If the household plumbing system includes hot water recirculation the substation must be connected to the hot water recirculation system
by using this circulation set.
It is to be recommended to prepare the substation for recirculation BEFORE mounting it on the wall.
The recirculation pipe in your household plumbing system must be connected to a nipple, mounted on the circulation pipe of the substation. - See following pages information about preparation of substation for and connection to the DHW recirculation system.
Remember always to mount circulation pump, non-return valve on the circulation pipe and to mount safety valve on the DCW inlet.
The pump must be installed so that the pump is pumping water towards the substation.
If a time-controlled pump is used, it is to be recommended that the circulation water temperature is set to approx. 35 °C.
If the circulation pump (outside the substation) is switched o for a longer period, it is to be recommended that the Danfoss bypass thermostat is closed during the same period.
Div.484 Code No. 004U8403
Div.487 Code No. 004U8405
NOTE!
Please note that substations with Danfoss AVE expanion unit must not be used on systems with DHW recirculation.
German - DE
Wenn eine Zirkulationsleitung in der Hausinstallation vorhanden ist, ist die Station an die Zirkulationsleitung anzuschließen, und eine
Umrüstung von Bypassbetrieb auf TWW-Zirkulation ist mittels dieses Zirkulationssatzes vorzunehmen.
Es wird empfohlen die Station für TWW-Zirkulation VOR der Montage auf der Wand vorzubereiten.
Die Zirkulationsleitung der Hausinstallation ist an einen Messing-Nippel, den auf dem Zirkulationsschlauch der Station montieret ist, anzuschliessen. - Siehe folgende Seiten für weitere Informationen über Zirkulationsanschluss.
Bitte einbau von Umwälzpumpe und Rückschlagventil in der Zirkulationsleitung beachten und Sicherheitsventil in der Kaltwasserzuleitung einzubauen. Die Fleißrichtung der Pumpe ist in Richtung Station.
Wird die Umwälzpumpe über eine Schaltuhr gesteuert, empfehlen wir, dass die Zirkulationswassertemperatur auf ungefähr. 35 °C eingestellt wird.
Wenn die Umwälzpumpe (außerhalb der Station) für einen längeren Zeitraum abgeschaltet wird, wird es empfohlen, dass der Danfoss
Bypass Thermostat im gleichen Zeitraum geschlossen wird.
BITTE BEMERKEN!
Der AVE Druckausgleichventil ist nicht auf Systemen mit TWW-Zirkulation zu verwenden.
You must always t a pump and non-return valve to the recirculation pipe, with ow direction towards the substation.
A safety valve must be mounted in the DCW inlet.
A
E1
F
D
Akva Lux II S-F, Type 004U8325
Akva Lux II S-F, Type 004U8533
Akva Lux II S-F, Type 004U8327
Akva Lux II S-F, Type 004U8543
Akva Lux II S-F, Type 004U8367
Fig. 1
Remove the nipples/plugs from the domestic hot water controller
(use a 6 mm Allen key).
Fig. 2
Mount hexagon nipple A in the DHW controller (pack).
Fig. 3
Fit pipe bushing B in the DHW controller.
Fig. 4
Remove the existing capillary tube and union nut from bypass
thermostat and T-piece (do not re-use).
2
DKDHR VI.IE.B1.5B Danfoss District Energy
Fig. 1Fig. 2
Fig. 3Fig. 4
Installation Guide S-F units
Fig. 5
Plug the hole in the T-piece with the steel ball C and a union nut D.
Fig. 6
Fit new capillary tube E2 in bypass thermostat by means of a cutting
ring F and a union nuts D. Tighten with single end wrench.
Fig. 7
Fit/screw hose end G1 onto the hexagon nipple A and t the other
end of the capillary tube E2 in pipe bushing B by means of a cutting
ring F and a union nut D. Tighten with single end wrench.
Fig. 8
Mount bracket H for recirculation connection on the mounting rail,
as shown, and fasten by means of two screws I.
Fig. 9
Mount non-return valve J and hexagon nipple K in the pump, as
shown in the photo to your right.
Fig. 10
Loosen union nut.
