Danfoss DCL 01.5s, DCL 03s, DCL 05s Data sheet

Data sheet
Filter drier with access port
Product type DCL 01.5s, DCL 03s and DCL 05s
All ELIMINATOR® driers have a solid core with binding material held to an absolute minimum.
The ELIMINATOR® core type DCL contain 80% Molecular Sieve with 20% activated alumina.
The ELIMINATOR® type DCL driers are designed for applications requiring high moisture capacity and acid adsorption capacity.
The integrated access port provides an additional point to diagnose issues or charge the system.
Available with solder (pure copper) connections. For other connections please contact your Danfoss Sales Representative.
Features The Core type DCL
• 80% 3Å Molecular Sieve with 20% activated alumina
• Perfect core blend for systems that operate at high condensing temperatures and require high drying capacity
• Recommended for use with R22, R32, R134a, R404A, R410A, R407C, R23, R600, R600a, R1234yf, R1234ze, R407F, R290, R452A, R444B, R449A, R448A, R450A, R507.
For other refrigerants, please contact Danfoss.
• Compatible with the oil types Mineral or AB, POE or PAG without additives.
© Danfoss | DCS (sw) | 2016.11
The Shell
• UL approved for MWP 667 psig.
• Available with solder (pure copper) connections.
• Outlet connector: 2.8 mm for capillary tube, or can be trimmed for ¼ inch.
• Corrosion resistant powder-painted nish. Special coating for marine applications available upon request.
• Allows installation with any orientation provided the arrow is in the ow direction.
• Available in sizes 1.5 - 5 cubic inches.
The Filter
• 25 μm (0.001 in.) lter provides high retention. with minimal pressure drop.
• Thermally stable up to 250 °F.
DKRCC.PD.EB0.C1.22 | 1
Data sheet | Filter drier with access port, type DCL 01.5s, DCL 03s and DCL 05s
Danfoss
R64-3043.
Approvals
Application
UL US, le no. SA 6398 PED 97/23/EC - a3p3 Compliant with ATEX hazard zone 2
ELIMINATOR® hermetic lter driers protect refrigeration and air-conditioning systems from moisture, acids, and solid particles.
Access port for service
DCL
With these contaminants eliminated, systems are safer from harmful chemical reactions and from abrasive impurities.
ERC
11
Technical data
Solder connection (pure copper)
Refrigerants: R22, R32, R134a, R404A, R410A, R407C, R23, R600, R600a, R1234yf, R1234ze, R407F, R290, R452A, R444B, R449A, R448A, R450A, R507. For other refrigerants, please contact Danfoss.
This product is approved for R32 by ignition source assessment in accordance to standard EN13463-1.
Surface and volume
Solid core
Filter
DCL 1.52/CAPsV 7.2 1.5 1.7 1.21 DCL 032/CAPsV 13.0 3.0 2.7 1.28 DCL 052/CAPsV 15.0 4.0 4.0 1.72
Acid capacity
Filter
DCL 1.52/CAPsV 0.01 DCL 032/CAPsV 0.02 DCL 052/CAPsV 0.03
1
) Adsorption capacity of oleic acid at 0.05
TAN (Total Acid Number)
surface
[in2] [in3] [. oz.] [. oz.]
Acid capacity 1)
[oz.]
Maximum working pressure and allowable temperature
Filter size
[in3] [psig] [°F]
DCL1.5 DCL 03 DCL 05
Solid core
volume
Connection
type
Solder pure
copper
Filter drier volume
(shell volume)
Connection
Inlet Outlet
1
4 inch ODF
2.8 mm ODM /
1
4 inch ODF
Filter drier volume
(net. volume)
Max. working
pressure MWP
667
Temperature
range
-40 – 160
© Danfoss | DCS (sw) | 2016.11
DKRCC.PD.EB0.C1.22 | 2
Data sheet | Filter drier with access port, type DCL 01.5s, DCL 03s and DCL 05s
Technical data and capacities
Drying and liquid capacity
Drying capacity [lb] refrigerant 1) Liquid capacity [TR] 2)
Type
