Danfoss Expansion Module Installation guide [da]

Installation Guide

Expansion Module

for Danfoss Icon™ Master

AN28953970588601-000201 | VIMDE20F | 088N2100

© Danfoss | FEC | 2018.12 | 1

Installation Guide

Expansion Module for Danfoss Icon™ Master

2 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installation Guide

Expansion Module for Danfoss Icon™ Master

 

 

 

Content

 

 

 

 

Expansion Module for Danfoss Icon™ Master

4

 

 

 

. .GB. . . .

Expansion Module for Danfoss Icon™ Master

24

 

 

 

. .DE. . . .

Expansion Module for Danfoss Icon™ Master

44

 

 

 

. .FR. . . .

Expansion Module for Danfoss Icon™ Master

64

 

 

 

. .IT. . . .

Expansion Module for Danfoss Icon™ Master

84

 

 

 

. .NL. . . .

Expansion Module for Danfoss Icon™ Master

104

 

 

 

. .DK. . .

Expansion Module for Danfoss Icon™ Master

124

 

 

 

. .SE. . .

Expansion Module for Danfoss Icon™ Master

144

 

 

 

. .NO. . .

Expansion Module for Danfoss Icon™ Master

164

 

 

 

. .IS. . .

Expansion Module for Danfoss Icon™ Master

184

 

 

 

. .FI. . .

Expansion Module for Danfoss Icon™ Master

 

 

 

204. . . .

 

. .CN. . .

 

 

 

 

Expansion Module for Danfoss Icon™ Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

224. . . .

 

. .LT. . .

 

 

 

 

Expansion Module for Danfoss Icon™ Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

244. . . .

 

. .PL. . .

 

 

 

 

Expansion Module for Danfoss Icon™ Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

264. . . .

 

. .TR. . .

 

 

 

 

Expansion Module for Danfoss Icon™ Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

284. . . .

 

. .UA. . .

 

 

 

 

Expansion Module for Danfoss Icon™ Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

304. . . .

 

. .RU. . .

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 3

Installation Guide

Expansion Module for Danfoss Icon™ Master

 

 

 

 

Perform wirring according to electrical

 

 

 

diagram, then insert the Expansion

1

 

 

Module into the Danfoss Icon™ Master

 

 

Controller for extra features.

 

APPLICATION

 

 

 

2

 

 

1. Use this key to choose application.

 

 

Press application key and then use

 

SETTINGS

 

 

3

and

to choose application

 

 

 

 

 

1-11 and confirm with “OK”. See

IN 1

IN 2

IN 3

applications drawings to help you

choose the correct application.

 

 

 

 

 

 

2. Use the key to set application

 

 

 

specific settings. See in application

 

 

 

description which settings are

 

 

 

available for the chosen application.

 

 

 

3. LED’s indicate the state of the inputs

 

 

 

1 to 3. See application description

 

 

 

for the specific application.

 

 

 

4. Terminals for connection of various

 

 

 

wiring /external devices.

 

 

 

5. Cable strain relief.

6. Break away for wiring /cables.

4

 

 

 

PWR3

IN 3

IN 2

IN 1

24

PT

 

 

VDC

1000

 

 

5

6

4 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installation Guide Expansion Module for Danfoss Icon™ Master

Application 0001: 2-pipe system, fixed supply temperature, electronically controlled.

Optional: Global standby. GB

Application description

Floor heating system with electronic supply temperature control. The supply temperature is set to a fixed value.

The system uses a PT1000 sensor to detect and control the supply temperature and is also used to ensure that the temperature does not exceed the max. allowed temperature. If connected, the system will control the circulation pump and the heat demand signal for e.g. a boiler or heat pump. The pump and heat demand signal will be on when minimum 1 circuit has a heat demand. Output 1 must be used for TWA on mixing shunt.

The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.

Settings

“SET 1” = Set desired supply flow temperature [25-70°C] “SET 2” = Set desired safety cut-off temperature [30-75°C]

Note: temperature must be higher than flow temperature.

APPLICATION

OK

 

SETTINGS

OK

OK

OK

OK

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 5

Installation Guide Expansion Module for Danfoss Icon™ Master

Application test function

Enter the “Test” menu via the installer key.

The Application test (APP test) is specific for each application. The test is split into steps to ensure that all components are installed correctly. Please follow the process.

Test steps

Step 1:1 Go to mixing shunt control valve actuator, and verify that the valve opens fully (up to 3 minutes opening time can be expected). After 5 minutes, the mixing shunt valve actuator will close again.

During the 5 minute test period, the display on the Master Controller will also show the measured supply flow temperature in the display.

Parts list

Pos. 1

088U0093-96

1 pc. Danfoss FHM-Cx Mixing shunt

 

 

 

Pos. 2

088U05XX / 088U06XX / 088U07XX

1 set Danfoss Manifold (types FHF or BasicPlus or SSM)

 

 

 

Pos. 3

NC: 088H3110 / NO: 088H3111

xx pcs. thermal actuator, 24 V TWA-A

 

 

 

Pos. 4

087B1165

1 pc. ESM-11 PT-1000 sensor

 

 

 

Pos. 5.