Fig. 11
Turn pump motor head by 180 degrees. Tighten the union nut
again.
Fig. 12
Please note that the arrow on the back of the housing indicates
the dirction of ow. - Please note the position of the arrow as
shown in the photo to your right.
Fig. 5Fig. 6
Fig. 7Fig. 8
J
K
Fig. 9
Fig.10
Fig. 13
Fit pump in bracket H and fasten with locknut L.
Fig. 11Fig.12
Fig. 14
Fit circulation hose end G2 in non-return valve J. (Do not forget
gasket!)
Fig. 13Fig.14
Danfoss District Energy VI.IE.B1.5B DKDHR
33
Installation Guide S-F units
PLEASE NOTE (only for 004U8543):
For systems with DHW recirculation the bypass thermostat
must alway be installed before the heat meter.
On substations, that are supplied with bypass thermostat
mounted after the heat meter (Akva Lux II S-F, Type 004U8543),
the bypass thermostat must therefore be relocated before the
substation is prepared for recirculation, - i.e. the bypass thermostat must be mounted before the heat meter.
Please follow the below instructions:
1.
Start by shutting o all connections to the substation.
2.
First follow the instructions for Fig. 1, 2 and 3 on page 15.
3.
Then demount 3/4” plug in T-piece (pos. A), as illustrated in g. 1.
A
C
D
4.
Remove the existing capillary tube from pos. C to D. See g. 2.
5.
Demount bypass thermostat incl. 3/4” reducer bushing from pos. B.
Unscrew 3/4” reducer bushing from bypass thermostat (the 3/4”
reducer bushing is not to be reused). See g. 3.
6.
Mount bypass thermostat in pos A, as illustrated in g. 4.
7.
Plug the hole in pos. B with 3/4” plug (from pos A) and gasket, as
illustrated in g. 5.
8.
Plug the hole in pos. D with a steel ball and 6 mm union nut, as illustrated in g. 6.
9.
Finally follow instructions for g. 6 to 14 on pages 15 and16.
You must always t a pump and non-return valve to the recirculation pipe, with ow direction towards the substation.
A safety valve must be mounted in the DCW inlet.
A
E1
F
D
Akva Lux II S-F, Type 004U8325
Akva Lux II S-F, Type 004U8533
Akva Lux II S-F, Type 004U8327
Akva Lux II S-F, Type 004U8543
Akva Lux II S-F, Type 004U8367
For recirculation connection please refer to installation instructions
for circulation set 1 - 004U8400.
You must always t a pump and non-return valve to the recirculation pipe, with ow direction towards the substation.
A safety valve must be mounted in the DCW inlet.
Fig. 1
Remove the nipples/plugs from the domestic hot water controller
(use a 6 mm Allen key).
E
F
H
Akva Lux II S-F, Type 004U8325
Akva Lux II S-F, Type 004U8533
Akva Lux II S-F, Type 004U8327
Akva Lux II S-F, Type 004U8543
Fig. 2
Mount hexagon nipple A in the DHW controller (pack), and mount
hexagon nipple C and union nut D in hexagon nipple A (for tting
of recirculation pipe.
Fig. 3
Fit pipe bushing B in the DHW controller.
Fig. 4
Remove the existing capillary tube and union nut from bypass
thermostat and angle piece (do not re-use).
Fig. 5
Plug the hole in the angle piece with steel ball E and union nut F.
Fig. 6
Fit new capillary tube G in bypass thermostat by means of a cutting
ring H and a union nut F. Tighten with single end wrench.
Akva Lux II S-F, Type 004U8637
Fig. 2
Fig. 1
Fig. 3
Fig. 4
6
DKDHR VI.IE.B1.5B Danfoss District Energy
Fig. 5
Installation Guide S-F units
Fig. 6
Fit new capillary tube G in bypass thermostat by means of a cutting
ring H and a union nut F. Tighten with single end wrench.
Fig. 7
Fit the other capillary tube end G in pipe bushing B by means of a
cutting ring H and a union nut F. Tighten with single end wrench.
PLEASE NOTE (only for 004U8543):
For systems with DHW recirculation the bypass thermostat
must alway be installed before the heat meter.