DCL 1.52/CAPsV 5.2 4.8 5.5 5.2 5.7 5.1 5.3 4.9 5.1 4.7 4.7 4.2 4.8 4.2 1.0 0.7 0.7 1.1 1.0 1.0 1.5 DCL 1.52sV 5.2 4.8 5.5 5.2 5.7 5.1 5.3 4.9 5.1 4.7 4.7 4.2 4.8 4.2 1.4 1.0 1.0 1.6 1.5 1.5 2.2 DCL 032/CAPsV 8.4 7.7 8.8 8.3 9.2 8.3 8.5 7.8 8.2 7.6 7.6 6.8 7.7 6.8 1.2 0.8 0.8 1.3 1.2 1.2 1.8 DCL 032sV 8.4 7.7 8.8 8.3 9.2 8.3 8.5 7.8 8.2 7.6 7.6 6.8 7.7 6.8 1.6 1.2 1.1 1.8 1.7 1.7 2.5 DCL 052/CAPsV 13.5 12.4 14.1 13.4 14.8 13.3 13.6 12.5 13.1 12.1 12.3 10.9 12.3 10.9 1.2 0.8 0.8 1.3 1.2 1.2 1.8 DCL 052sV 13.5 12.4 14.1 13.4 14.8 13.3 13.6 12.5 13.1 12.1 12.3 10.9 12.3 10.9 1.7 1.2 1.2 1.9 1.8 1.8 2.6
1
) Drying capacity is based on following moisture content test standards before and after drying:
– R32: 990 ppm W - 50 ppm W – R134a: 1050 ppm W – 50 ppm W – R404A, R507: 1020 ppm W – 50 ppm W – R407C: 1020 ppm W – 50 ppm W – R410A: 1050 ppm W – 50 ppm W – R22: 1050 ppm W – 60 ppm W
in accordance with ARI 710-2004
2
) Given in accordance with ARI 710-2004 for
– t
= 5 °F
e
– t
= 85 °F
c
– Δp = 1 psi
For technical data on other refrigerants, please contact your Danfoss Sales Representative
R134a R404A R507 R22 R407C R410A R32
R134a R404A R507 R22 R407C R410A R32[°F]
75 125 75 125 75 125 75 125 75 125 75 125 75 125
Conversions
Ordering
Drops of water =
(lbs of refrigerant × (Initial PPM of water - Final PPM of water))
110
See ARI standard 710-2004 for recommended initial and nal PPM values for dierent refrigerants
Type DCL Solder (copper)
Type
DCL 1.52/CAPsV
DCL 032/CAPsV
DCL 052/CAPsV
Inlet connection Outlet connection Multi pack
[inch] [inch] [mm] Code no. Qty.
1
4
1
4
1
4
1
4
1
4
1
4
2.8 023Z8261 32
2.8 023Z5174 32
2.8 023Z5181 24
© Danfoss | DCS (sw) | 2016.11
DKRCC.PD.EB0.C1.22 | 3
Data sheet | Filter drier with access port, type DCL 01.5s, DCL 03s and DCL 05s
Design / Function
1. Inlet
2. Access port (Schrader valve)
3. Spring
4. Solid core
5. Polyester mat
6. Perforated plate
7. Outlet
DCL 1.5s
1
DCL 05s
1
DCL 03s
1 654
6
4
32 7
2
3
5
4
5
6
7
2 7
3
The relatively large diameter of the hermetic lter drier means that the liquid ow velocity is suitably low and the pressure drop minimal.
Powder formation is eliminated because the solid core grains are bonded and cannot move against each other.
Identication
Type codes
Type Codes Description Filter drier D Drier Solid core C 80% Molecular Sieve / 20% activated alumina Application L Liquid line
1.5 1.5 in
Size (volume)
Connection (lter connection in 1/8 of an inch increments)
Connection type s Solder connection (pure copper) Access valve V Schradervalve
03 3 in 05 5 in
CAP 2.8 mm
2
2.5 3 4
1
4 in.
5
16 in.
3
8 in.
1
2 in.
3
3
3
Example for type codes
D C L 05 2 CAP s V
Filter drier
Solid core
Application
Size (volume)
Access valve
Connection size
Connection type
© Danfoss | DCS (sw) | 2016.11
Connection (lter connection
8 of an inch increments)
1
in
DKRCC.PD.EB0.C1.22 | 4
Data sheet | Filter drier with access port, type DCL 01.5s, DCL 03s and DCL 05s
Selection example
Select the appropriate type (DCL) based on refrigerant and oil type. Then select the drier size based on the liquid and adsorption capacity required.
a. Cooling capacity: Qe = 0.25 TR To obtain a mass ow corresponding to 0.25 TR
cooling capacity with a DCL 1.52/CAPsV lter drier.
b. Amount of charge: 1 lbs R134a at tL = 75 °F To dry 1 lbs R134a at 75 °F from 1050 to 50 ppm moisture, a DCL 1.52/CAPsV is necessary.
c. Result
DCL 1.52/CAPsV can be used If a bigger lter is used, the increase of drying capacity protects the system in better way.
