for extra features.
1. Use this key to choose application.
2. Use the key to set application
3. LED’s indicate the state of the inputs
4. Terminals for connection of various
5. Cable strain relief.
6. Break away for wiring /cables.
Press application key and then use
and to choose application 1-11 and confirm with “OK”. See applications drawings to help you choose the correct application.
specific settings. See in application description which settings are available for the chosen application.
1 to 3. See application description for the specific application.
wiring /external devices.
4
IN 3 IN 2 IN 1
PWR3
PT
24
1000
VDC
5
6
4 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application 0001: 2-pipe system, fixed supply temperature, electronically controlled.
Optional: Global standby.
Application description
Floor heating system with electronic supply temperature control. The supply temperature is set to a fixed value. The system uses a PT1000 sensor to detect and control the supply temperature and is also used to ensure that the temperature does not exceed the max. allowed temperature. If connected, the system will control the circulation pump and the heat demand signal for e.g. a boiler or heat pump. The pump and heat demand signal will be on when minimum 1 circuit has a heat demand. Output 1 must be used for TWA on
mixing shunt.
The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.
Settings
“SET 1” = Set desired supply flow temperature [25-70°C] “SET 2” = Set desired safety cut-off temperature [30-75°C]
Note: temperature must be higher than flow temperature.
GB
APPLICATION
SETTINGS
OK
OK
OK
OK
OK
OK
OK
OK
© Danfoss | FEC | 2018.12 | 5VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application test function
Enter the “Test” menu via the installer key. The Application test (APP test) is specific for each applica­tion. The test is split into steps to ensure that all compo­nents are installed correctly. Please follow the process.
Test steps
RUN INSTALL UNINSTALL
TEST
TEST NET
TEST APP
TEST FL
O
Step 1:1 Go to mixing shunt control valve actuator, and verify that the valve opens fully (up to 3 minutes opening time can be expected). After 5 minutes, the mixing shunt valve actuator will close again. During the 5 minute test period, the display on the Master Controller will also show the measured supply flow tem­perature in the display.
Parts list
Pos. 1 088U0093-96 1 pc. Danfoss FHM-Cx Mixing shunt
Pos. 2 088U05XX / 088U06XX / 088U07XX 1 set Danfoss Manifold (types FHF or BasicPlus or SSM)
Pos. 3 NC: 088H3110 / NO: 088H3111 xx pcs. thermal actuator, 24 V TWA-A
Pos. 4 087B1165 1 pc. ESM-11 PT-1000 sensor
Pos. 5. NC: 088H3110 / NC: 193B2148 1 pc. thermal actuator, 24 V (types TWA-A or ABN-FBH)
OK
6 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application 0002: 2-pipe system with demand based supply temperature control.
Optional: Global standby.
Application description
Floor heating system with electronic supply temperature control. The demand based supply temperature is controlled depending on the heat demand from the rooms. The system uses a PT1000 sensor to detect the supply temperature and is also used to ensure that the temperature does not exceed the max. allowed temperature via a safety Tmax. If connected, the system will control the circulation pump and the heat demand signal for e.g. a boiler or heat pump. The pump and heat demand signal will be on when minimum 1 circuit has a heat demand. Output 1 must be used for
TWA on mixing shunt.
The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.
Settings
“SET 1” = Set desired min. supply flow temperature [25-65°C] “SET 2” = Set desired max. supply flow [30-70°C]
Note: temperature cannot be set less than 5°C higher than min. supply flow temperature.
“SET 3” = Set desired safety cut-off temperature [30-75°C]
Note: temperature must be higher than flow temperature.
GB
APPLICATION
SETTINGSSETTINGS
OK
OKOK
OKOK
OKOK
OK
OKOK
OKOK
OKOK
OKOK
OKOK
OKOK
© Danfoss | FEC | 2018.12 | 7VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application test function
Enter the “Test” menu via the installer key. The Application test (APP test) is specific for each applica­tion. The test is split into steps to ensure that all compo­nents are installed correctly. Please follow the process.
Test steps
RUN INSTALL UNINSTALL
TEST
TEST NET
TEST APP
TEST FL
O
Step 1:1 Go to mixing shunt control valve actuator, and verify that the valve opens fully (up to 3 minutes opening time can be expected). After 5 minutes, the mixing shunt valve actuator will close again. During the 5 minute test period, the display on the master controller will also show the measured supply flow tem­perature in the display.
Parts list
Pos. 1 088U0093-96 1 pc. Danfoss FHM-Cx Mixing shunt
Pos. 2 088U05XX / 088U06XX / 088U07XX 1 set Danfoss Manifold (types FHF or BasicPlus or SSM)
Pos. 3 NC: 088H3110 / NO: 088H3111 xx pcs. thermal actuator, 24 V TWA-A
Pos. 4 087B1165 1 pc. ESM-11 PT-1000 sensor
Pos. 5. NC: 088H3110 / NC: 193B2148 1 pc. thermal actuator, 24 V (types TWA-A or ABN-FBH)
OK
8 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application 0003: 2-pipe system with automatic changeover for cooling based on supply temperature.