NC: 088H3110 / NC: 193B2148

1 pc. thermal actuator, 24 V (types TWA-A or ABN-FBH)

 

 

 

6 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Danfoss Expansion Module Installation guide

Installation Guide Expansion Module for Danfoss Icon™ Master

Application 0002: 2-pipe system with demand based supply temperature control.

Optional: Global standby. GB

Application description

Floor heating system with electronic supply temperature control.

The demand based supply temperature is controlled depending on the heat demand from the rooms. The system uses a PT1000 sensor to detect the supply temperature and is also used to ensure that the temperature does not exceed the max. allowed temperature via a safety Tmax. If connected, the system

will control the circulation pump and the heat demand signal for e.g. a boiler or heat pump. The pump and heat demand signal will be on when minimum 1 circuit has a heat demand. Output 1 must be used for

TWA on mixing shunt.

The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.

Settings

“SET 1” = Set desired min. supply flow temperature [25-65°C] “SET 2” = Set desired max. supply flow [30-70°C]

Note: temperature cannot be set less than 5°C higher than min. supply flow temperature.

“SET 3” = Set desired safety cut-off temperature [30-75°C]

Note: temperature must be higher than flow temperature.

APPLICATION

OK

 

SETTINGS

OK

OK

OK

OK

OK

OK

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 7

Installation Guide Expansion Module for Danfoss Icon™ Master

Application test function

Enter the “Test” menu via the installer key.

The Application test (APP test) is specific for each application. The test is split into steps to ensure that all components are installed correctly. Please follow the process.

Test steps

Step 1:1 Go to mixing shunt control valve actuator, and verify that the valve opens fully (up to 3 minutes opening time can be expected). After 5 minutes, the mixing shunt valve actuator will close again.

During the 5 minute test period, the display on the master controller will also show the measured supply flow temperature in the display.

Parts list

Pos. 1

088U0093-96

1 pc. Danfoss FHM-Cx Mixing shunt

 

 

 

Pos. 2

088U05XX / 088U06XX / 088U07XX

1 set Danfoss Manifold (types FHF or BasicPlus or SSM)

 

 

 

Pos. 3

NC: 088H3110 / NO: 088H3111

xx pcs. thermal actuator, 24 V TWA-A

 

 

 

Pos. 4

087B1165

1 pc. ESM-11 PT-1000 sensor

 

 

 

Pos. 5.

NC: 088H3110 / NC: 193B2148

1 pc. thermal actuator, 24 V (types TWA-A or ABN-FBH)

 

 

 

8 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installation Guide

Expansion Module for Danfoss Icon™ Master

Application 0003: 2-pipe system with automatic changeover for cooling based on supply temperature.

Optional: Dewpoint sensor (recommended), Global standby, Circulation pump and heat demand GB signal.

Application description

Floor heating system with automatic changeover for cooling based on supply temperature input. The supply temperature is monitered using a PT1000 sensor. Based on the measurement, the system

switches to heating or cooling. If connected, the system will control the circulation pump which will be turned on when minimum 1 room has a heat or cooling demand.

The heat signal for e.g. a boiler or heat pump is only activated when the system is in heating mode and minimum 1 room has a heat demand. For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point.

The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.

Settings

“SET 1” = Set supply flow temperature for change-over to heating [25-55°C] “SET 2” = Set supply flow temperature for change-over to cooling [15-25°C]

Note: temperature cannot be set higher than 2°C lower than heating change-over temperature.

APPLICATION

OK

 

SETTINGS

OK

OK

OK

OK

Settings on thermostat

Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide for further information.

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 9

Installation Guide Expansion Module for Danfoss Icon™ Master

Application test function

Enter the “Test” menu via the installer key.

The Application test (APP test) is specific for each application. The test is split into steps to ensure that all components are installed correctly. Please follow the process.

Test steps

Step 1:1 During the 1 minute test period, the display on the master controller will show the measured supply flow temperature in the display.

Parts list

Pos. 1

087B1165

1 pc. ESM-11 PT1000 sensor

 

 

 

Pos. 2

088U05XX / 088U06XX / 088U07XX

1 set Danfoss Manifold (types FHF or BasicPlus or SSM)

 

 

 

Pos. 3

NC: 088H3110 / NO: 088H3111

xx pcs. thermal actuator, 24 V TWA-A

 

 

 

Pos. 4

088U0251

1 pc. dew point sensor, type CF-DS

 

 

 

10 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installation Guide Expansion Module for Danfoss Icon™ Master

Application 0004: 2 pipe system with heat pump controlled changeover to cooling.

Optional: Dewpoint sensor (recommended), Circulation pump and heat demand signal. GB

Application description

Floor heating system with automatic changeover for cooling controlled by heat source e.g. heat pump. The heat pump provides the cooling signal to the Danfoss Icon™ Master, when the heat pump goes into cooling mode thus activating cooling mode. If connected, the system will control the circulation pump and it will be turned on when minimum 1 room has a heat or cooling demand.

The heat signal for e.g. a boiler or heat pump is only activated when the system is in heating mode and minimum 1 room has a heat demand. For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point.

Settings

No settings necessary.

APPLICATION

OK

Settings on thermostat

Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide for further information.

