Installation guide
ELIMINATOR® Hermetic bi-flow filter drier
Types DMB and DCB
Refrigerants:
A1: R134a, R404A, R407C, R507, R22, R410A.
A2L: R32, R444B, R452B, R454B, R1234yf.
023R9532
A3: R290, R600a
For other refrigerants, please contact Danfoss representative.
Only solder versions (cu-plated / pure copper) and connection sizes
below 25mm are approved for A3 refrigerants.
Only connection sizes below 25 mm are approved for A2L.
Temperature range:
-40 – 70 °C
-40 – 160 °F
Max. working pressure:
PS / MWP = 46 bar / 667 psig
023R9532
Installation
Indoor coil
DMB/DCB
TGE
STF
Outdoor coil
Soldering
Min.5% Ag
Danfoss
23Z7016.10
After charging, mark the system with the refrigerant and the oil
used.
Customer best practice will still be needed:
• Use wet wrap when installing.
• Braze the joints.
• Let them cool down.
• Clean the brazing /welding area after the installation (remove
remaining flux with a brush).
• This is an important operation and needs to be done with
great care to remove all remaining flux.
• Paint / Anti-corrosive needs to cover all open steel parts, areas
where the black original paint has been burnt due to brazing
and at least 3 cm approx of the copper.
• Paint the joints twice.
Danfoss
23Z 7016.10
Mounting
Danfoss
23Z 7013.10
Danfoss
© Danfoss | Climate Solutions | 2021.11
23Z7015.10
Danfoss
23Z 7015.10
Danfoss
AN142486435382en-000501 | 1