Optional: Dewpoint sensor (recommended), Global standby, Circulation pump and heat demand signal.
Application description
Floor heating system with automatic changeover for cooling based on supply temperature input. The supply temperature is monitered using a PT1000 sensor. Based on the measurement, the system switches to heating or cooling. If connected, the system will control the circulation pump which will be turned on when minimum 1 room has a heat or cooling demand. The heat signal for e.g. a boiler or heat pump is only activated when the system is in heating mode and minimum 1 room has a heat demand. For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.
Settings
“SET 1” = Set supply flow temperature for change-over to heating [25-55°C] “SET 2” = Set supply flow temperature for change-over to cooling [15-25°C]
Note: temperature cannot be set higher than 2°C lower than heating change-over temperature.
GB
APPLICATION
SETTINGS
OK
OK
OK
OK
OK
OK
OK
OK
Settings on thermostat
Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling
would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide for further information.
© Danfoss | FEC | 2018.12 | 9VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application test function
Enter the “Test” menu via the installer key. The Application test (APP test) is specific for each applica­tion. The test is split into steps to ensure that all compo­nents are installed correctly. Please follow the process.
Test steps
RUN INSTALL UNINSTALL
TEST
TEST NET
TEST APP
TEST FL
O
Step 1:1 During the 1 minute test period, the display on the master controller will show the measured supply flow temperature in the display.
Parts list
Pos. 1 087B1165 1 pc. ESM-11 PT1000 sensor
Pos. 2 088U05XX / 088U06XX / 088U07XX 1 set Danfoss Manifold (types FHF or BasicPlus or SSM)
Pos. 3 NC: 088H3110 / NO: 088H3111 xx pcs. thermal actuator, 24 V TWA-A
Pos. 4 088U0251 1 pc. dew point sensor, type CF-DS
OK
10 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application 0004: 2 pipe system with heat pump controlled changeover to cooling.
Optional: Dewpoint sensor (recommended), Circulation pump and heat demand signal.
Application description
Floor heating system with automatic changeover for cooling controlled by heat source e.g. heat pump. The heat pump provides the cooling signal to the Danfoss Icon™ Master, when the heat pump goes into cooling mode thus activating cooling mode. If connected, the system will control the circulation pump and it will be turned on when minimum 1 room has a heat or cooling demand. The heat signal for e.g. a boiler or heat pump is only activated when the system is in heating mode and minimum 1 room has a heat demand. For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point.
Settings
No settings necessary.
GB
APPLICATION
OK
OK
Settings on thermostat
Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling
would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide for further information.
Application test function
Not relevant.
Parts list
Pos. 1 NA 1 pc. heat pump
Pos. 2 088U05XX / 088U06XX / 088U07XX 1 set Danfoss Manifold (types FHF or BasicPlus or SSM)
Pos. 3 NC: 088H3110 / NO: 088H3111 xx pcs. thermal actuator, 24 V TWA-A
Pos. 4 088U0251 1 pc. dew point sensor, type CF-DS
© Danfoss | FEC | 2018.12 | 11VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application 0005: 2 pipe system with hybrid Air/water heat pump with inte­grated condensing boiler (example: Itho Cool Cube). Change over ordered from reference room thermostat.
Optional: Dewpoint sensor (recommended) and Global standby.
Application description
Floor heating system with cooling done via e.g. Coolcube used as heating and cooling source. The Icon™ system controls the heat and cooling demand by activating the corrosponding relay (PWR1 and potential free relay). For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. Four conditions must be true before cooling in a room is allowed:
Reference room temperature must exceed the room setpoint + cooling hysterhesis.
No room has called for heating within neutral time.
The dew point sensor must not be active / no condensation risk present.
The room thermostat must be enabled for cooling (default = enabled).
The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.
Settings
“SET 1” = Set desired cooling hysterhesis for change-over [+2 to +4K] “SET 2” = Set neutral time that must pass without active heating or cooling, before change-over can be
activated [3-6 Hrs.]
APPLICATION
SETTINGS
12 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
OK
OK
OK
OK
OK
OK
OK
OK
Installation Guide Expansion Module for Danfoss Icon™ Master
Settings on thermostat
Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling
would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide for further information. Choose reference room thermostat: To assign a thermostat as reference room thermostat, go to the desired reference room thermostat and in menu set to . When selected the thermostat will control when the system goes from heating mode to cooling mode based on the actual temperature in the room. It is only possible to have one reference thermostat per system and if more than one thermostats are assigned as reference, the last assigned will overwrite the previous reference room thermostats and cause these to revert to normal function.