Application test function

Not relevant.

Parts list

Pos. 1

NA

1 pc. heat pump

 

 

 

Pos. 2

088U05XX / 088U06XX / 088U07XX

1 set Danfoss Manifold (types FHF or BasicPlus or SSM)

 

 

 

Pos. 3

NC: 088H3110 / NO: 088H3111

xx pcs. thermal actuator, 24 V TWA-A

 

 

 

Pos. 4

088U0251

1 pc. dew point sensor, type CF-DS

 

 

 

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 11

Installation Guide

Expansion Module for Danfoss Icon™ Master

Application 0005: 2 pipe system with hybrid Air/water heat pump with integrated condensing boiler (example: Itho Cool Cube). Change over ordered from reference room thermostat.

Optional: Dewpoint sensor (recommended) and Global standby.

Application description

Floor heating system with cooling done via e.g. Coolcube used as heating and cooling source.

The Icon™ system controls the heat and cooling demand by activating the corrosponding relay (PWR1 and potential free relay). For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. Four conditions must be true before cooling in a room is allowed:

Reference room temperature must exceed the room setpoint + cooling hysterhesis.

No room has called for heating within neutral time.

The dew point sensor must not be active / no condensation risk present.

The room thermostat must be enabled for cooling (default = enabled).

The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.

Settings

“SET 1” = Set desired cooling hysterhesis for change-over [+2 to +4K]

“SET 2” = Set neutral time that must pass without active heating or cooling, before change-over can be activated [3-6 Hrs.]

APPLICATION

OK

SETTINGS

OK

OK

OK

OK

12 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installation Guide

Expansion Module for Danfoss Icon™ Master

Settings on thermostat

Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide

for further information. GB Choose reference room thermostat: To assign a thermostat as reference room thermostat, go to the

desired reference room thermostat and in menu set to .

When selected the thermostat will control when the system goes from heating mode to cooling mode based on the actual temperature in the room.

It is only possible to have one reference thermostat per system and if more than one thermostats are assigned as reference, the last assigned will overwrite the previous reference room thermostats and cause these to revert to normal function.

Application test function

Enter the “Test” menu via the installer key.

The Application test (APP test) is specific for each application. The test is split into steps to ensure that all components are installed correctly. Please follow the process.

Test steps

Step 1:3 During the first minute of the test, the heat source is set to "heating mode" via "PWR1 output". Check on heat source user interface that heating is active. Step 2:3 During the second minute of the test, the heat source is set to "cooling mode" via "Relay output". Check on heat source user interface that cooling is active

Step 3:3 During the third minute of the test, the heat source is set to "neutral mode", neither heating nor cooling is active.

Parts list

Pos. 1

NA

1 pc. e.g. Coolcube

 

 

 

Pos. 2

088U05XX / 088U06XX / 088U07XX

1 set Danfoss Manifold (types FHF or BasicPlus or SSM)

 

 

 

Pos. 3

NC: 088H3110 / NO: 088H3111

xx pcs. thermal actuator, 24 V TWA-A

 

 

 

Pos. 4

088U0251

1 pc. dew point sensor, type CF-DS

 

 

 

Pos. 5.

NA

External relay (convert 230 V to potential free relay), not

supplied by Danfoss

 

 

 

 

 

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 13

Installation Guide

Expansion Module for Danfoss Icon™ Master

Application 0006: 3-pipe system with cooling control via motorized valve and common return, change over signal ordered by reference room thermostat.

Optional: Dewpoint sensor (recommended), Global standby and heat demand signal relay.

Application description

3 -pipe Floor heating system with cooling controlled via motorized valve and common return.

The Icon™ system controls the heat and cooling demand by activating the corresponding relay (PWR1 and PWR2). For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. Four conditions must be true before cooling in a room is allowed:

Reference room temperature must exceed the room setpoint + cooling hysterhesis.

No room has called for heating within neutral time.

The dew point sensor must not be active / no condensation risk present.

The room thermostat must be enabled for cooling (default = enabled).

The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.

Settings

“SET 1” = Set desired cooling hysterhesis for change-over [+2 to +4K]

“SET 2” = Set neutral time that must pass without active heating or cooling, before change-over can be activated [3-6 Hrs.]

APPLICATION

OK

SETTINGS

OK

OK

OK

OK

14 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installation Guide

Expansion Module for Danfoss Icon™ Master

Settings on thermostat

Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide

for further information. GB Choose reference room thermostat: To assign a thermostat as reference room thermostat, go to the

desired reference room thermostat and in menu set to .

When selected the thermostat will control when the system goes from heating mode to cooling mode based on the actual temperature in the room.

It is only possible to have one reference thermostat per system and if more than one thermostats are assigned as reference, the last assigned will overwrite the previous reference room thermostats and cause these to revert to normal function.

Application test function

Enter the “Test” menu via the installer key.

The Application test (APP test) is specific for each application. The test is split into steps to ensure that all components are installed correctly. Please follow the process.

Test steps

Step 1:2 During the first minute of the test, the AMZ 113 valve is set to "heating mode" via "PWR1 output going ON". Check on valve/actuator that position is correct for "heating".

