Installation Guide
Bluetooth Adapter
08 0R 4219
Type EKA 202 & EKA 203
AN404136884216en-000101
Bluetooth Adapter (EKA 202 & EKA 203) is a plug in type device for ERC and EETa range of
controllers to provide bluetooth connectivity with companion mobile application 'KoolConnect'.
• Bluetooth Low Energy 5.2
• Simple Plug and Play module
• Powered from controller
• Data logging for 15 days
• Real time clock with power back up option
Scan to connect
80G8346
Technical specifications:
Specifications EKA 202 EKA 203
Input voltage 5 V DC / 12 V DC 5 V DC / 12 V DC
Max Current 70 mA 76 mA
Bluetooth version 5.2 5.2
Bluetooth range (without any obstruction around) 10 m 10 m
Data storage duration 15 days 15 days
RTC power back up No power backup 36 hours (approx.)
Communication interface with controller UART, One wire UART, One wire
Operating temperature -25 – +55 °C -25 – +55 °C
Maximum humidity <90% RH (Non-condensing) <90% RH (Non-condensing)
Storage temperature -40 – +70 °C -40 – +70 °C
Ordering code
Bluetooth adapter
Interface cable
Supported Controllers ERC11x, ERC21x (080G34xx series only) and EETa
Approvals
1)
For latest approval status and other local approvals, please check at danfoss.com or contact your local Danfoss representative.
1)
080N0022 (Single Pack) | 080N0026 (I Pack) 080N0023 (Single Pack) | 080N0027 (I Pack)
080N0329 (ERC 11x) | 080N0327 (ERC21x) | 080N0325 (EETa)
CE, UL, FCC, ISED
Fig. 1: EKA 202/203
Dimensions (units are in mm)
Fig. 2: Top view Fig. 3: Rear view
Danfoss
Scan to connect
A
C
B
Procedure for adapter installation
1. Detach the QR code chip from the Bluetooth Adapter by
breaking. The QR code chip is used for pairing with mobile
2. Attach the QR code chip to the door or any clean part of the
cabinet that can be easily accessed for the pairing procedure.
application.
Scan to connect
Danfoss
80G8345
80G8315
A. Bluetooth Adapter
B. QR code chip
C. TTL port for connection
with controller
80G8340
Scan to connect
Danfoss
80G8315
© Danfoss | Climate Solutions | 2022.02
AN404136884216en-000101 | 1
3. Secure the Bluetooth Adapter in a convenient location using
double sided tape (Fig. 4-5) or by screw mounting (Fig. 6)
Fig. 4
Danfoss
80G8313
Fig. 5
Danfoss
80G8314
4. Power off the controller by switching off the main supply to the
controller.
5. Connect the Bluetooth Adapter to communication port of
controller using interface cable (Fig. 7)
– TTL port in ERC21x and EETa
– DI port in ERC11x
Fig. 7
Bluetooth Adapter
Interface
cable
Danfoss
80G8316
Fig. 6
80G8317
Controller
Note:
• Ensure the Bluetooth Adapter is installed away from heating
source, direct sunlight, dripping water, dusty environment.
• Avoid any obstruction around the adapter that impacts
Bluetooth communication.
• Interface cable ordered separately for the respective controller
to be used for connecting Bluetooth Adapter to Controller.
Power up sequence and connection with mobile application:
Function Description Illustration LED info
• White – Blue – Red – Green
LED blinking in sequence
indicates power up
initialization.
• After few seconds, Green
LED rapid flashes indicating
controller detection is in
progress.
• Green LED slow flashes (1s/1s)
• Red LED rapid flashes.
Power-up
Established
communication
with controller and
broadcasting.
Power up the controller connected with
Bluetooth Adapter.
Bluetooth Adapter starts power up initialization
(it gets power from connected controller).
After power up initialization, the adapter
establishes communication with connected
controller and start broadcasting.
Unsuccessful identification/communication with
controller.
Danfoss
80G8341
Gree
Danfoss
80G8342
Gree
Danfoss
80G8347
Red
Danfoss
80G8343
Connection with mobile
app and Real time clock
(RTC) update
1)
Note:
Search and connect broadcasting adapter using
KoolConnect companion app. Click on "Set
time" when mobile app shows alert message to
synchronize the adapter time with mobile time.
Danfoss
1)
80G8344
Blue
• LED turns to constant Blue
indicating Bluetooth is
connected.
1. Ensure that the module is connected to the mobile app after final power up and installation to finalize the setup properly. If the
module is not connected after final power up at customer's site, the module will log the data without the correct time stamp.
2. If the Bluetooth Adapter is changed from one controller model to another (ex: ERC112C to ERC112D or EETa 3W), all the logged
data from previous controller are erased and start logging afresh from new controller. The data from previous controller is retained
if one code no. is changed to another code no. within the same controller model.
KoolConnect companion mobile app download and connection:
Android version 8.0 or later
2 | AN404136884216en-000101
iOS 11 or later (Iphone 8 & above)
KoolConnect
© Danfoss | Climate Solutions | 2022.02