Application test function
Enter the “Test” menu via the installer key. The Application test (APP test) is specific for each applica­tion. The test is split into steps to ensure that all compo­nents are installed correctly. Please follow the process.
Test steps
Step 1:3 During the first minute of the test, the heat
source is set to "heating mode" via "PWR1 output". Check on heat source user interface that heating is active. Step 2:3 During the second minute of the test, the heat source is set to "cooling mode" via "Relay output". Check on heat source user interface that cooling is active Step 3:3 During the third minute of the test, the heat source is set to "neutral mode", neither heating nor cooling is active.
RUN
INSTALL
UNINSTALL
TEST
TEST NET
TEST APP
TEST FL
OK
O
GB
Parts list
Pos. 1 NA 1 pc. e.g. Coolcube
Pos. 2 088U05XX / 088U06XX / 088U07XX 1 set Danfoss Manifold (types FHF or BasicPlus or SSM)
Pos. 3 NC: 088H3110 / NO: 088H3111 xx pcs. thermal actuator, 24 V TWA-A
Pos. 4 088U0251 1 pc. dew point sensor, type CF-DS
Pos. 5. NA
External relay (convert 230 V to potential free relay), not supplied by Danfoss
© Danfoss | FEC | 2018.12 | 13VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application 0006: 3-pipe system with cooling control via motorized valve and common return, change over signal ordered by reference room thermostat.
Optional: Dewpoint sensor (recommended), Global standby and heat demand signal relay.
Application description
3 -pipe Floor heating system with cooling controlled via motorized valve and common return. The Icon™ system controls the heat and cooling demand by activating the corresponding relay (PWR1 and PWR2). For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. Four conditions must be true before cooling in a room is allowed:
Reference room temperature must exceed the room setpoint + cooling hysterhesis.
No room has called for heating within neutral time.
The dew point sensor must not be active / no condensation risk present.
The room thermostat must be enabled for cooling (default = enabled).
The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.
Settings
“SET 1” = Set desired cooling hysterhesis for change-over [+2 to +4K] “SET 2” = Set neutral time that must pass without active heating or cooling, before change-over can be
activated [3-6 Hrs.]
APPLICATION
SETTINGS
14 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
OK
OK
OK
OK
OK
OK
OK
OK
Installation Guide Expansion Module for Danfoss Icon™ Master
Settings on thermostat
Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling
would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide for further information. Choose reference room thermostat: To assign a thermostat as reference room thermostat, go to the desired reference room thermostat and in menu set to . When selected the thermostat will control when the system goes from heating mode to cooling mode based on the actual temperature in the room. It is only possible to have one reference thermostat per system and if more than one thermostats are assigned as reference, the last assigned will overwrite the previous reference room thermostats and cause these to revert to normal function.
Application test function
Enter the “Test” menu via the installer key. The Application test (APP test) is specific for each applica­tion. The test is split into steps to ensure that all compo­nents are installed correctly. Please follow the process.
Test steps
Step 1:2 During the first minute of the test, the AMZ 113
valve is set to "heating mode" via "PWR1 output going ON". Check on valve/actuator that position is correct for "heating". Step 2:2 During the second minute of the test, the AMZ 113 valve is set to "cooling mode" via "PWR1 output going OFF". Check on valve/actuator that position is correct for "Cooling".
RUN
INSTALL
UNINSTALL
TEST
TEST NET
TEST APP
TEST FL
OK
O
GB
Parts list
Pos. 1 DN15: 082G5511 DN20: 088G5512 1 pc. AMZ 113 (3 -way valve)
Pos. 2 088U05XX / 088U06XX / 088U07XX 1 set Danfoss Manifold (types FHF or BasicPlus or SSM)
Pos. 3 NC: 088H3110 / NO: 088H3111 xx pcs. thermal actuator, 24 V TWA-A
Pos. 4 088U0251 1 pc. dew point sensor, type CF-DS
© Danfoss | FEC | 2018.12 | 15VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application 0007: 3-pipe system with cooling control via thermal actuators and common return controlled by reference room thermostat.
Optional: Dewpoint sensor (recommended), Global standby, pump relay and heat demand signal.
Application description
3 -pipe Floor heating system with cooling controlled via thermal actuators and common return. The Icon™ system controls the heat and cooling demand by activating the corresponding outputs (M1 and M2). For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. Four conditions must be true before cooling in a room is allowed:
Reference room temperature must exceed the room setpoint + cooling hysterhesis.
No room has called for heating within neutral time.
The dew point sensor must not be active / no condensation risk present.
The room thermostat must be enabled for cooling (default = enabled).
The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.
Settings
“SET 1” = Set desired cooling hysterhesis for change-over [+2 to +4K] “SET 2” = Set neutral time that must pass without active heating or cooling, before change-over can be
activated [3-6 Hrs.]