Step 2:2 During the second minute of the test, the AMZ 113 valve is set to "cooling mode" via "PWR1 output going OFF". Check on valve/actuator that position is correct for "Cooling".

Parts list

Pos. 1

DN15: 082G5511 DN20: 088G5512

1 pc. AMZ 113 (3 -way valve)

 

 

 

Pos. 2

088U05XX / 088U06XX / 088U07XX

1 set Danfoss Manifold (types FHF or BasicPlus or SSM)

 

 

 

Pos. 3

NC: 088H3110 / NO: 088H3111

xx pcs. thermal actuator, 24 V TWA-A

 

 

 

Pos. 4

088U0251

1 pc. dew point sensor, type CF-DS

 

 

 

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 15

Installation Guide

Expansion Module for Danfoss Icon™ Master

Application 0007: 3-pipe system with cooling control via thermal actuators and common return controlled by reference room thermostat.

Optional: Dewpoint sensor (recommended), Global standby, pump relay and heat demand signal.

Application description

3 -pipe Floor heating system with cooling controlled via thermal actuators and common return.

The Icon™ system controls the heat and cooling demand by activating the corresponding outputs (M1 and M2). For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. Four conditions must be true before cooling in a room is allowed:

Reference room temperature must exceed the room setpoint + cooling hysterhesis.

No room has called for heating within neutral time.

The dew point sensor must not be active / no condensation risk present.

The room thermostat must be enabled for cooling (default = enabled).

The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.

Settings

“SET 1” = Set desired cooling hysterhesis for change-over [+2 to +4K]

“SET 2” = Set neutral time that must pass without active heating or cooling, before change-over can be activated [3-6 Hrs.]

APPLICATION

OK

SETTINGS

OK

OK

OK

OK

16 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installation Guide

Expansion Module for Danfoss Icon™ Master

Settings on thermostat

Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide

for further information. GB Choose reference room thermostat: To assign a thermostat as reference room thermostat, go to the

desired reference room thermostat and in menu set to .

When selected the thermostat will control when the system goes from heating mode to cooling mode based on the actual temperature in the room.

It is only possible to have one reference thermostat per system and if more than one thermostats are assigned as reference, the last assigned will overwrite the previous reference room thermostats and cause these to revert to normal function.

Application test function

Enter the “Test” menu via the installer key.

The Application test (APP test) is specific for each application. The test is split into steps to ensure that all components are installed correctly. Please follow the process.

Test steps

Step 1:3 During the first five minutes, the output 1 is set to "ON" = heating mode/hot flow side (up to 3 minutes opening time can be expected).

Step 2:3 During next five minutes, the output 1 is set to "OFF", and the outputs 3 & 4 are set to "ON" = cooling mode/cold flow side (up to 3 minutes opening time can be expected).

Step 3:3 During last 5 minutes, all outputs 1 and 2 should close.

Parts list

Pos. 1

DN15: 013G3094 DN20: 013G3016

2 pcs. RA-C valve

 

 

 

Pos. 2

088U05XX / 088U06XX / 088U07XX

1 set Danfoss Manifold (types FHF or BasicPlus or SSM)

 

 

 

Pos. 3

NC: 088H3110 / NO: 088H3111

xx pcs. thermal actuator, 24 V TWA-A

 

 

 

Pos. 4

088U0251

1pc. dew point sensor, type CF-DS

 

 

 

Pos. 5a & 5b

088H3110

2 pcs. thermal actuator, 24 V TWA-A

 

 

 

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 17

Installation Guide

Expansion Module for Danfoss Icon™ Master

Application 0008: 3-pipe system with cooling control via motorized actuators and common return controlled by reference room thermostat.

Optional: Dewpoint sensor (recommended), Global standby, pump relay and heat demand signal.

Application description

3 -pipe Floor heating system with cooling controlled via motorized actuators and common return.

The Icon™ system controls the heat and cooling demand by activating the corrosponding outputs (PWR1 and potential free relay). For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. Four conditions must be true before cooling in a room is allowed:

Reference room temperature must exceed the room setpoint + cooling hysterhesis.

No room has called for heating within neutral time.

The dew point sensor must not be active / no condensation risk present.

The room thermostat must be enabled for cooling (default = enabled)

If no heating or cooling demand is present, the two shut-off valves will close (AMZ 112).

The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.

Settings

“SET 1” = Set desired cooling hysterhesis for change-over [+2 to +4K]

“SET 2” = Set neutral time that must pass without active heating or cooling, before change-over can be activated [3-6 Hrs.]

APPLICATION

OK

 

SETTINGS

OK

OK

OK

OK

18 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installation Guide

Expansion Module for Danfoss Icon™ Master

Settings on thermostat

Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide

for further information. GB Choose reference room thermostat: To assign a thermostat as reference room thermostat, go to the

desired reference room thermostat and in menu set to .

When selected the thermostat will control when the system goes from heating mode to cooling mode based on the actual temperature in the room.

It is only possible to have one reference thermostat per system and if more than one thermostats are assigned as reference, the last assigned will overwrite the previous reference room thermostats and cause these to revert to normal function.

Application test function

Enter the “Test” menu via the installer key.

