Installation guide
Solenoid valve
Types EVUL 1 - EVUL 8, EVU 1 - EVU 8, EVUB, and EVUF
032R 9551
Refrigerants
R744, R22/R407C, R404A/R507, R410A, R134a, R407A,
R23, R290 (only EVUL), R407F, R448A, R449A, R450A, and
R452A.
For complete list of approved refrigerants, visit
www.products.danfoss.com and search for individual code
numbers, where refrigerants are listed as part of technical
data.
Special note only for EVUL and R290:
Only EVUL is approved for R290 and is validated in
accordance to ATEX, ISO 5149, IEC 60335, and UL.
Ignition risk is evaluated in accordance to ISO 5149, and IEC
60335.
Mounting Mounting angle
Valve connection:
Max. 700 °C / 1300 °F
Cobber tube: 10 - 15 sec
Max. working pressure
EVUL 1 - EVUL 8: 90 bar / 1305 psig
EVU 1 - EVU 8: 70 bar / 1015 psig
EVUB and EVUF: 45.2 bar / 655 psig
Max. opening di. pressure (MOPD):
Coil dependent
Ambient temperature:
-40 °C / -40 °F – 50 °C / 122 °F
Media temperature:
-40 °C / -40 °F – 105 °C / 221 °F
032R 9551
Valve connection: 2 - 5 sec
Special note for EVU:
Danfoss recommends that a suitable lter or
lter drier (max. size of 40 - 50 μm) is installed
ahead of each EVU valve to keep scale, solder
material and other foreign dirt and particles
out of the valve.
© Danfoss | DCS (rja) | 2017.05
Always disconnect power from the coil when
dismounted from the valve. The coil may
be damaged and there is risk of injuries and
burns.
DKRCC.PI.BD0.C8.02 | 1
ø3.5 mm
(0.14 in .)
Be sure that the
O-ring is in place
Be sure that
there is no
O-ring!
To ensure correct sealing between coil and valve make sure that the coil is fully clicked on to the valve.
Only EVUL can be applied on systems with R290 as the working uid.
For countries where safety standards are not an indispensable part of the safety system Danfoss
recommends the installer gets a third party approval of any system containing ammable refrigerant.
Note: Please follow specic selection criteria stated in the datasheet for this particular refrigerants.
© Danfoss | DCS (rja) | 2017.05
DKRCC.PI.BD0.C8.02 | 2