APPLICATION
SETTINGS
16 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
OK
OK
OK
OK
OK
OK
OK
OK
Installation Guide Expansion Module for Danfoss Icon™ Master
Settings on thermostat
Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling
would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide for further information. Choose reference room thermostat: To assign a thermostat as reference room thermostat, go to the desired reference room thermostat and in menu set to . When selected the thermostat will control when the system goes from heating mode to cooling mode based on the actual temperature in the room. It is only possible to have one reference thermostat per system and if more than one thermostats are assigned as reference, the last assigned will overwrite the previous reference room thermostats and cause these to revert to normal function.
Application test function
Enter the “Test” menu via the installer key. The Application test (APP test) is specific for each applica­tion. The test is split into steps to ensure that all compo­nents are installed correctly. Please follow the process.
Test steps Step 1:3 During the first five minutes, the output 1
is set to "ON" = heating mode/hot flow side (up to 3 minutes opening time can be expected). Step 2:3 During next five minutes, the output 1 is set to "OFF", and the outputs 3 & 4 are set to "ON" = cooling mode/cold flow side (up to 3 minutes opening time can be expected). Step 3:3 During last 5 minutes, all outputs 1 and 2 should close.
RUN
INSTALL
UNINSTALL
TEST
TEST NET
TEST APP
TEST FL
OK
O
GB
Parts list
Pos. 1 DN15: 013G3094 DN20: 013G3016 2 pcs. RA-C valve
Pos. 2 088U05XX / 088U06XX / 088U07XX 1 set Danfoss Manifold (types FHF or BasicPlus or SSM)
Pos. 3 NC: 088H3110 / NO: 088H3111 xx pcs. thermal actuator, 24 V TWA-A
Pos. 4 088U0251 1pc. dew point sensor, type CF-DS
Pos. 5a & 5b 088H3110 2 pcs. thermal actuator, 24 V TWA-A
© Danfoss | FEC | 2018.12 | 17VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application 0008: 3-pipe system with cooling control via motorized actuators and common return controlled by reference room thermostat.
Optional: Dewpoint sensor (recommended), Global standby, pump relay and heat demand signal.
Application description
3 -pipe Floor heating system with cooling controlled via motorized actuators and common return. The Icon™ system controls the heat and cooling demand by activating the corrosponding outputs (PWR1 and potential free relay). For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. Four conditions must be true before cooling in a room is allowed:
Reference room temperature must exceed the room setpoint + cooling hysterhesis.
No room has called for heating within neutral time.
The dew point sensor must not be active / no condensation risk present.
The room thermostat must be enabled for cooling (default = enabled)
If no heating or cooling demand is present, the two shut-off valves will close (AMZ 112). The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.
Settings
“SET 1” = Set desired cooling hysterhesis for change-over [+2 to +4K] “SET 2” = Set neutral time that must pass without active heating or cooling, before change-over can be
activated [3-6 Hrs.]
APPLICATION
SETTINGS
18 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
OK
OK
OK
OK
OK
OK
OK
OK
Installation Guide Expansion Module for Danfoss Icon™ Master
Settings on thermostat
Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling
would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide for further information. Choose reference room thermostat: To assign a thermostat as reference room thermostat, go to the desired reference room thermostat and in menu set to . When selected the thermostat will control when the system goes from heating mode to cooling mode based on the actual temperature in the room. It is only possible to have one reference thermostat per system and if more than one thermostats are assigned as reference, the last assigned will overwrite the previous reference room thermostats and cause these to revert to normal function.
Application test function
Enter the “Test” menu via the installer key. The Application test (APP test) is specific for each applica­tion. The test is split into steps to ensure that all compo­nents are installed correctly. Please follow the process.
Test steps
Step 1:3 During the first minute of the test, the AMZ 112
valve of the hot flow side is set to "heating mode" via "PWR1 output going ON". Check on valve/actuator that position is correct for "heating". Step 2:3 During the second minute of the test, the AMZ 112 valve on the cold flow side is set to "cooling mode" via "PWR1 output going OFF" and "Relay output" going ON. Check on valve/actuator that position is correct for "cooling". Step 3:3 During last minute of the test, botm AMZ 112 valves are closed.
RUN
INSTALL
UNINSTALL
TEST
TEST NET
TEST APP
TEST FL
OK
O
GB
Parts list
Pos. 1a & 1b DN15: 082G5511 DN20: 082G5512 2 pcs. AMZ112
Pos. 2 088U05XX / 088U06XX / 088U07XX 1 set Danfoss Manifold (types FHF or BasicPlus or SSM)
Pos. 3 NC: 088H3110 / NO: 088H3111 xx pcs. thermal actuator, 24 V TWA-A
Pos. 4 088U0251 1 pc. dew point sensor, Type CF-DS
© Danfoss | FEC | 2018.12 | 19VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application 0009: 4-pipe system with 6-port valve, automatic change over for cooling controlled by a reference room thermostat. (Require external 24 VAC PSU).
