Danfoss Colibri ETS 12C, Colibri ETS 24C, Colibri ETS 50C, Colibri ETS 100C, Colibri ETS 25C Installation Manual

...
ENGINEERING
TOMORROW
Installation guide
Colibri® Electric Expansion Valves
Type ETS 12C, ETS 24C, ETS 25C, ETS 50C, ETS 100C Colibri® Electric Regulating Valves
Type KVS 2C, KVS 3C KVS 5C
034R9806
© Danfoss | DCS (sw) | 2018.01
DKRCC.PI.VD1.F6.ML | 1
Danfoss R64-3051.10
Danf
oss
R
64-3051.1
0
Place the valve close to the evaporator.
It is recommended to use Danfoss filter drier before the expansion valve or a strainer for particles of 150 micron or smaller.
Application ETS Colibri®
Flow direction
Allowable ambient temperature:
Min. -40 °C / -40 °F Max. 70 °C / 158 °F
Max. working pressure:
50 bar(g) / 725 psi(g)
Refrigerants : R410A, R404A, R507, R134a, R407A, R407B, R407C, R407F, R32, R290, R1234ze, R1234yf, R449A, R449B, R452A, R1270, R600, R600a, R22, R23, R227, R417A, R444B, R447A, R448A, R454B, R422A, R422D, R427A, R502, R513A, R413A, R438A, R450A, R455B, R454C, R454A, R452B and *L40
*R-number allocation by ASHRAE is pending
Fluid temperature:
Min. -40 °C / -40 °F Max. 70 °C / 158 °F
Total steps:
600 full steps
Phase current:
800 mA peak / 600 mA RMS
Coil resistance:
10 Ω (20 °C / 68 °F)
Stepper motor type:
Bipolar
Do not connect directly to AC/DC power source. Connect valve to appropriate controller/driver only.
ETS / KVS Colibri® valves are delivered in open position, ready for brazing. An AST –g service driver is available for manual operation / service of ETS / KVS Colibri® valves.
English
Bi-flow
Reverse flow
Normal flow (Using sight glass for flash gas detection - ETS 25C to ETS 100C) KVS Colibri® valves have no sight glass integrated
Danfoss 34G231.10
Application KVS Colibri®
ETS Colibri®
KVS Colibri®
NormalReverse
GREEN: DRY
YELLOW: WET
Danfoss
34G136.12
MADE IN DENMARK
ETS XXXC
10 Ω, 800mA peak
N0311A
Colibri® Electric Expansion valve
-40/+70°C / -40/+158°F
PS 50bar / MWP 735psig
034GXXXX
NormalReverse
Danfoss
34G156.12
MADE IN DENMARK
ETS XXXC
10 Ω, 800mA peak
N0311A
Colibri® Electric Expansion valve
-40/+70°C / -40/+158°F
PS 50bar / MWP 735psig
034GXXXX
© Danfoss | DCS (sw) | 2018.01
DKRCC.PI.VD1.F6.ML | 2
Danfoss 34G58.15
2
1
oss
B1
B2
A1
A2
Danfoss
34G152.10
1
2
Danfoss
34G153.11
MADE IN DENMARK
ETS XXXC
10 Ω, 800mA peak
N0311A
Colibri® Electric Expansion valve
-40/+70°C / -40/+158°F
PS 50bar / MWP 735psig
034GXXXX
Danfoss
34G60..16
+90°
-90°
Danfoss
34G59.11
Brazing
Motor coil resistance check.
Coil A = Coil B = 10 Ω (20 °C / 68 °F)
Min. 5 % Ag
Mounting
N2 gas from opposite site of soldering point.
Max. 30 sec.
Max. 15 sec.
M12 Connection
N
2
Max. 150 °C
Installation video
Recommended:
Connector Nozzle size
1
/2 inch 2 mm 1/16 inch
5
/8 inch
7
/8 inch 1 1/8 inch 1 3/8 inch 1 5/8 inch 9 mm 3/8 inch
Loading...
+ 4 hidden pages