The Application test (APP test) is specific for each application. The test is split into steps to ensure that all components are installed correctly. Please follow the process.

Test steps

Step 1:3 During the first minute of the test, the AMZ 112 valve of the hot flow side is set to "heating mode" via "PWR1 output going ON". Check on valve/actuator that position is correct for "heating".

Step 2:3 During the second minute of the test, the AMZ 112 valve on the cold flow side is set to "cooling mode" via "PWR1 output going OFF" and "Relay output" going ON. Check on valve/actuator that position is correct for "cooling".

Step 3:3 During last minute of the test, botm AMZ 112 valves are closed.

Parts list

Pos. 1a & 1b

DN15: 082G5511 DN20: 082G5512

2 pcs. AMZ112

 

 

 

Pos. 2

088U05XX / 088U06XX / 088U07XX

1 set Danfoss Manifold (types FHF or BasicPlus or SSM)

 

 

 

Pos. 3

NC: 088H3110 / NO: 088H3111

xx pcs. thermal actuator, 24 V TWA-A

 

 

 

Pos. 4

088U0251

1 pc. dew point sensor, Type CF-DS

 

 

 

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 19

Installation Guide

Expansion Module for Danfoss Icon™ Master

Application 0009: 4-pipe system with 6-port valve, automatic change over for cooling controlled by a reference room thermostat. (Require external 24 VAC PSU).

Optional: Dewpoint sensor (recommended), shut-off function and Global standy.

Application description

Floor heating system with automatic changeover for cooling via 6-way changeover valve controlled by a reference room thermostat.

The system can be configured with optional shut off function via a Danfoss AMZ-112 2-way ball valve and Global standby. For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. Four conditions must be true before cooling in a room is allowed:

Reference room temperature must exceed the room setpoint + cooling hysterhesis.

No room has called for heating within neutral time.

The dew point sensor must not be active / no condensation risk present.

The room thermostat must be enabled for cooling (default = enabled).

If no heating or cooling demand is present, the shut-off valve will close.

The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.

Settings

“SET 1” = Set desired cooling hysterhesis for change-over [+2 to +4K]

“SET 2” = Set neutral time that must pass without active heating or cooling, before change-over can be activated [3-6 Hrs.]

APPLICATION

OK

SETTINGS

OK

OK

OK

OK

20 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installation Guide

Expansion Module for Danfoss Icon™ Master

Settings on thermostat

Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide

for further information. GB Choose reference room thermostat: To assign a thermostat as reference room thermostat, go to the

desired reference room thermostat and in menu set to .

When selected the thermostat will control when the system goes from heating mode to cooling mode based on the actual temperature in the room.

It is only possible to have one reference thermostat per system and if more than one thermostats are assigned as reference, the last assigned will overwrite the previous reference room thermostats and cause these to revert to normal function.

Application test function

Enter the “Test” menu via the installer key.

The Application test (APP test) is specific for each application. The test is split into steps to ensure that all components are installed correctly. Please follow the process.

Test steps

Step 1:3 During the first two minutes, the AMZ 112 valve goes to position "Flow" and the ChangeOver6 valve goes to position "Cooling" for 1 minute.

Step 2:3 The ChangeOver6 valve now goes to position "Heating" for 1 minute.

Step 3:3 The AMZ 112 valve goes to position "No Flow".

Parts list

Pos. 1

DN 15: 003Z3150 / DN 20: 003Z31511

1 pc. Danfoss ChangeOver6 6-port valve

 

 

 

Pos. 2

003Z3155

1 pc. Danfoss ChangeOver6 actuator

 

 

 

Pos. 3

DN15: 082G5501 / DN20: 082G55021

1 pc. AMZ 112

 

 

 

Pos. 4

088U05XX / 088U06XX / 088U07XX

1 pc. Danfoss manifold (types FHF or BasicPlus or SSM)

 

 

 

Pos. 5

N/A

1 pc. external power supply 230 V->24 VAC, not supplied by

Danfoss. Minimum 5 VA output on 24 V side.

 

 

 

 

 

Pos. 6

088U0251

1 pc. dew point sensor, type CF-DS

 

 

 

Pos. 7

NC: 088H3110 / NO: 088H3111

xx pcs. thermal actuator, 24 V TWA-A

 

 

 

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 21

Installation Guide

Expansion Module for Danfoss Icon™ Master

Application 0010: 4-pipe system with 2-way valves on supply pipes and automatic change over for cooling controlled by a reference room thermostat.

Optional: Dewpoint sensor (recommended), circulation pump, heat demand signal and Global standby.

Application description

4-pipe system with 2-way valves on supply pipes and automatic change over for cooling controlled by reference room thermostat.

The system activates cooling mode via 2-way valves with thermal actuators on supply and return side by activating the corresponding outputs (M1 - M4). Note: In this application outputs 1, 2, 3 & 4 on Danfoss Icon™ Master is used for the application and cannot be assigned to thermostats.

For cooling applications it is always recommended to have a dew point sensor installed in the system to prevent moisture damage to floor and installations in cases where the relative humidty exceeds dew point. Four conditions must be true before cooling in a room is allowed:

Reference room temperature must exceed the room setpoint + cooling hysterhesis.