Optional: Dewpoint sensor (recommended), shut-off function and Global standy.
Application description
Floor heating system with automatic changeover for cooling via 6-way changeover valve controlled by a reference room thermostat. The system can be configured with optional shut off function via a Danfoss AMZ-112 2-way ball valve and Global standby. For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. Four conditions must be true before cooling in a room is allowed:
Reference room temperature must exceed the room setpoint + cooling hysterhesis.
No room has called for heating within neutral time.
The dew point sensor must not be active / no condensation risk present.
The room thermostat must be enabled for cooling (default = enabled).
If no heating or cooling demand is present, the shut-off valve will close. The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.
Settings
“SET 1” = Set desired cooling hysterhesis for change-over [+2 to +4K] “SET 2” = Set neutral time that must pass without active heating or cooling, before change-over can be
activated [3-6 Hrs.]
APPLICATION
SETTINGS
20 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
OK
OK
OK
OK
OK
OK
OK
OK
Installation Guide Expansion Module for Danfoss Icon™ Master
Settings on thermostat
Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling
would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide for further information. Choose reference room thermostat: To assign a thermostat as reference room thermostat, go to the desired reference room thermostat and in menu set to . When selected the thermostat will control when the system goes from heating mode to cooling mode based on the actual temperature in the room. It is only possible to have one reference thermostat per system and if more than one thermostats are assigned as reference, the last assigned will overwrite the previous reference room thermostats and cause these to revert to normal function.
Application test function
Enter the “Test” menu via the installer key. The Application test (APP test) is specific for each applica­tion. The test is split into steps to ensure that all compo­nents are installed correctly. Please follow the process.
RUN
INSTALL
UNINSTALL
TEST
Test steps
Step 1:3 During the first two minutes, the AMZ 112 valve
goes to position "Flow" and the ChangeOver6 valve goes to position "Cooling" for 1 minute. Step 2:3 The ChangeOver6 valve now goes to position "Heating" for 1 minute.
Step 3:3 The AMZ 112 valve goes to position "No Flow".
Parts list
Pos. 1 DN 15: 003Z3150 / DN 20: 003Z31511 1 pc. Danfoss ChangeOver6 6-port valve
Pos. 2 003Z3155 1 pc. Danfoss ChangeOver6 actuator
Pos. 3 DN15: 082G5501 / DN20: 082G55021 1 pc. AMZ 112
Pos. 4 088U05XX / 088U06XX / 088U07XX 1 pc. Danfoss manifold (types FHF or BasicPlus or SSM)
Pos. 5 N/A
Pos. 6 088U0251 1 pc. dew point sensor, type CF-DS
Pos. 7 NC: 088H3110 / NO: 088H3111 xx pcs. thermal actuator, 24 V TWA-A
1 pc. external power supply 230 V->24 VAC, not supplied by Danfoss. Minimum 5 VA output on 24 V side.
TEST NET
TEST APP
TEST FL
OK
O
GB
© Danfoss | FEC | 2018.12 | 21VIMDE20F / 088N2100
Installation Guide Expansion Module for Danfoss Icon™ Master
Application 0010: 4-pipe system with 2-way valves on supply pipes and automatic change over for cooling controlled by a reference room thermostat.
Optional: Dewpoint sensor (recommended), circulation pump, heat demand signal and Global standby.
Application description
4-pipe system with 2-way valves on supply pipes and automatic change over for cooling controlled by reference room thermostat. The system activates cooling mode via 2-way valves with thermal actuators on supply and return side by activating the corresponding outputs (M1 - M4). Note: In this application outputs 1, 2, 3 & 4 on Danfoss Icon
Master is used for the application and cannot be assigned to thermostats.
For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. Four conditions must be true before cooling in a room is allowed:
Reference room temperature must exceed the room setpoint + cooling hysterhesis.
No room has called for heating within neutral time.
The dew point sensor must not be active / no condensation risk present.
The room thermostat must be enabled for cooling (default = enabled).
The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.
Settings
“SET 1” = Set desired cooling hysterhesis for change-over [+2 to +4K] “SET 2” = Set neutral time that must pass without active heating or cooling, before change-over can be
activated [3-6 Hrs.]
APPLICATION
SETTINGS
22 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
OK
OK
OK
OK
OK
OK
OK
OK
Installation Guide Expansion Module for Danfoss Icon™ Master
Settings on thermostat
Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling
would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide for further information. Choose reference room thermostat: To assign a thermostat as reference room thermostat, go to the desired reference room thermostat and in menu set to . When selected the thermostat will control when the system goes from heating mode to cooling mode based on the actual temperature in the room. It is only possible to have one reference thermostat per system and if more than one thermostats are assigned as reference, the last assigned will overwrite the previous reference room thermostats and cause these to revert to normal function.
