Instructions
70
65
60
SH 11K
55
50
45
40
35
30
25
20
-30 -20 -15-25 -10 -5 50 10 15
Condensing Temperature (°C)
Evaporating Temperature (°C)
70
65
60
SH 5K
SH 11K
HCJ120 & HCJ121
55
50
45
40
35
30
25
20
-30 -20 -15-25 -10 -5 50 10 15
Condensing Temperature (°C)
Evaporating Temperature (°C)
70
65
60
SH 11K
55
50
45
40
35
30
25
20
-30 -20 -15-25 -10 -5 50 10 15
Condensing Temperature (°C)
Evaporating Temperature (°C)
SH 5K
SH 10K
70
65
60
55
50
45
40
35
30
25
20
Condensing Temperature (°C)
-30 -20 -15-25 -10 -5 50 10 15
Evaporating Temperature (°C)
10
15
20
25
30
35
40
45
50
55
60
65
70
-35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25
Condensing temperature (℃)
Evaporating temperature (℃)
SH5K
Danfoss scroll compressors
DCJ / H series
1 – Introduction
These instructions pertain to the Danfoss scroll compressors used for HVAC systems. They provide
necessary information regarding safety and proper usage of this product.
2 – Nameplate
3 - Operating map
DCJ (R410A)
4 - Electrical connections
HRH/HLH/HLJ/HCJ Model variation T (R410A)
A: Model number
B: Serial Number
C: Manufacturing year
D: Internal protection
E: Supply voltage range
F: Locked rotor current
Maximum operating current
G: Lubricant type and nominal charge
H: Approved Refrigerant
Single pack
PSC wiring
C
Line
S
Run
Capacitor
HRM/HLM/HCM - HRH/HL H/HLJ/HCJ
Model variation U (R22 / R410A)
HRM/HLM/HCM-HRP/HLP/HCP Model variation T
(R22/407C)
HHP (R407C)
When HRM compressors are used with R417A, the factory
charged oil must be replaced by PVE oil 320HV (120Z5034).
Quick connect spade terminals
P & T terminal box type
C
T₁
R
T₃
C
S
S
T₂
Line
R
2
Run
Capacitor
CSR wiring
5
Potential
Relay
1
Start
Capacitor
5 - Connections size
R
Ring connect screw terminals
C & Q terminal box type
push
push
push
Brazed connection Rotolock connection
Models
HRM032-042
HRP034-042
HRM/HRP045-047
HRH029-040
HRM/HRP048-060
HLM/HLP068-075
HRH041-056
HLH061-068
HLJ061-068
HLM/HLP078-081
HCM/HCP094-120
HCJ090-121
DCJ091-121
Connec.
size
Suction
3/4"
Disch. 1/2"
Suction
7/8"
Disch. 1/2"
Suction
7/8"
Disch. 3/4"
Suct. 1"1/8
Disch. 7/8"
Models
- -
HRH044-
056
HLH061-
068
HLJ072-083
- -
- -
Connec.
size
Suct. 1"1/4
Disch. 1"
Installation and servicing of the compressor by qualied personnel only. Follow these
instructions and sound refrigeration engineering practice relating to installation,
commissioning, maintenance and service.
The compressor must only be
used for its designed purpose(s)
and within its scope of application
(refer to «operating limits»). Consult
Application guidelines and datasheet
available from cc.danfoss.com
The compressor is delivered under nitrogen gas pressure
(between 0.3 and 0.4 bar / 4 and 6 psi). Do not disassemble
bolts, plugs, ttings, etc... unless all pressure has been
relieved from the compressor.
Never operate
compressor without
terminal box cover in
place and secured.
Under all circumstances, the
EN378 (or other applicable local
safety regulation) requirements
must be fullled.
Wear protective goggles and
work gloves.
The compressor must be handled
with caution in the vertical
position (maximum oset from
the vertical : 15°).
© Danfoss | DCS (CC) | 2016.01AN146886422104en-000501
6 – Handling and storage
Handle the compressor with care. Use the dedicated
•
handles in the packaging. Use the compressor lifting
lug and use appropriate and safe lifting equipment.