On substations, that are supplied with bypass thermostat
mounted after the heat meter (Akva Lux II S-F, Type 004U8543),
the bypass thermostat must therefore be relocated before the
substation is prepared for recirculation, - i.e. the bypass thermostat must be mounted before the heat meter.
Please follow the below instructions:
1.
Start by shutting o all connections to the substation.
2.
First follow the instructions for Fig. 1, 2 and 3 on page 19.
3.
Then demount 3/4” plug in T-piece (pos. A), as illustrated in g. 1.
4.
Remove the existing capillary tube from pos. C to D. See g. 2.
Fig. 6
Fig. 7
5.
Demount bypass thermostat incl. 3/4” reducer bushing from pos. B.
Unscrew 3/4” reducer bushing from bypass thermostat (the 3/4”
reducer bushing is not to be reused). See g. 3.
6.
Mount bypass thermostat in pos A, as illustrated in g. 4.
7.
Plug the hole in pos. B with 3/4” plug (from pos A) and gasket, as
illustrated in g. 5.
8.
Plug the hole in pos. D with a steel ball and 6 mm union nut, as illustrated in g. 6.
9.
Finally follow above instructions for g. 6 and 7 on pages 19 and
You must always t a pump and non-return valve to the recirculation pipe, with ow direction towards the substation.
A safety valve must be mounted in the DCW inlet.
PLEASE NOTE!
This circulation set can be mounted only on substations without
insulation.
Fig. 1
Remove the nipples/plugs from the domestic hot water controller
(use a 6 mm Allen key).
AB
G
E
F
H
Akva Lux II S-F, Type 004U8325
Akva Lux II S-F, Type 004U8533
Akva Lux II S-F, Type 004U8327
Akva Lux II S-F, Type 004U8543
Fig. 2
Mount hexagon nipple A in the DHW controller (pack).
Fig. 3
Mount circulation pipe C incl. hexagon nipple D in hexagon nipple
A.
Fig. 4
Fit pipe bushing B in the DHW controller.
Fig. 5
Remove the existing capillary tube and union nut from
bypass thermostat and angle piece (do not re-use).
Fig. 6
Plug the hole in the angle piece with ball E and union nut F.
Fig. 1Fig. 2
Fig. 3Fig. 4
Fig. 5Fig. 6
8
DKDHR VI.IE.B1.5B Danfoss District Energy
Installation Guide S-F units
Fig. 7
Fit the new capillary tube G in the bypass thermostat by means of
a cutting ring H and a union nut F. Tighten with single end wrench.
Fig. 8
Fit the other capillary tube end in the pipe bushing by means of a
cutting ring H and a union nut F. Tighten with single end wrench.
PLEASE NOTE (only for 004U8543):
For systems with DHW recirculation the bypass thermostat
must alway be installed before the heat meter.
On substations, that are supplied with bypass thermostat
mounted after the heat meter (Akva Lux II S-F, Type 004U8543),
the bypass thermostat must therefore be relocated before the
substation is prepared for recirculation, - i.e. the bypass thermostat must be mounted before the heat meter.
Fig. 7Fig. 8
Please follow the below instructions:
1.
Start by shutting o all connections to the substation.
2.
First follow the instructions for Fig. 1, 2, 3 and 4 on page 21.
3.
Then demount 3/4” plug in T-piece (pos. A), as illustrated in g. 1.
4.
Remove the existing capillary tube from pos. C to D. See g. 2.
5.
Demount bypass thermostat incl. 3/4” reducer bushing from pos. B.
Unscrew 3/4” reducer bushing from bypass thermostat (the 3/4”
reducer bushing is not to be reused). See g. 3.
6.
Mount bypass thermostat in pos A, as illustrated in g. 4.
7.
Plug the hole in pos. B with 3/4” plug (from pos A) and gasket, as
illustrated in g. 5.
A
Fig. 1Fig. 2
B
Fig. 3Fig. 4
C
D
A
8.
Plug the hole in pos. D with a steel ball and 6 mm union nut, as illustrated in g. 6.
9.
Finally follow above instructions for g. 7 and 8 on this page.