Application test function
Enter the “Test” menu via the installer key. The Application test (APP test) is specific for each applica­tion. The test is split into steps to ensure that all compo­nents are installed correctly. Please follow the process.
Test steps
Step 1:3 During the first five minutes, the outputs 1&2 are
set to "ON" = heating mode/hot flow side (up to 3 minutes opening time can be expected). Step 2:3 During next five minutes, the outputs 1&2 are set to "OFF", and the outputs 3 & 4 are set to "ON" = cooling mode/cold flow side (up to 3 minutes opening time can be expected). Step 3:3 During last 5 minutes, all outputs 1, 2, 3 and 4 should close.
RUN
INSTALL
UNINSTALL
TEST
TEST NET
TEST APP
TEST FL
OK
O
GB
Parts list
Pos. 1 DN15: 013G3094 DN20: 013G3016 4 pcs. RA-C valve
Pos. 2 088U05XX / 088U06XX / 088U07XX 1 pc. Danfoss manifold (types FHF or BasicPlus or SSM)
Pos. 3 NC: 088H3110 / NO: 088H3111 xx pcs. thermal actuator, 24 V TWA-A
Pos. 4 088U0251 1 pc. dew point sensor, type CF-DS
Pos. 5 NC: 088H3110 2 pcs. thermal actuator, 24 V TWA-A
Pos. 6 NC: 088H3110 2 pcs. thermal actuator, 24 V TWA-A
© Danfoss | FEC | 2018.12 | 23VIMDE20F / 088N2100
Installationsanleitung Erweiterungsmodus für Danfoss Icon™ Master
Die Verdrahtung gemäß dem Schaltdiagramm durchführen und
1
APPLICATION
anschließend das Erweiterungsmodul für zusätzliche Funktionen in den Danfoss Icon™ Hauptregler einführen.
2
IN 1
SETTINGS
IN 2 IN 3
3
1. Mit dieser Taste können Sie die Anwendung auswählen. Drücken Sie die Anwendungstaste, wählen Sie mit und Anwendung 1-11 aus und bestätigen Sie mit „OK“. Wählen Sie die geeignete Anwendung mithilfe der Anwen­dungszeichnungen aus.
2. Mit dieser Taste können Sie anwendungsspezifische Einstel­lungen einstellen. Die für die ge­wählte Anwendung verfügbaren Einstellungen sind in der Anwen­dungsbeschreibung aufgeführt.
3. LED-Leuchten zeigen den Status der Eingänge 1 bis 3 an. Vgl. die Anwendungsbeschreibung für die jeweilige Anwendung.
4. Anschlussklemmen für den An­schluss verschiedener Verdrahtun­gen/externer Geräte.
5. Kabel-Zugentlastung.
6. Lösevorrichtung für Verdrahtung/ Kabel.
4
IN 3 IN 2 IN 1
PWR3
PT
24
1000
VDC
5
6
24 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
Installationsanleitung Erweiterungsmodus für Danfoss Icon™ Master
Anwendung 0001: Zweirohrsystem, vorgegebene Zulufttemperatur, elektro­nisch kontrolliert.
Optional: Global Standby.
Anwendungsbeschreibung
Fußbodenheizungssystem mit elektronischer Regelung der Zulufttemperatur. Die Zulufttemperatur ist auf einen vorgegebenen Wert eingestellt. Das System nutzt einen PT1000-Fühler, um die Zulufttemperatur zu erkennen und zu regeln, und wird auch eingesetzt, um sicherzustellen, dass die Temperatur nicht die zulässige Höchsttemperatur übersteigt. Wenn verbunden, steuert das System die Umwälzpumpe und das Heizbedarfssignal, beispielsweise für einen Kessel oder eine Wärmepumpe. Die Pumpe und das Heizbedarfssignal sind eingeschaltet, wenn bei min­destens einem Kreislauf Heizbedarf besteht. Ausgang 1 muss für TWA an der Mischergruppe verwendet
werden.
Das Globale Standby ist ein potentialfreier Eingang, mit dem das System per Fernzugriff in den Globalen Abwesenheitsmodus versetzt werden kann, z. B. über ein externes GSM-Modul eines Drittanbieters. Wenn der globale Standby-Eingang aktiv ist, erhalten alle Räume einen Sollwert von 15 Grad Celsius.
Einstellungen
„SET 1“ = Gewünschte Vorlauftemperatur [25-70 °C] einstellen „SET 2“ = Gewünschte Sicherheits-Abschalttemperatur [30-75 °C] einstellen
Hinweis: Die Temperatur muss über der Vorlauftemperatur liegen.
