Danfoss EKC 202 User Manual

Controller for temperature control
- EKC 202
Manual
2 Manual RS8DZ602 © Danfoss 08-2010 EKC 202
Introduction
• The controller is used for temperature control refrigeration appliances and cold room in supermarkets
• Control of defrost, fans, alarm and light
• For front panel mounting
Principle
The controller contains a temperature control where the signal can be received from one temperature sensor. The sensor is placed in the cold air ow after the evaporator or in the warm air ow just before the evaporator. The controller controls the defrost with either natural defrost or electric defrost. Renewed cutin after defrost can be accomplished based on time or temperature. A measurement of the defrost temperature can be obtained directly through the use of a defrost sensor. Two to four relays will cut the required functions in and out – the application determines which:
• Refrigeration (compressor or solenoid valve)
• Defrost
• Fan
• Alarm
• Light
The dierent applications are described on next page.
Advantages
• Integrated refrigeration-technical functions
• Defrost on demand in 1:1 systems
• Buttons and seal imbedded in the front
• IP65 density from the front panel
• Digital input for either:
- Door contact function with alarm
- Defrost start
- Start/stop of regulation
- Night operation
- Change-over between two temperature reference
- Case cleaning function
• Instant programming via programming key
• HACCP Factory calibration that will guarantee a better measuring accu­racy than stated in the standard EN 441-13 without subsequent calibration (Pt 1000 ohm sensor)
Extra module
• The controller can afterwards be tted with an insertion module
if the application requires it. The controller has been prepared with plug, so the module simply has to be pushed in
- Battery and buzzer module
The module guarantees voltage to the controller if the supply voltage should drop out for more than four hours. The clock function can thus be protected during a power failure.
- Data communication
If you require operation from a PC, a data communication mod­ule has to be placed in the controller.
- Coordinated defrost via data communication
Contents
Introduction ....................................................................................................... 2
Operation ............................................................................................................ 5
Menu survey .......................................................................................................6
Functions .............................................................................................................8
Connections .....................................................................................................14
Data .....................................................................................................................15
Ordering ............................................................................................................16
EKC 202 Manual RS8DZ602 © Danfoss 08-2010 3
EKC 202A
Controller with two relay outputs, two temperature sensors and digital input.
Temperature control at start/stop of compressor / solenoid valve Defrost sensor Electrical defrost / gas defrost
EKC 202B
Controller with three relay outputs, two temperature sensors and digital input.
Temperature control at start/stop of compressor / solenoid valve Defrost sensor Electrical defrost / gas defrost Relay output 3 is used for control of fan.
EKC 202C
Controller with four relay outputs, two temperature sensors and digital input.
Temperature control at start/stop of compressor / solenoid valve Defrost sensor Electrical defrost / gas defrost Control of fan
Relay output 4 can be used for an alarm function or for a light function.
Alarm function If an alarm function is required, relay number two may be used for it. Defrost is performed here with circulation of the air as the fans are operating continuously.
4 Manual RS8DZ602 © Danfoss 08-2010 EKC 202
Start of defrost
A defrost can be started in dierent ways Interval: Defrost is started at xed time intervals, say, every eight hour Refrigeration time: Defrost is started at xed refrigeration time inter- vals, in other words, a low need for refrigeration will ”postpone” the coming defrost Contact Defrost is started here with a pulse signal on a
digital input. Manual: An extra defrost can be activated from the control­ ler’s lower-most button S5-temp. In 1:1 systems the eciency of the evaporator can
be followed. Icing-up will start a defrost. Schedule Defrost here can be started at xed times of the
day and night. But max. six defrosts Network A defrost can be started via data communication All the mentioned methods can be used at random – if just one them is activated a defrost will be started. When the defrost starts the defrost timers are set at zero
Digital input
The digital input can be used for the following functions:
- Door contact function with alarm if the door has been open for
too long.
- Defrost start
- Start/stop of regulation
- Change-over to night operation
- Case cleaning
- Change to another temperature reference
- Inject on/o
Case cleaning function
This function makes it easy to steer the refrigeration appliance through a cleaning phase. Via three pushes on a switch you change from one phase to the next phase. The rst push stops the refrigeration – the fans keep working ”Later”: The next push stops the fans ”Still later”: The next push restarts refrigeration The dierent situations can be followed on the display.
There is no temperature monitoring during case cleaning.
On the network a cleaning alarm is transmitted to the system unit. This alarm can be ”logged” so that proof of the sequence of events is provided.
Defrost on demand
1 Based on refrigeration time
When the aggregate refrigeration time has passed a xed time, a defrost will be started.
2 Based on temperature
The controller will constantly follow the temperature at S5. Between two defrosts the S5 temperature will become lower the more the evaporator ices up (the compressor operates for a longer time and pulls the S5 temperature further down). When the temperature passes a set allowed variation the defrost will be started.
This function can only be used in 1:1 systems
A pulse signal starts the defrost
- + + °C
1 ÷ + Fan
2 ÷ ÷ O
3 + + °C
EKC 202 Manual RS8DZ602 © Danfoss 08-2010 5
Light-emitting diodes (LED) on front panel
There are LED’s on the front panel which will light up when the belonging relay is activated.
= Refrigeration = Defrost = Fan
The light-emitting diodes will ash when there is an alarm. In this situation you can download the error code to the display and cancel/sign for the alarm by giving the top button a brief push.
Defrost
During defrost a –d– is shown in the display. This view will continue up till 15 min. after the cooling has resumed. However the view of –d– will be discontinued if:
- The temperature is suitable within the 15 minutes
- The regulation is stopped with “Main Switch”
- A high temperature alarm appears
The buttons
When you want to change a setting, the upper and the lower buttons will give you a higher or lower value depending on the button you are pushing. But before you change the value, you must have access to the menu. You obtain this by pushing the upper button for a couple of seconds - you will then enter the col­umn with parameter codes. Find the parameter code you want to change and push the middle buttons until value for the parameter is shown. When you have changed the value save the new value by once more pushing the middle button
Display The values will be shown with three digits, and with a setting you can determine whether the temperature are to be shown in °C or in °F.
Operation
Examples
Set menu
1. Push the upper button until a parameter r01 is shown
2. Push the upper or the lower button and nd that parameter you want to change
3. Push the middle button until the parameter value is shown
4. Push the upper or the lower button and select the new value
5. Push the middle button again to enter the value.
Cutout alarm relay / receipt alarm/see alarm code
• Push briey the upper button
If there are several alarm codes they are found in a rolling stack. Push the uppermost or lowermost button to scan the rolling stack.
Set temperature
1. Push the middle button until the temperature value is shown
2. Push the upper or the lower button and select the new value
3. Push the middle button to select the setting
Manuel start or stop of a defrost
• Push the lower button for four seconds.
See the temperature at the defrost sensor
• Push briey the lower button
If no sensor has been mounted, ”non” will appear.
100% tight
The buttons and the seal are imbedded in the front. A special moulding technique unites the hard front plastic, the softer buttons and the seal, so that they become an integral part of the front panel. There are no openings that can receive moisture or dirt.
Loading...
+ 11 hidden pages