No room has called for heating within neutral time.

The dew point sensor must not be active / no condensation risk present.

The room thermostat must be enabled for cooling (default = enabled).

The Global standby is a potential free input that can be used to remotely put the system in Global away mode e.g. via an external 3rd party GSM module. When global standby input is active, all rooms receive a 15 degree celcius setpoint.

Settings

“SET 1” = Set desired cooling hysterhesis for change-over [+2 to +4K]

“SET 2” = Set neutral time that must pass without active heating or cooling, before change-over can be activated [3-6 Hrs.]

APPLICATION

OK

SETTINGS

OK

OK

OK

OK

22 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installation Guide

Expansion Module for Danfoss Icon™ Master

Settings on thermostat

Excluding rooms from cooling: To exclude a room from cooling - typically in bathrooms where cooling would be uncomfortable - go to thermostat and set menu to . See Thermostat Installation Guide

for further information. GB Choose reference room thermostat: To assign a thermostat as reference room thermostat, go to the

desired reference room thermostat and in menu set to .

When selected the thermostat will control when the system goes from heating mode to cooling mode based on the actual temperature in the room.

It is only possible to have one reference thermostat per system and if more than one thermostats are assigned as reference, the last assigned will overwrite the previous reference room thermostats and cause these to revert to normal function.

Application test function

Enter the “Test” menu via the installer key.

The Application test (APP test) is specific for each application. The test is split into steps to ensure that all components are installed correctly. Please follow the process.

Test steps

Step 1:3 During the first five minutes, the outputs 1&2 are set to "ON" = heating mode/hot flow side (up to 3 minutes opening time can be expected).

Step 2:3 During next five minutes, the outputs 1&2 are set to "OFF", and the outputs 3 & 4 are set to "ON" = cooling mode/cold flow side (up to 3 minutes opening time can be expected).

Step 3:3 During last 5 minutes, all outputs 1, 2, 3 and 4 should close.

Parts list

Pos. 1

DN15: 013G3094 DN20: 013G3016

4 pcs. RA-C valve

 

 

 

Pos. 2

088U05XX / 088U06XX / 088U07XX

1 pc. Danfoss manifold (types FHF or BasicPlus or SSM)

 

 

 

Pos. 3

NC: 088H3110 / NO: 088H3111

xx pcs. thermal actuator, 24 V TWA-A

 

 

 

Pos. 4

088U0251

1 pc. dew point sensor, type CF-DS

 

 

 

Pos. 5

NC: 088H3110

2 pcs. thermal actuator, 24 V TWA-A

 

 

 

Pos. 6

NC: 088H3110

2 pcs. thermal actuator, 24 V TWA-A

 

 

 

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 23

Installationsanleitung

Erweiterungsmodus für Danfoss Icon™ Master

 

 

 

Die Verdrahtung gemäß dem

 

 

 

Schaltdiagramm durchführen und

1

 

 

anschließend das Erweiterungsmodul

 

 

für zusätzliche Funktionen in den

 

APPLICATION

 

Danfoss Icon™ Hauptregler einführen.

2

 

 

1. Mit dieser Taste können Sie die

 

SETTINGS

 

 

3

Anwendung auswählen. Drücken

 

 

 

 

 

Sie die Anwendungstaste, wählen

IN 1

IN 2

IN 3

Sie mit

und

Anwendung

1-11 aus und bestätigen Sie mit

 

 

 

 

 

 

„OK“. Wählen Sie die geeignete

 

 

 

Anwendung mithilfe der Anwen-

 

 

 

dungszeichnungen aus.

 

 

 

2. Mit dieser Taste können Sie

 

 

 

anwendungsspezifische Einstel-

 

 

 

lungen einstellen. Die für die ge-

 

 

 

wählte Anwendung verfügbaren

 

 

 

Einstellungen sind in der Anwen-

 

 

 

dungsbeschreibung aufgeführt.

 

 

 

3. LED-Leuchten zeigen den Status

 

 

 

der Eingänge 1 bis 3 an. Vgl. die

 

 

 

Anwendungsbeschreibung für die

 

 

 

jeweilige Anwendung.

4

 

 

 

PWR3

IN 3

IN 2

IN 1

24

PT

 

 

VDC

1000

 

 

5

6

4.Anschlussklemmen für den Anschluss verschiedener Verdrahtungen/externer Geräte.

5.Kabel-Zugentlastung.

6.Lösevorrichtung für Verdrahtung/ Kabel.

24 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installationsanleitung

Erweiterungsmodus für Danfoss Icon™ Master

Anwendung 0001: Zweirohrsystem, vorgegebene Zulufttemperatur, elektronisch kontrolliert.

Optional: Global Standby.

Anwendungsbeschreibung

DE

Fußbodenheizungssystem mit elektronischer Regelung der Zulufttemperatur. Die Zulufttemperatur ist auf einen vorgegebenen Wert eingestellt.