APPLICATION
SETTINGS
OK
OK
OK
OK
OK
OK
OK
OK
© Danfoss | FEC | 2018.12 | 25VIMDE20F / 088N2100
Installationsanleitung Erweiterungsmodus für Danfoss Icon™ Master
Anwendungstestfunktion
Rufen Sie über die Installateurstaste das Menü „Test“ auf. Der Anwendungstest (APP-Test) ist anwendungsspezifisch. Der Test ist in mehrere Schritte unterteilt, um sicherzustel­len, dass alle Komponenten ordnungsgemäß installiert werden. Befolgen Sie bitte das Verfahren.
RUN INSTALL UNINSTALL
TEST
TEST NET
TEST APP
TEST FL
OK
O
Testschritte
Schritt 1:1 Gehen Sie zum Regelventilantrieb der Mischer-
gruppe und überprüfen Sie, ob sich das Ventil vollständig öffnet (es sind bis zu drei Minuten Öffnungszeit zu erwar­ten). Nach fünf Minuten schließt sich der Ventilantrieb der Mischergruppe wieder. Während der fünfminütigen Testphase zeigt das Display am Hauptregler auch die gemessene Vorlauftemperatur an.
Teileliste
Pos. 1 088U0093-96 1 Stk. Danfoss FHM-Cx Mischergruppe
Pos. 2 088U05XX/088U06XX/088U07XX 1 Satz Danfoss Verteiler (Typen FHF oder BasicPlus oder SSM)
Pos. 3 NC: 088H3110/NO: 088H3111 xx Stk. Thermischer Stellantrieb, 24 V TWA-A
Pos. 4 087B1165 1 Stk. ESM-11 PT-1000 Fühler
Pos. 5. NC: 088H3110/NC: 193B2148 1 Stk. Thermischer Stellantrieb, 24 V (Typen TWA-A oder ABN-FBH)
26 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
Installationsanleitung Erweiterungsmodus für Danfoss Icon™ Master
Anwendung 0002: Zweirohrsystem mit bedarfsbasierter Regelung der Zulufttemperatur.
Optional: Globales Standby.
Anwendungsbeschreibung
Fußbodenheizungssystem mit elektronischer Regelung der Zulufttemperatur. Die bedarfsbasierte Zulufttemperatur wird je nach dem Heizbedarf aus den Räumen geregelt. Das System nutzt einen PT1000-Fühler, um die Zulufttemperatur zu erkennen, und wird auch eingesetzt, um mithilfe eines Sicherheits-Tmax sicherzustellen, dass die Temperatur nicht die zulässige Höchsttemperatur über­steigt. Wenn verbunden, steuert das System die Umwälzpumpe und das Heizbedarfssignal, beispielsweise für einen Kessel oder eine Wärmepumpe. Die Pumpe und das Heizbedarfssignal sind eingeschaltet, wenn bei mindestens einem Kreislauf Heizbedarf besteht. Ausgang 1 muss für TWA an der Mischergruppe
verwendet werden.
Das Globale Standby ist ein potentialfreier Eingang, mit dem das System per Fernzugriff in den Globalen Abwesenheitsmodus versetzt werden kann, z. B. über ein externes GSM-Modul eines Drittanbieters. Wenn der globale Standby-Eingang aktiv ist, erhalten alle Räume einen Sollwert von 15 Grad Celsius.
Einstellungen
“SET 1” = Set desired min. supply flow temperature [25-65°C] „SET 1“ = Gewünschte minimale Vorlauftemperatur [25-65 °C] einstellen „SET 2“ = Gewünschte maximale Vorlauftemperatur [30-70 °C] einstellen
Hinweis: Die Temperatur muss mindestens 5 °C höher als die minimale Vorlauftemperatur eingestellt werden.
„SET 3“ = Gewünschte Sicherheits-Abschalttemperatur [30-75 °C] einstellen
Hinweis: Die Temperatur muss über der Vorlauftemperatur liegen.
APPLICATION
SETTINGSSETTINGS
OK
OKOK
OK
OKOK
OKOK
OKOK
OKOK
OKOK
OKOK
OKOK
OKOK
© Danfoss | FEC | 2018.12 | 27VIMDE20F / 088N2100
Installationsanleitung Erweiterungsmodus für Danfoss Icon™ Master
Anwendungstestfunktion
Rufen Sie über die Installateurstaste das Menü „Test“ auf. Der Anwendungstest (APP-Test) ist anwendungsspezifisch. Der Test ist in mehrere Schritte unterteilt, um sicherzustel­len, dass alle Komponenten ordnungsgemäß installiert werden. Befolgen Sie bitte das Verfahren.
Testschritte
Schritt 1:1 Gehen Sie zum Regelventilantrieb der Mischer-
gruppe und überprüfen Sie, ob sich das Ventil vollständig öffnet (es sind bis zu drei Minuten Öffnungszeit zu erwar­ten). Nach fünf Minuten schließt sich der Ventilantrieb der Mischergruppe wieder. Während der fünfminütigen Testphase zeigt das Display am Hauptregler auch die gemessene Vorlauftemperatur an.
