Danfoss EKA 166 Data sheet

Data Sheet
Display
Accessory
Type EKA 166 For AK-PC 7xx controllers
Application:
This display can be used with AK-PC 710/AK-PC 781 compressor controllers.
Features:
The LEDs on the panel correspond to the connected compressors and condensers. There are LEDs for the following functions:
• Compressors
• Speed control
• Optimisation
• Alarm
• Load limitation
• Heat recovery
• Injection is active
If a compressor is stopped because of a safety cutout the corresponding LED will ash.
The optimisation LED will light up when the regulation reference is 2 K or above the set point.
AI000086415223en-000201
Features
Description
Power supply
From controller
Display operation
Display accuracy in measuring range: 0.1% LED, three digits, control buttons
Electrical connection
Connector
Ambient conditions
-10 – 55 °C (operating)
-40 – 70 °C (transport)
20 – 80% RH, non condensing
No shock load or vibration
Mounting
Front panel
Enclosure
IP 65
Display, Accessory
Functions
The display shows P0 or Pc and the control loop status relative to the neutral zone. During normal operation the light-emitting diodes in the display will indicate where regulation is taking place:
• Highest + second highest: ++Zone
• Second highest: Zone
• None: Neutral zone
• Second lowest: –Zone
• Lowest + second lowest: – – Zone
When the display shows the evaporation pressure the condensation pressure can be shown briey by pressing the lowermost key.
Product specication
Technical data
Table 1: Technical data
© Danfoss | Climate Solutions | 2021.03 AI000086415223en-000201 | 2