Drying and liquid capacity
Drying capacity [lb] refrigerant 1) Liquid capacity [TR] 2)
Type
DCL 1.52/CAPsV 5.2 4.8 5.5 5.2 5.7 5.1 5.3 4.9 5.1 4.7 4.7 4.2 4.8 4.2 1.0 0.7 0.7 1.1 1.0 1.0 1.5 DCL 1.52sV 5.2 4.8 5.5 5.2 5.7 5.1 5.3 4.9 5.1 4.7 4.7 4.2 4.8 4.2 1.4 1.0 1.0 1.6 1.5 1.5 2.2 DCL 032/CAPsV 8.4 7.7 8.8 8.3 9.2 8.3 8.5 7.8 8.2 7.6 7.6 6.8 7.7 6.8 1.2 0.8 0.8 1.3 1.2 1.2 1.8 DCL 032sV 8.4 7.7 8.8 8.3 9.2 8.3 8.5 7.8 8.2 7.6 7.6 6.8 7.7 6.8 1.6 1.2 1.1 1.8 1.7 1.7 2.5 DCL 052/CAPsV 13.5 12.4 14.1 13.4 14.8 13.3 13.6 12.5 13.1 12.1 12.3 10.9 12.3 10.9 1.2 0.8 0.8 1.3 1.2 1.2 1.8 DCL 052sV 13.5 12.4 14.1 13.4 14.8 13.3 13.6 12.5 13.1 12.1 12.3 10.9 12.3 10.9 1.7 1.2 1.2 1.9 1.8 1.8 2.6
1
) Drying capacity is based on following moisture content test standards before and after drying:
– R32: 990 ppm W - 50 ppm W – R134a: 1050 ppm W – 50 ppm W – R404A, R507: 1020 ppm W – 50 ppm W – R407C: 1020 ppm W – 50 ppm W – R410A: 1050 ppm W – 50 ppm W – R22: 1050 ppm W – 60 ppm W
in accordance with ARI 710-2004
2
) Given in accordance with ARI 710-2004 for
– t
= 5 °F
e
– t
= 85 °F
c
– Δp = 1 psi
For technical data on other refrigerants, please contact your Danfoss Sales Representative
R134a R404A R507 R22 R407C R410A R32
R134a R404A R507 R22 R407C R410A R32[°F]
75 125 75 125 75 125 75 125 75 125 75 125 75 125
© Danfoss | DCS (sw) | 2016.11
DKRCC.PD.EB0.C1.22 | 5
Danf already on order pro All trademarks in this material are property of the respec
Dimensions and weights
2
9
.
3 mm
Valve body for
Valve body for
27.92 mm
Valve body for
36.59 mm
1/4 in ODF solder connector
(1.153 in)
Schader Valve
Ø43 mm
(1.67 in)
DCL 1.52/CAPsV / DCL 1.52sV
Recommended cut for 1/4 in ODF use
16 mm
(0.630 in)
2.8mm ODF Solder connector
6.35 mm
Ø
(0.250 in)
(0.276 in)
Weight 0.15 kg / 0.34 lb
1/4 in ODF solder connector
(1.099 in)
Ø6.35 mm (0.25 in)
7 mm (0.276 in)
Weight 0.19 kg / 0.42 lb
7 mm
16 mm (0.63 in)
16 mm
(0.63 in)
Schader Valve
47.5 mm
(1.87 in)
66 mm (2.598 in)
112 mm (4.409 in)
93.5 mm
(3.681 in)
Ø43 mm
6.35 mm
Ø
(0.25 in)
Min. 4.7 mm
(0.185 in)
Danfoss 23Z85.10
2.8 mm
Ø
(0.11 in)
(1.811 in)
Ø46 mm
DCL 032/CAPsV / DCL 032sV
Recommended cut
Ø6.35 (0.25 in)
for 1/4 in ODF use
2.8 mm ODF Solder connector
Min. 4.7 mm (0.85 in)
Danfoss 23Z86.10
Ø2.8 mm (0.11 in)
Ø46 mm
(1.811 in)
16 mm
(1.693 in)
(0.63 in)
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
vided that such alterations can be made without subsequential changes being necessary eady agreed.
© Danfoss | DCS (sw) | 2016.11
Schader Valve
1/4 in ODF solder connector
(1.441 in)
Ø53.5 mm
(2.106 in)
Ø6.35 mm (0.25 in)
7 mm (0.276 in)
16 mm (0.63 in)
75.1 mm (2.957 in)
121.1 mm (4.768 in)
Weight 0.27 kg / 0.60 lb
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
DCL 052/CAPsV / DCL 052sV
Recommended cut for 1/4 in ODF use
16 mm (0.63 in)
2.8mm ODF Solder connector
Min. 4.7 mm (0.185 in)
Ø6.35 mm (0.25 in)
Danfoss 23Z87.10
Ø2.8 mm (0.11 in)
DKRCC.PD.EB0.C1.22 | 6
57.5 mm
(2.264 in)