Teileliste
Pos. 1
Pos. 2
Pos. 3
Pos. 4
Pos. 5.
088U0093-96 1 Stk. Danfoss FHM-Cx Mischergruppe
088U05XX/088U06XX/088U07XX 1 Satz Danfoss Verteiler (Typen FHF oder BasicPlus oder SSM)
NC: 088H3110/NO: 088H3111 xx Stk. Thermischer Stellantrieb, 24 V TWA-A
087B1165 1 Stk. ESM-11 PT-1000 Fühler
NC: 088H3110/NC: 193B2148 1 Stk. Thermischer Stellantrieb, 24 V (Typen TWA-A oder ABN-FBH)
RUN INSTALL UNINSTALL
TEST
TEST NET
TEST APP
TEST FL
OK
O
28 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
Installationsanleitung Erweiterungsmodus für Danfoss Icon™ Master
Anwendung 0003: Zweirohrsystem mit automatischer Umschaltung zur Kühlung auf der Grundlage der Zulufttemperatur.
Optional: Taupunktfühler (empfohlen), Globales Standby, Umwälzpumpe und Heizbedarfssignal.
Anwendungsbeschreibung
Fußbodenheizungssystem mit automatischer Umschaltung zur Kühlung auf der Grundlage des Zulufttem­peratureingangs. Die Zulufttemperatur wird mittels eines PT1000-Fühlers überwacht. Je nach Messung schaltet das System von Heizung auf Kühlung um. Wenn verbunden, steuert das System die Umwälzpumpe, die eingeschaltet wird, wenn mindestens ein Raum Heiz- oder Kühlbedarf hat. Das Heizsignal für beispielsweise einen Kessel oder eine Wärmepumpe wird nur aktiviert, wenn sich das System im Heizmodus befindet und mindestens ein Raum Heizbedarf hat. Für Kühlanwendungen empfiehlt es sich immer, im System einen Taupunktfühler installiert zu haben, um Feuchtigkeitsschäden an Boden und Installationen zu vermeiden, wenn die relative Luftfeuchte den Taupunkt übersteigt. Das Globale Standby ist ein potentialfreier Eingang, mit dem das System per Fernzugriff in den Globalen Abwesenheitsmodus versetzt werden kann, z. B. über ein externes GSM-Modul eines Drittanbieters. Wenn der globale Standby-Eingang aktiv ist, erhalten alle Räume einen Sollwert von 15 Grad Celsius.
Einstellungen
„SET 1“ = Vorlauftemperatur für die Umschaltung zum Heizen [25-55 °C] einstellen „SET 2“ = Vorlauftemperatur für die Umschaltung zum Kühlen [15-25 °C] einstellen
Hinweis: Die Temperatur kann nicht höher als 2 °C unter der Umschalttemperatur zum Heizen eingestellt werden.
APPLICATION
SETTINGS
OK
OK
OK
OK
OK
OK
OK
OK
Einstellungen des Thermostats
Räume von der Kühlung ausschließen: Um einen Raum von der Kühlung auszuschließen, etwa ein Bade-
zimmer, in dem eine Kühlung unangenehm wäre, den Thermostat aufsuchen und Menü auf einstellen. Weitere Informationen sind in der Installationsanleitung des Thermostats enthalten.
© Danfoss | FEC | 2018.12 | 29VIMDE20F / 088N2100
Installationsanleitung Erweiterungsmodus für Danfoss Icon™ Master
Anwendungstestfunktion
Rufen Sie über die Installateurstaste das Menü „Test“ auf. Der Anwendungstest (APP-Test) ist anwendungsspezifisch. Der Test ist in mehrere Schritte unterteilt, um sicherzustel­len, dass alle Komponenten ordnungsgemäß installiert werden. Befolgen Sie bitte das Verfahren.
Testschritte
Schritt 1:1 Während der einminütigen Testphase zeigt das
Display am Hauptregler die gemessene Vorlauftemperatur an.
Teileliste
Pos. 1
Pos. 2
Pos. 3
Pos. 4
087B1165 1 Stk. ESM-11 PT1000 Fühler
088U05XX/088U06XX/088U07XX 1 Satz Danfoss Verteiler (Typen FHF oder BasicPlus oder SSM)
NC: 088H3110/NO: 088H3111 xx Stk. Thermischer Stellantrieb, 24 V TWA-A
088U0251 1 Stk. Taupunktfühler, Typ CF-DS
RUN INSTALL UNINSTALL
TEST
TEST NET
TEST APP
TEST FL
OK
O
30 | © Danfoss | FEC | 2018.12 VIMDE20F / 088N2100
Loading...
+ 294 hidden pages