Danfoss Distribution Systems Fact sheet

Fact sheet
Distribution Systems
Prefabricated solutions for floor heating. Plug & Play construction, which required minimum space and minimum time for installation.
GTZC
GC
Application
The Danfoss distribution systems are pre­fabricated solutions for floor heating, which can be installed separately or be imple­mented with the Danfoss flat station range, in connection with a boiler or as an exten­sion of an existing heating system. These solutions make it easier for the install­er to order a ready-made plug & play con­struction for mounting of distribution pipes for the building section.
The systems are available as standard solu­tions with 3 to 14 connections. In addition the solutions include a flow meter to main­tain the designated flow rate.
Solution GTZC also includes a shunt with a circulation pump as well as a Danfoss FTC self-acting thermostat for control of the supply temperature as well as. The solutions GC and GTZC are fitted with a hard-wired master controller for control of the floor heating system.
For solution GTZC an electric safety thermo­stat, in combination with a zone valve with actuator, ensures maximum temperature limitation in the floor heating circuit, and protects the floor heating circuit from over­heating. The built-in zone valve, in combina­tion with the thermal actuator and a room thermostat (not part of the deliv­ery), enables a comfortable and energy-
efficient control of heating times.
The distribution systems are available as built-in variants with a recess box as an op­tion, or as surface mounted variants with a white cover as an option. Recess boxes for built-in variants are avail­able in two variants, - in width 610 mm for built-in variants with up to 7 connections, in width 850 mm for built-in variants with up to 12 connections and in width 1000 mm for built-in variants with up to 14 connections.
Description
Type G: Distribution system for floor heating without shunt, with flow meter. This variant is available with 3 to 14 connections.
Type GC: Distribution system for floor he­ating without shunt, with flow meter and with hard-wired Master controller FH-WC as standard. This variant is avail­able with 3 to 14 connections.
Type GTZC: Distribution system for floor heating with integrated shunt with circula­tion pump, with flow meter, zone valve and FTC thermostat for control of supply tem­perature. With hard-wired Master controller FH-WC as standard. This variant is available with 3 to 14 connections.
Flexible solutions
The Danfoss distribution systems are pre­pared for implementation with the Danfoss flat station ranges EvoFlat MSS, EvoFlat FSS, Akva Lux II S-F and Akva Lux II TDP-F.
For more information about implemen­tation with the Danfoss flat station range please refer to the relevant product sheets for the respective flat stations.
FEATURES AND BENEFITS
• Minimum space required for installation
• Minimum time required for installation
• Plug & Play construction
• Exact setting of the flow rate per circuit by means of presettable valve RA-C
• Flexible - prepared for implementation with the Danfoss flat station range
www.danfoss.com
SECTION
C-C
D
C
B
A
87
6
5
4
3
2
E
D
C
B
A
87
6
5
4
3
CIRCUIT DIAGRAM  EXAMPLE
HE Supply
HE Return
GTZC
HE Supply
HE Return
Technical parameters:
Nominal pressure: PN 10 DH supply temperature: T
max
= 90°C
Weight: 20-30 kg
(incl. packing)
Electrical supply: 230 V AC
GC
Dimensions (mm):
H 600 x W
1000 x D 150
(max.)
W 600 = Max. 7 connections W 850 = Max. 12 connections W 1000 = Max. 14 connections
Connections sizes:
Flat station: G ¾” (IT) HE: G ¾”
6 Non-return valve 10 Circulation pump Wilo Yonos 15/6-130 230V 19 Tapping point with manual air valve 25 Electrical junction box 33 Thermostat Danfoss RA-C/FTC 15-50°C 43 Connection for radiator 52 Zone valve VMT/TWA-V 57 Safety thermostat 58 Manifold w. 7 connecting pieces 90 Wireless Hydronic controller 90A Thermo -actuator Danfoss TWA-A 24 V
Options:
• Pipe set for high temperature connection
• Room thermostat
• Recess box (for built-in variant)
Recess box for built-in variant
Flat station with distribution system - recess mounted variant
665 610
1300
1382,5
85
128
31 110 50 65 65 65 65
165
150
Min.1355
45
90
130
634,5
147,5 145
Flat station with distribution system - surface mounted variant
350
75 130
24
65 65 65 65
180
555
44
89
129
697
1301
604
78 145
160
© Danfoss | DHS-SRMT/ PL | 2018 . 02
VL.IE.R3.02
Loading...