Das System nutzt einen PT1000-Fühler, um die Zulufttemperatur zu erkennen und zu regeln, und wird auch eingesetzt, um sicherzustellen, dass die Temperatur nicht die zulässige Höchsttemperatur übersteigt. Wenn verbunden, steuert das System die Umwälzpumpe und das Heizbedarfssignal, beispielsweise für einen Kessel oder eine Wärmepumpe. Die Pumpe und das Heizbedarfssignal sind eingeschaltet, wenn bei mindestens einem Kreislauf Heizbedarf besteht. Ausgang 1 muss für TWA an der Mischergruppe verwendet werden.

Das Globale Standby ist ein potentialfreier Eingang, mit dem das System per Fernzugriff in den Globalen Abwesenheitsmodus versetzt werden kann, z. B. über ein externes GSM-Modul eines Drittanbieters. Wenn der globale Standby-Eingang aktiv ist, erhalten alle Räume einen Sollwert von 15 Grad Celsius.

Einstellungen

„SET 1“ = Gewünschte Vorlauftemperatur [25-70 °C] einstellen

„SET 2“ = Gewünschte Sicherheits-Abschalttemperatur [30-75 °C] einstellen

Hinweis: Die Temperatur muss über der Vorlauftemperatur liegen.

APPLICATION

OK

 

SETTINGS

OK

OK

OK

OK

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 25

Installationsanleitung

Erweiterungsmodus für Danfoss Icon™ Master

Anwendungstestfunktion

Rufen Sie über die Installateurstaste das Menü„Test“ auf. Der Anwendungstest (APP-Test) ist anwendungsspezifisch. Der Test ist in mehrere Schritte unterteilt, um sicherzustellen, dass alle Komponenten ordnungsgemäß installiert werden. Befolgen Sie bitte das Verfahren.

Testschritte

Schritt 1:1 Gehen Sie zum Regelventilantrieb der Mischergruppe und überprüfen Sie, ob sich das Ventil vollständig öffnet (es sind bis zu drei Minuten Öffnungszeit zu erwarten). Nach fünf Minuten schließt sich der Ventilantrieb der Mischergruppe wieder.

Während der fünfminütigen Testphase zeigt das Display am Hauptregler auch die gemessene Vorlauftemperatur an.

Teileliste

Pos. 1

088U0093-96

1 Stk. Danfoss FHM-Cx Mischergruppe

 

 

 

Pos. 2

088U05XX/088U06XX/088U07XX

1 Satz Danfoss Verteiler (Typen FHF oder BasicPlus oder SSM)

 

 

 

Pos. 3

NC: 088H3110/NO: 088H3111

xx Stk. Thermischer Stellantrieb, 24 V TWA-A

 

 

 

Pos. 4

087B1165

1 Stk. ESM-11 PT-1000 Fühler

 

 

 

Pos. 5.

NC: 088H3110/NC: 193B2148

1 Stk. Thermischer Stellantrieb, 24 V (Typen TWA-A oder ABN-FBH)

 

 

 

26 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installationsanleitung Erweiterungsmodus für Danfoss Icon™ Master

Anwendung 0002: Zweirohrsystem mit bedarfsbasierter Regelung der Zulufttemperatur.

Optional: Globales Standby.

Anwendungsbeschreibung DE

Fußbodenheizungssystem mit elektronischer Regelung der Zulufttemperatur.

Die bedarfsbasierte Zulufttemperatur wird je nach dem Heizbedarf aus den Räumen geregelt. Das System nutzt einen PT1000-Fühler, um die Zulufttemperatur zu erkennen, und wird auch eingesetzt, um mithilfe eines Sicherheits-Tmax sicherzustellen, dass die Temperatur nicht die zulässige Höchsttemperatur übersteigt. Wenn verbunden, steuert das System die Umwälzpumpe und das Heizbedarfssignal, beispielsweise für einen Kessel oder eine Wärmepumpe. Die Pumpe und das Heizbedarfssignal sind eingeschaltet, wenn bei mindestens einem Kreislauf Heizbedarf besteht. Ausgang 1 muss für TWA an der Mischergruppe verwendet werden.

Das Globale Standby ist ein potentialfreier Eingang, mit dem das System per Fernzugriff in den Globalen Abwesenheitsmodus versetzt werden kann, z. B. über ein externes GSM-Modul eines Drittanbieters. Wenn der globale Standby-Eingang aktiv ist, erhalten alle Räume einen Sollwert von 15 Grad Celsius.

Einstellungen

“SET 1” = Set desired min. supply flow temperature [25-65°C]

„SET 1“ = Gewünschte minimale Vorlauftemperatur [25-65 °C] einstellen „SET 2“ = Gewünschte maximale Vorlauftemperatur [30-70 °C] einstellen

Hinweis: Die Temperatur muss mindestens 5 °C höher als die minimale Vorlauftemperatur eingestellt werden.

„SET 3“ = Gewünschte Sicherheits-Abschalttemperatur [30-75 °C] einstellen

Hinweis: Die Temperatur muss über der Vorlauftemperatur liegen.

APPLICATION

OK

 

SETTINGS

OK

OK

OK

OK

OK

OK

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 27

Installationsanleitung

Erweiterungsmodus für Danfoss Icon™ Master

Anwendungstestfunktion

Rufen Sie über die Installateurstaste das Menü„Test“ auf. Der Anwendungstest (APP-Test) ist anwendungsspezifisch. Der Test ist in mehrere Schritte unterteilt, um sicherzustellen, dass alle Komponenten ordnungsgemäß installiert werden. Befolgen Sie bitte das Verfahren.