• Store and transport the compressor in an upright
position.
• Store the compressor between -35°C and 70°C
(31°F and 158°F).
• Don’t expose the compressor and the
packaging to rain or corrosive atmosphere.
7 – Safety measures before assembly
Never use the compressor in a ammable
atmosphere.
• Mount the compressor on a horizontal at
surface with less than 7° slope.
Verify that the power supply corresponds to the
•
compressor motor characteristics (see nameplate).
• When installing a compressor model, use
equipment specically reserved for HFC
refrigerants which was never used for CFC or
HCFC refrigerants.
• Use clean and dehydrated refrigeration-grade
copper tubes and silver alloy brazing material.
• Use clean and dehydrated system components.
The piping connected to the compressor must be
•
exible in 3 dimensions to dampen vibrations.
•
The compressor must always be mounted with the
rubber grommets supplied with the compressor.
8 – Assembly
• Slowly release the nitrogen holding charge
through discharge and suction ports.
• Connect the compressor to the system as soon
as possible to avoid oil contamination from
ambient moisture.
Avoid material entering into the system while cutting
•
tubes. Never drill holes where burrs cannot be
removed.
•
Braze with great care using state-of-the-art
technique and vent piping with nitrogen gas ow.
• Connect the required safety and control devices.
When the schrader port, if any, is used for this,
remove the internal valve.
• For parallel assemblies of the compressors in
version C8, contact Danfoss.
9 – Leak detection
Never pressurize the circuit with oxygen or dry
air. This could cause re or explosion.
• Do not use leak detection dye.
Perform a leak detection test on the complete
•
system.
• The low side test pressure must not exceed 31
bar /450 psi.
• When a leak is discovered, repair the leak and
repeat the leak detection.
10 – Vacuum dehydration
• Never use the compressor to evacuate the
system.
Connect a vacuum pump to both the LP & HP sides.
•
• Pull down the system under a vacuum of 500 µm
Hg (0.67 mbar) / 0.02 inch Hg absolute.
• Do not use a megohmmeter nor apply power to
the compressor while it is under vacuum as this
may cause internal damage.
11 – Electrical connections
• Switch o and isolate the main power supply.
All electrical components must be selected as per
•
local standards and compressor requirements.
• Refer to page 1 for electrical connections
details.For three phase applications, the
terminals are labeled T1, T2, and T3. For singlephase applications the terminals are labeled C
(common), S (start), and R (run).
• Danfoss scroll compressors will only compress
gas while rotating counter-clockwise (when
viewed from the compressor top). Since
single-phase motors will start and run in only
one direction, reverse rotation is not a major
consideration. Three-phase motors, however,
Danfoss A/S, 6430 Nordborg, Denmark
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
AN146886422104en-000501
will start and run in either direction, depending
on the phase angles of the supplied power. Care
must be taken during installation to ensure that
the compressor operates in the correct direction.
Use ø 4.8 mm / #10 - 32 screws and ¼” ring
•
terminals for the power connection with ring
connect screw terminal (C type). Fasten with 3
Nm torque.
• Use ø 6.3 mm tabs for quick connect spade
terminals (P type).
• Use a self tapping screw to connect the
compressor to earth.
12 – Filling the system
• Keep the compressor switched o.
• Keep the refrigerant charge below the indicated
charge limits if possible. Above this limit; protect
the compressor against liquid ood-back with a
pump-down cycle or suction line accumulator.
Never leave the lling cylinder connected to the
•
circuit.
Compressor models
HRM032-034-038-040-042-045-047
HRP034-038-040-042-045-047 /
HHP015-019-021-026 /
HRH031-032-034-036-038-040
HRM048-051-054-058-060 /
HLM068-072-075-078-081 /
HRP048-051-054-058-060 /
HLP068-072-075-081 /
HHP030-038-045 /
HRH044-049-051-054-056 /
HLH061-068 - HLJ072-083
HCM094-109-120 /
HCP094-109-120 /
HCJ090-091-105-106-120-121 /
DCJ091-106-121
Refrigerant
charge limit
3.6 kg / 8 lb
5.4 kg / 12 lb
7.2 kg / 16 lb
13 – Verification before commissioning
Use safety devices such as safety pressure
switch and mechanical relief valve in compliance
with both generally and locally applicable
regulations and safety standards. Ensure that
they are operational and properly set.
