Danfoss DCL Installation guide

Installation guide
Danfoss
23Z92
023R9521
023R9521
ELIMINATOR® Hermetic filter driers Type DCL with access port
Refrigerants:
R22, R23, R32, R1234yf, R1234ze, R134a, R404A, R407A, R407C, R407F, R410A, R444B, R448A,
023R9521
Media Temperature range: -40 °C – 70 °C / -40 °F – 160 °F
023R9521
Connection
type
Solder pure copper 1.5, 03, 05
Core size
[cu inch]
Conn. size
inlet
¼ inch ODF
¼ – 3/8 ODF ¼ – 3/8 ODF
Application Installation
Accessory bag
Remove Schrader valve before brazing.
Converting from capillary tube outlet
2.8 mm to ¼ inch
Conn. size
outlet
2.8 mm ODF / ¼ inch ODF
<50 °C (122 °F)
PS/MWP
46 bar / 667 psig
Min 5% Ag
Min. 5% Ag
1
Max. 70 °C / 160 °F
Danfoss
0.5 Nm (5 in.-lbs)
2
23Z88.10
Danfoss
23Z89.10
After charging, mark the system with the refrigerant and the oil type used.
© Danfoss | Climate Solutions (nb) | 2021.06
Cutting line
1.5 Nm (13 in.-lbs)
Danfoss
23Z93
If any paint is burnt off during the brazing process then clean the area and protect it with an anti-corrosion paint or heat shrink.
AN217986428752en-000301 | 1
Loading...