Danfoss EVRS 10, EVRS 15, EVRS 20, EVRS 3 Installation guide

Installation Guide
Solenoid Valve
Types EVRS 3 – 20 and EVRST 10 – 20
Refrigerants:
R744, R717, R22/R407C, R404A/R507, R410A, R134a,
032R 9513
R4 07A , R23. For other refrigerants, please contact Danfoss.
Max. 150 °C (300 °F)
T = 50 Nm (37 ft-lbs)
T = 20 Nm (15 ft-lbs)
T = 30 Nm (22 ft-lbs)
Body material – stainless steel
1.4308 for EVRS 10, EVRS 15, EVRS 20
1.4301 for EVRS 3
a.c.~ a.c.~ a.c.~
max.
t
10 W a.c.
10 / 12 W a.c.
20 W d.c.
80 °C
(175 °F)
max.
t
80 °C
(175 °F)
max.
t
50 °C
(120 °F)
min.
t
- 40 °C
(-40 ° F)
032R 9513
a.c.~
Oil
Min. medium temperature -40 °C (- 40 °F)
75 Nm ± 5 Nm
New
Used
Max. medium temperature 105 °C (221 °F)
EVRS/ T 3
Max. working pressure PS/MWP
Max. opening di. pressure: Max. working pressure PS/MWP:
EVRS/ T 10 EVRS/T 15
EVRS/T 20
28 barg / 406 psig for 032F3086 and 032F2237 50 barg / 725 psig for 032F5437 and 032F5438
50 barg / 725 psig
On
Warning
The manual opener of EVRS 3-20 and EVRST 10-20 is intended to be activated only during initial pressure testing of the refrigeration system.
After pressure testing or service-related manual forced opening of the manual opener the spindle must be turned fully back to back-seated position to avoid any packing gland leakage.
Furthermore it is essential that the sealing cap is properly reinstalled. This will eliminate any risk of leakage from the manual opener.
Clip-on
O
© Danfoss | DCS (MWA) | 2016.12
DKRCC.PI.BP0.A4.02 | 520H6992 | 1
EVRS 3
EVRS 10 – 20
EVRST 10 – 20
EVRS 3
EVRS 10 – 20
EVRST 10 – 20