Testschritte

Schritt 1:1 Gehen Sie zum Regelventilantrieb der Mischergruppe und überprüfen Sie, ob sich das Ventil vollständig öffnet (es sind bis zu drei Minuten Öffnungszeit zu erwarten). Nach fünf Minuten schließt sich der Ventilantrieb der Mischergruppe wieder.

Während der fünfminütigen Testphase zeigt das Display am Hauptregler auch die gemessene Vorlauftemperatur an.

Teileliste

Pos. 1

088U0093-96

1 Stk. Danfoss FHM-Cx Mischergruppe

 

 

 

Pos. 2

088U05XX/088U06XX/088U07XX

1 Satz Danfoss Verteiler (Typen FHF oder BasicPlus oder SSM)

 

 

 

Pos. 3

NC: 088H3110/NO: 088H3111

xx Stk. Thermischer Stellantrieb, 24 V TWA-A

 

 

 

Pos. 4

087B1165

1 Stk. ESM-11 PT-1000 Fühler

 

 

 

Pos. 5.

NC: 088H3110/NC: 193B2148

1 Stk. Thermischer Stellantrieb, 24 V (Typen TWA-A oder ABN-FBH)

 

 

 

28 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Installationsanleitung

Erweiterungsmodus für Danfoss Icon™ Master

Anwendung 0003: Zweirohrsystem mit automatischer Umschaltung zur Kühlung auf der Grundlage der Zulufttemperatur.

Optional: Taupunktfühler (empfohlen), Globales Standby, Umwälzpumpe und Heizbedarfssignal.

Anwendungsbeschreibung

DE

Fußbodenheizungssystem mit automatischer Umschaltung zur Kühlung auf der Grundlage des Zulufttemperatureingangs.

Die Zulufttemperatur wird mittels eines PT1000-Fühlers überwacht. Je nach Messung schaltet das System von Heizung auf Kühlung um. Wenn verbunden, steuert das System die Umwälzpumpe, die eingeschaltet wird, wenn mindestens ein Raum Heizoder Kühlbedarf hat.

Das Heizsignal für beispielsweise einen Kessel oder eine Wärmepumpe wird nur aktiviert, wenn sich das System im Heizmodus befindet und mindestens ein Raum Heizbedarf hat. Für Kühlanwendungen empfiehlt es sich immer, im System einen Taupunktfühler installiert zu haben, um Feuchtigkeitsschäden an Boden und Installationen zu vermeiden, wenn die relative Luftfeuchte den Taupunkt übersteigt.

Das Globale Standby ist ein potentialfreier Eingang, mit dem das System per Fernzugriff in den Globalen Abwesenheitsmodus versetzt werden kann, z. B. über ein externes GSM-Modul eines Drittanbieters. Wenn der globale Standby-Eingang aktiv ist, erhalten alle Räume einen Sollwert von 15 Grad Celsius.

Einstellungen

„SET 1“ = Vorlauftemperatur für die Umschaltung zum Heizen [25-55 °C] einstellen „SET 2“ = Vorlauftemperatur für die Umschaltung zum Kühlen [15-25 °C] einstellen

Hinweis: Die Temperatur kann nicht höher als 2 °C unter der Umschalttemperatur zum Heizen eingestellt werden.

APPLICATION

OK

 

SETTINGS

OK

OK

OK

OK

Einstellungen des Thermostats

Räume von der Kühlung ausschließen: Um einen Raum von der Kühlung auszuschließen, etwa ein Badezimmer, in dem eine Kühlung unangenehm wäre, den Thermostat aufsuchen und Menü auf einstellen. Weitere Informationen sind in der Installationsanleitung des Thermostats enthalten.

VIMDE20F / 088N2100

© Danfoss | FEC | 2018.12 | 29

Installationsanleitung

Erweiterungsmodus für Danfoss Icon™ Master

Anwendungstestfunktion

Rufen Sie über die Installateurstaste das Menü„Test“ auf. Der Anwendungstest (APP-Test) ist anwendungsspezifisch. Der Test ist in mehrere Schritte unterteilt, um sicherzustellen, dass alle Komponenten ordnungsgemäß installiert werden. Befolgen Sie bitte das Verfahren.

Testschritte

Schritt 1:1 Während der einminütigen Testphase zeigt das Display am Hauptregler die gemessene Vorlauftemperatur an.

Teileliste

Pos. 1

087B1165

1 Stk. ESM-11 PT1000 Fühler

 

 

 

Pos. 2

088U05XX/088U06XX/088U07XX

1 Satz Danfoss Verteiler (Typen FHF oder BasicPlus oder SSM)

 

 

 

Pos. 3

NC: 088H3110/NO: 088H3111

xx Stk. Thermischer Stellantrieb, 24 V TWA-A

 

 

 

Pos. 4

088U0251

1 Stk. Taupunktfühler, Typ CF-DS

 

 

 

30 | © Danfoss | FEC | 2018.12

VIMDE20F / 088N2100

Loading...
+ 294 hidden pages