Check that the settings of high-pressure
switches don’t exceed the maximum service
pressure of any system component.
• A low-pressure switch is recommended to avoid
low pressure operation.
Minimum setting for R22
Minimum setting for R407C
Minimum setting for R410A 2.5bar (absolute)/36 psia
•
Verify that all electrical connections are properly
fastened and in compliance with local regulations.
• When a crankcase heater is required, it must be
1.5bar (absolute)/22 psia
energized at least 24 hours before initial start-up
and start-up after prolonged shutdown.
• Please respect a 90 Nm ± 20 Nm for tightening
torque of all rotolock nut.
14 – Start-up
• Never start the compressor when no refrigerant
is charged.
• Do not provide any power to the compresor
unless suction and discharge service valves are
open, if installed.
Energize the compressor. It must start promptly.
•
If the compressor does not start, check wiring
conformity and voltage on terminals.
•
Eventual reverse rotation can be detected by
following phenomena; the excessive noise,
no pressure dierential between suction and
discharge, and line warming rather than immediate
cooling. A service technician should be present at
initial start-up to verify that supply power is properly
phased and that the compressor is rotating in the
correct direction. H-series Scroll compressors are
designed to operate for a maximum of 150 hours
in reverse, but as a reverse rotation situation can go
unnoticed for longer periods, phase monitors are
recommended. For compressors HLM078, HLP081,
HLJ083 and larger, phase monitors are required
for all applications. Danfoss recommends phase
protection for residential compressors.
• If the internal overload protector trips out, it must
cool down to 60°C / 140°F to reset. Depending on
ambient temperature, this may take up to several
hours.
15 – Check with running compressor
Check current draw and voltage. Measurement
of amps and volts during running conditions must
be taken at other points in the power supply, not
in the compressor electrical box.
•
Check suction superheat to reduce risk of slugging.
• Observe the oil level in the sight glass (if
provided) for about 60 minutes to ensure proper
oil return to the compressor.
• Respect the operating limits.
Check all tubes for abnormal vibration.
•
Movements in excess of 1.5 mm / 0.06 in require
corrective measures such as tube brackets.
•
When needed, additional refrigerant in liquid phase
may be added in the low-pressure side as far as
possible from the compressor. The compressor
must be operating during this process.
• Do not overcharge the system.
• Never release refrigerant to atmosphere.
• Before leaving the installation site, carry out
a general installation inspection regarding
cleanliness, noise and leak detection.
• Record type and amount of refrigerant charge
as well as operating conditions as a reference for
future inspections.
16 – Maintenance
Internal pressure and surface temperature
are dangerous and may cause permanent injury.
Maintenance operators and installers require
appropriate skills and tools. Tubing temperature may
exceed 100°C / 212°F and can cause severe burns.
Ensure that periodic service inspections to
ensure system reliability and as required by local
regulations are performed.
To prevent system related compressor problems,
following periodic maintenance is recommended:
• Verify that safety devices are operational and
properly set.
• Ensure that the system is leak tight.
• Check the compressor current draw.
• Conrm that the system is operating in a way
consistent with previous maintenance records
and ambient conditions.
• Check that all electrical connections are still
adequately fastened.
• Keep the compressor clean and verify the
absence of rust and oxidation on the compressor
shell, tubes and electrical connections.
• Acid / moisture content in system and oil should
be checked regularly.
17 - Warranty
Always transmit the model number and serial
number with any claim led regarding this product.
The product warranty may be void in following
cases:
• Absence of nameplate.
• External modications; in particular, drilling,
welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
• Rust, water or leak detection dye inside the
compressor.
• Use of a refrigerant or lubricant not approved by
Danfoss.
• Any deviation from recommended instructions
pertaining to installation, application or
maintenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• No model number or serial number transmitted
with the warranty claim.
14 – Disposal
Danfoss recommends that compressors
and compressor oil should be recycled
by a suitable company at its site.
© Danfoss | DCS (CC) | 2016.01